Lopi Cape Cod Wood Stove User manual

Cape Cod
Wood Stove
Owner's Manual
Freestanding Stove
Hearth-Stove Approved
Save these instructions
for future reference
SAFETY NOTICE:
If this appliance is not properly installed, a house fire
may result. For your safety, follow the installation
directions. Contact local building or fire officials about
restrictions and installation inspection requirements
in your area.
Dragon Wholesaling Pty. Ltd.
Unit 4, 16 Lexington Drive
Bella Vista NSW
Australia 2153
Copyright 2014,
Travis Industries, Inc.
$10.00
100-01383
4140402
Tested by:
HRL Technology
Tramway Road, Morwell 3840
Victoria
Tested to: AS/NZS 4012/4013: 1999
Report Number: HCMG/14/017

2 Introduction
© Travis Industries 100-01383 4140402
Introduction
We welcome you as a new owner of a Lopi Cape Cod wood-burning stove. In purchasing a Cape Cod
you have joined the growing ranks of concerned individuals whose selection of an energy system reflects
both a concern for the environment and aesthetics. The Lopi Cape Cod is one of the finest appliances
the world over. This manual will explain the installation, operation, and maintenance of this appliance.
Please familiarize yourself with the Owner's Manual before operating your appliance and save the manual
for future reference. Included are helpful hints and suggestions which will make the installation and
operation of your new appliance an easier and more enjoyable experience. We offer our continual
support and guidance to help you achieve the maximum benefit and enjoyment from your appliance.
Important Information
No other Lopi Cape Cod appliance has the same
serial number as yours. The serial number is
stamped onto the label on the back of the appliance.
This serial number will be needed in case you require
service of any type.
Model: Lopi Cape Cod Stove
Serial Number:
Purchase Date:
Purchased From:

Table of Contents 3
© Travis Industries 100-01383 4140402
Introduction ......................................................2
Important Information......................................2
Installation Options..........................................6
Features ............................................................6
Heating Specifications.....................................6
Dimensions.......................................................6
Emissions / Efficiency.....................................6
Installation Warnings.......................................7
Planning the Installation..................................7
Preparation for Installation....................................7
Packing List......................................................7
Floor Protection Requirements ......................8
Stove Placement Requirements .....................8
Clearances........................................................8
Top View - Straight Installation .............................9
Top View - Corner Installation...............................9
Rear Heat Shield Installation.........................10
Chimney Connector Requirements..............11
Chimney Requirements.................................12
Chimney Termination Requirements ...........13
Outside Air Requirements.............................13
Standard Ceiling with a Factory-Built Chimney...14
Cathedral Ceiling with a Factory-Built Chimney..14
Exterior Factory-Built Chimney ...........................15
Wall Penetrations Under 84”...................................15
Hearth Stove Installation.....................................16
Interior or Exterior Masonry Chimney .................16
Safety Notice ..................................................17
Before Your First Fire....................................17
Curing the Paint..................................................17
Over-Firing the Stove..........................................17
Opening the Door...........................................18
Bypass Operation ..........................................18
Post Combustor – Use and Cleaning...........19
Inspecting & Cleaning the Combustor.................19
Starting a Fire.................................................20
Adjusting the Burn Rate................................21
Approximate Air Control Settings........................21
Ash Removal ..................................................22
Ash Pan Removal...............................................22
Re-Loading the Stove....................................23
Overnight Burn...............................................23
Normal Operating Sounds ............................23
Hints for Burning ...........................................24
Selecting Wood..............................................24
Why Dry Wood is Key.........................................24
Wood Cutting and Storage..................................24
Troubleshooting.............................................25
Daily Maintenance (while stove is in use)...26
Remove Ash (if necessary).................................26
Clean the Glass (if necessary)............................26
Monthly Maintenance (while appliance is in
use)..................................................................27
Door and Glass Inspection..................................27
Door Adjustment.................................................27
Door Removal.....................................................27
Creosote - Formation and Need for Removal .....28
Yearly Maintenance .......................................28
Touch-Up Paint...................................................28
Enamel Surfaces.....................................................28
Cleaning the Air Duct and Blower (if applicable).28
Firebrick and Baffle Inspection............................28
Cleaning the Post Combustor.............................29
Door Parts.......................................................30
Replacing the Glass............................................30
Replacing the Door Gasket.................................30
Replacing the Door Handle.................................30
Removing the Door.............................................30
Firebox Parts..................................................31
Baffle Removal & Replacement....................31
Andiron Removal...........................................31
Air Tube Removal & Replacement...............32
Combustor Removal......................................33
Firebrick Removal & Replacement.................33
Listing Label...................................................36
Rear Blower (Part # 99000139) .....................37
GreenStart™Woodstove Igniter (Part #
94400951)........................................................37

4 Safety Precautions
© Travis Industries 100-01383 4140402
The viewing door must be
closed and latched during
operation.
Smoke from this appliance may
active a smoke detector when
the door is open.
Never block free airflow through
the air vents on this appliance.
Gasoline or other flammable
liquids must never be used to
start the fire or "Freshen Up" the
fire. Do not store or use
gasoline or other flammable
liquids in the vicinity of this
appliance.
This appliance is designed and
approved for the burning of cord
wood only. Do not attempt to
burn any other type of fuel other
than cord wood in this
appliance, it will void all
warranties and safety listings.
Ashes must be disposed in a
metal container with a tight lid
and placed on a non-
combustible surface well away
from the home or structure.
Do not touch the appliance while
it is hot and educate all children
of the danger of a high-
temperature appliance. Young
children should be supervised
when they are in the same room
as the appliance.
Keep furniture, drapes, curtains,
wood, paper, and other
combustibles a minimum of 36"
(914mm) away from the front of
the appliance.
This appliance must be properly
installed to prevent the
possibility of a house fire. The
instructions must be strictly
adhered to. Do not use
makeshift methods or
compromise in the installation.
Contact your local building
officials to obtain a permit and
information on any installation
restrictions or inspection
requirements in your area.
Notify your insurance company
of this appliance as well.
Inspect the chimney connector
and chimney at least twice
monthly and clean if necessary.
Creosote may build up and
cause a house fire.
Do not connect this appliance to
any chimney serving another
appliance.
This appliance must be
connected to a listed high
temperature (UL 103 HT)
residential type chimney or an
approved masonry chimney with
a standard clay tile, or stainless
steel liner.
Gas
ASHES
36"
Ok
Type
HT Clay
Liner

Safety Precautions 5
© Travis Industries 100-01383 4140402
Do not throw this manual away.
This manual has important
operating and maintenance
instructions that you will need at
a later time. Always follow the
instructions in this manual.
Do not place clothing or other
flammable items on or near this
appliance.
Never try to repair or replace
any part of this appliance unless
instructions are given in this
manual. All other work must be
done by a trained technician.
Do not make any changes or
modifications to an existing
masonry fireplace or chimney to
install this appliance.
Do not make any changes to the
appliance to increase
combustion air.
Allow the appliance to cool
before carrying out any
maintenance or cleaning.
Over-firing the appliance may
cause a house fire. If a unit or
chimney connector glows, you
are over-firing.
Maintain the door and glass seal
and keep them in good
condition.
Do not operate this heater with
broken or missing glass.
Avoid placing wood against the
glass when loading. Do not
slam the door or strike the glass.
Do not use a grate or other
device to elevate the fire off of
the firebox floor. Burn the fire
directly on the firebox floor.
Travis Industries, Inc. grants
no warranty, implied or
stated, for the installation or
maintenance of your
appliance,and assumes no
responsibility of any
consequential damage(s).
This
Manual

6 Features & Specifications
© Travis Industries 100-01383 4140402
Installation Options
Freestanding
Optional GreenStart Igniter
Optional High-Tech Blower
Features
0.083 Cubic Meter Firebox Volume
Single Operating Control
Accepts Logs Up to 610mm (24”) Long
Cast Iron Construction
Heavy Duty Refractory Firebrick
Heating Specifications
Approximate Maximum Heating Capacity* Up to 300 Square Meters (3,200 sq. ft.)
Maximum Burn Time Up to 12 Hours
* Heating capacity will vary depending on the home's floor plan, degree of insulation, and the outside
temperature. It is also affected by the quality and moisture level of the fuel.
Dimensions
Figure 1
(a) Side, rear and corner clearances are measured from the stove top.
(b) Rubber-Tipped Leveling Bolts (at each corner).
Emissions / Efficiency
Appliance Emission Factor Burning Hardwood: 1.3g/Kg
Appliance Combustion Efficiency: 83%
Weight: 600 Lbs. (267 Kg)
3-1/4"
83mm
32-1/4"
821mm
19-3/4"
501mm
2"
51mm
a
b
35"
889mm

Stove Installation (for qualified installers only) 7
© Travis Industries 100-01383 4140402
SAFETY NOTICE:
Please read this entire manual before you install and use your new room heater.
Failure to follow instructions may result in property damage, bodily injury, or even
death. Contact local building or fire officials about restrictions and installation
inspection requirements in your area.
Installation Warnings
Failure to follow all of the requirements may result in property damage, bodily
injury, or even death.
Notify your insurance company before hooking up this heater.
The requirements listed below are divided into sections. All requirements must
be met simultaneously. The order of installation is not rigid – the authorised
installer should follow the procedure best suited for the installation.
Planning the Installation
We suggest that you have an authorized Travis Industries dealer install your stove. If you install the
stove yourself, your authorized dealer should review your installation plans.
Check with local building officials for any permits required for installation of this stove and notify your
insurance company before proceeding with installation.
Preparation for Installation
Make sure the baffles and combustor are in place.
Check for damage to the exterior of the stove (dents should be reported, scratches can be fixed by
applying touch-up paint).
Check the interior of the firebox (replace any cracked firebricks and make sure the baffle and post
combustor are in place).
Packing List
(9) Firebricks (see page 33 for installation instructions)
(1) Fire poker (shipped on pallet)
(1) Wood moisture meter
(1) Pair of gloves
(1) Bypass Rod
Rear Heat Shield

8 Stove Installation (for qualified installers only)
© Travis Industries 100-01383 4140402
Floor Protection Requirements
Floor protection must extend to the sides, rear, and front of the stove (see “Clearances” below for
minimum floor protection).
Floor protection must be 12mm thick cement fiber sheet which has a thermal resistance of 0.8M2K/W
per 4mm thick sheet.
Stove Placement Requirements
Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or
other means approved by local building or fire officials.
Stove must be placed so that no combustibles are within, or can swing within 36" (914mm) of the
front of the stove (drapes, doors, etc.)
Must maintain the clearances to combustibles listed below (drywall, furniture)
The stove requires an air source to operate. Combustion air starvation will result in poor performance
or smoke in the house.
Clearances
The following clearances must be met (see Figure 2 and Figure 3):
Minimum Clearance No Flue Shield
(corner install only) With Flue Shield
(no rear heat shield) With Flue Shield and
Rear Heat Shield
A Sidewall to stovetop N/A 450mm 450mm
B Back wall to stovetop N/A 476mm 201mm
C Corner wall to stovetop 250mm 250mm 250mm
D Connector to sidewall N/A 787mm 787mm
E Connector to back wall N/A 482mm 207mm
F Connector to corner wall 510mm 510mm 510mm
G Floor protection side 75mm 75mm 75mm
H Floor protection front 420mm 420mm 420mm
I Total Floor protection 970mm 970mm 970mm
AUSTRALIAN FLUE KIT REQUIREMENTS:
The above clearances are in accordance to the following:
The heater is to be installed with a 150mm/6” Stainless Steel triple skin (default) flue kit (fitted with heat
shields see below) which conforms to the requirements of the joint AS/NZS 2918:2001 Standard,
Appendix, with respect to the rear wall, side wall, floor and ceiling surface temperatures, when tested in
the positions shown.
Heat Shield Options:
1. 200mm/8” Decorative Mesh, up into the drop box, with the 1st length (900mm) to have a solid back.
2. Stainless Steel ½ Heat Shield x 1200mm/4ft in length.
3. 200mm ventilated, flue pipe up into the drop box.

Stove Installation (for qualified installers only) 9
© Travis Industries 100-01383 4140402
Top View -
Straight Installation
Figure 2
Top View -
Corner Installation
Figure 3
Measure rear and side clearances from
the nearest edge of the stove top.
Floor Protection
Measure front clearances from the
face of the stove (door opening).
Clearance A
NOTE: vent diameter may vary
depending on brand and model.
Clearance B
Back Wall
Side Wall
Clearance D
Typical Flue Center
Singlewall 18"
Reduced Clearance 15-1/2"
Typical Flue Center 29-1/2" 750mm
3-1/4"
83mm
32-1/4" 821mm
2"
51mm
19-3/4"
501mm
Clearance G
Clearance H
Clearance I
Clearance E
2"
51mm
Measure rear and side clearances from
the nearest edge of the stove top.
Floor Protection
Measure front clearances from the
face of the stove (door opening).
NOTE: vent diameter may vary
depending on brand and model.
Corner Wall
Corner Wall
Clearance C
Clearance F
Typical Flue Center
20-1/2" 521mm
3-1/4"
83mm
32-1/4" 821mm
19-3/4"
501mm
Clearance G
Clearance H
Clearance I

10 Stove Installation (for qualified installers only)
© Travis Industries 100-01383 4140402
Rear Heat Shield Installation
The rear heat shield is required for the clearances listed on page 8. It must be
installed prior to operation. Do not remove or alter the heat shield.
Install the rear heat shield as shown below.
Attach the four legs to the heat
shield. The nuts are shipped pre-
attached to the heat shield.
a
bAttach the the heat shield to the
stove. The screws are shipped pre-
attached to the stove.

Stove Installation (for qualified installers only) 11
© Travis Industries 100-01383 4140402
Chimney Connector Requirements
Chimney connector is required from the flue collar of the stove to the factory-built chimney or
masonry chimney.
The chimney connector must be 6” (152mm) diameter and stainless steel, or one of the reduced-
clearance connector.
NOTE: Aluminum or galvanized steel is not allowed – these materials cannot withstand the flue
temperatures and may give off toxic fumes when heated.
The chimney connector may not pass through a ceiling, attic, roof, closet, or any other concealed
space (use listed chimney – see “Chimney Requirements for details). DO NOT USE CONNECTOR
PIPE AS CHIMNEY.
The chimney connector should be as short and direct as possible. No more than 180oof elbows for the
entire system – connector and chimney (up to 4 45oelbows). No horizontal runs are allowed (45oslope
allowed).
The chimney connector must be installed with the crimped end pointing downwards. This prevents
creosote from leaking to the exterior of the pipe.
The chimney connector must be fastened to the stove and each adjoining section (and chimney).

12 Stove Installation (for qualified installers only)
© Travis Industries 100-01383 4140402
Chimney Requirements
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
DO NOT CONNECT TO OR USE IN CONJUNCTION WITH ANY AIR DISTRIBUTION DUCTWORK
UNLESS SPECIFICALLY APPROVED FOR SUCH INSTALLATIONS
IN CANADA: This appliance must be connected to a factory-built chimney conforming to CAN/ULC-
S629, Standard for 650°C Factory-Built Chimneys.
UL 103 HT Chimney must be used from the first ceiling or floor or wall penetration to the chimney
cap.
Use 6" (152mm) diameter type UL 103 HT chimney from one manufacturer (do not mix brands) or
code approved masonry chimney with a flue liner.
Chimney must be fastened to each adjoining section.
Follow the chimney manufacturer's clearances and requirements.
Use the chimney manufacturer's fire stops, attic guards, roof supports, and flashings when passing
through a ceiling and roof (see “b” and “d” below).
NOTE: Additional elbows may be allowed if draft is sufficient. Whenever elbows are used the draft is
adversely affected. Additional chimney height may be required to boost draft.
(a) Min. System Height 15’ (4.5M)
Max. System Height 33’ (10.058M)
(b) Roof Penetration and Termination (see
chimney manufacturer’s requirements)
(c) Chimney Sections
(d) Ceiling Penetration (see chimney
manufacturer’s requirements)
(e) Minimum air space to combustibles (see
chimney manufacturer’s requirements.
(f) Connector – see “Chimney Connector” on
the previous page.
Figure 4
Drafting
Performance This appliance relies upon natural draft to operate. External forces, such as wind,
barometric pressure, topography, or factors of the home (negative pressure from exhaust
fans, chimneys, air infiltration, etc.), may adversely affect draft. Travis Industries cannot be
responsible for external forces leading to less than optimal performance.
}
}
}
a
b
c
de
f
f
b

Stove Installation
(for qualified installers only)
13
© Travis Industries 100-01383 4140402
Chimney Termination Requirements
Must have an approved cap (to prevent water from entering)
Must not be located where it will become plugged by snow or other material
Must terminate at least 3' (914mm) above the roof and at least 2' (610mm) above any portion of the
roof within 10' (3.048M) (see Figure 5)
Figure 5
Outside Air Requirements
Must not be drawn from an enclosed space (garage, unventilated crawl space)
Requires a 3” duct that attaches to the bottom of the stove (see “a” and “b” below).
Outside air duct must have a rodent screen and rain hood (“c”).
The Travis Industries Outside Air Kit (sku 99200139) includes all the above components.
Figure 6
S
lanted Roofs
F
lat Roofs
Chimney must
extend 3'
above the roof
Chimney must extend 2'
above any portion of the roof
within 10' of the chimney
Chimney must
extend 3'
above the roof
Chimney must extend 2'
above any portion of the roof
within 10' of the chimney
a
b
c

14 Stove Installation (for qualified installers only)
© Travis Industries 100-01383 4140402
Standard Ceiling
with a Factory-
Built Chimney
Figure 7
Cathedral Ceiling
with a Factory-
Built Chimney
Figure 8
Chimney Cap
(See the section "Chimney
Termination Requirements"
for more details)
Chimney Sections
Minimum Air Space to
Combustibles (See
Chimney Manufacturer's
Instructions - usually 2")
Chimney Connector Sections
Follow the chimney
manufacturer's instructions
and clearances for roof
penetrations. A storm collar
and flashing are required
(some require a radiation
shield).
}
}
Minimum 15'
Maximum 33'
Stove Clearances
(See the section "Stove
Placement Requirements"
for more details)
Floor Protection
(See the section "Floor
Protection Requirements"
for more details)
Follow the chimney
manufacturer's instructions
and clearances for floor
penetrations. A ceiling
support is required, an attic
insulation shield is required
where insulation is present.
Insulation
Chimney Cap
(See the section "Chimney
Termination Requirements"
for more details)
Chimney Sections
Minimum Air Space to
Combustibles (See Chimney
Manufacturer's Instructions -
usually 2")
Follow the chimney
manufacturer's instructions
and clearances for roof
penetrations. A storm
collar, flashing, and
cathedral-style chimney
support are required
(some require a radiation
shield).
}
Minimum 15'
Maximum 33'
Stove Clearances
(See the section "Stove
Placement Requirements"
for more details)
Floor Protection
(See the section "Floor
Protection Requirements"
for more details)
Chimney
Connector
Sections

Stove Installation (for qualified installers only) 15
© Travis Industries 100-01383 4140402
Exterior Factory-Built Chimney
A vertical rise of 84” of chimney connector is required, measured from the floor, before entering a Class
‘A’ wall penetration. For those wishing to pass the chimney through the lower wall, a NFPA 211 wall
pass-through may be used (if approved by local building codes).
Wall Penetrations Under 84”
In cases where the chimney connector must be passed through a combustible wall or partition under 84”,
the following NFPA 211 method may be used if local building codes permit. Check with local authorities
before installation to insure all necessary requirements have been met. Figure 12 details a wall pass-
through based on the NFPA 211 standard. After the pass-through, Class A Chimney may be used in
accordance with the chimney installation instructions.
Figure 9
NFPA 211 Wall Pass-Through
(see NFPA 211 for a full description)
12 Min.
12 Min.
Combustible Materials
Brick
Fire Clay Thimble

16 Stove Installation (for qualified installers only)
© Travis Industries 100-01383 4140402
Hearth Stove
Installation
NOTE:
This type of installation
requires a full reline
(positive connection).
Interior or Exterior
Masonry Chimney
NOT ALLOWED IN
CANADA UNLESS FULL
RELINE IS USED>.
NOTE:
This type of installation
requires a UBC approved
masonry connector or other
method approved by the
NFPA 211 Standard. See
page 10 for further details.
WARNING:
We strongly recommend a
full reline (positive
connection) when venting
through a masonry chimney.
The Cape Cod is equipped
with a post combustor and
may draft poorly without a full
reline. We also recommend
that a minimum 3’ chimney
be added to the minimum
system height for every 1’ of
horizontal run.
Always use 45 degree
elbows if possible.
Remove damper
or wire it open
Airtight Insulated
Clean-Out
Min. 36"
Combustible
Mantle
NOTE: The entire fireplace and
chimney must be clean, undamaged,
and meet all local building codes
(UBC, etc.). Damage must be
repaired prior to installation. The
chimney must be 15' to 33' tall.
Floor Protection
(See the section
"Floor Protection
Requirements"
for more details)
See the section
"Stove Placement
Requirements" for
minimum clearances
required.
The liner must be
stainless steel connector
or flexible vent. Follow
the liner manufacturer's
instructions for installation
and support.
Cap and flashing
prevents water from
entering
Make sure the
clean-out seals in
place.
Clay Liner
See the section "Stove
Placement Requirements" for
minimum clearances required.
Min. 18"
clearance
to ceiling This type of
installation requires
a UBC approved
masonry connector
or other method
approved by the
NFPA 211 standard.
Chimney connector sections
NOTE: The chimney must
have a clay tile liner. If it does
not, the installation must use a
full reline (positive
connection). The entire
fireplace and chimney must
be clean, undamaged, and
meet all local building codes
(UBC, etc.). Damage must be
repaired prior to installation.
The chimney must be 15' to
33' tall.
See the section
"Floor Protection
Requirements"
Full Reline

Operating Your Appliance 17
© Travis Industries 100-01383 4140402
Safety Notice
If this appliance is not properly installed, a house fire may result. For your safety, follow the installation
directions. Contact local building or fire officials about restrictions and installation inspection
requirements in your area.
Read and follow all of the warnings on pages 4 and 5 of this manual.
Do not operate this stove with the ash pan open. A fire
hazard will result.
Before Your First Fire
Verify the Installation:
Before starting the stove, verify that the stove is properly installed and all of the requirements in this
manual have been followed.
Keep all flammable materials 36" (914mm) away from the front of the stove (drapes, furniture, clothing, etc.).
Curing the Paint
This heater uses a heat-activated paint that will emit some fumes while
starting the first fire. Open doors and windows to the room to vent these
fumes. This typically lasts two to four hours. You may also notice oil burning
off of the interior of the heater. This rust-stopping agent will soon dissipate.
Door Gasket - The door gasket might adhere to the paint on the front of the
heater. Leave the door slightly ajar for the first fire and be careful when
opening the door after the first fire.
Over-Firing the Stove
This stove was designed to operate at a high temperature. But due to differences in vent configuration,
fuel, and draft, this appliance can be operated at an excessive temperature. If the stove top or other area
starts to glow red, you are over-firing the stove. Shut the air control down to low and allow the stove to
cool before proceeding.
Over-firing may lead to damage. If you are uncertain of over-firing conditions, we suggest placing a
stove thermometer (e.g. Rutland® Model 710) directly in front of the flue outlet on the stovetop (see
photo below) temperatures exceeding 700° are generally considered over-firing and will void the
warranty.
2 to 4 hours

18 Operating Your Appliance
© Travis Industries 100-01383 4140402
Opening the Door
The door becomes hot during use. Use a glove to open the door if the handle is hot.
Do not operate this stove with the door open. A fire hazard will result.
To prevent smoke from entering the room, open the air control and bypass (see instructions below)
before opening the door. You can also open the door a small amount and let air enter the firebox to
equalize the pressure, and then open the door fully.
Bypass Operation
The bypass controls the flow of smoke inside the heater. When pulled out, smoke goes directly up the
flue, creating more draft. When pushed in, the smoke goes around the baffle, utilizing the secondary
combustion and making the heater more efficient.
When re-loading, pull the bypass out.
During normal operation, push the bypass in.
Bypass Pushed In
Used for normal operation
Bypass Pulled Out
Used for starting and re-loading
Use the included pull tool
to operate the bypass rod

Operating Your Appliance 19
© Travis Industries 100-01383 4140402
Post Combustor – Use and Cleaning
This heater uses a post combustor to improve efficiency and reduce emissions. To work at its
optimum, the combustor must be kept free of excessive ash. If the heater becomes sluggish
when the bypass is closed, flyash may be building up on the combustor. See the directions
below to inspect and clean the combustor with the included brush.
Inspecting & Cleaning the Combustor
The combustor becomes very hot during operation. Let the heater cool before cleaning the combustor.
The combustor is located directly above
the firebox opening. Make sure the
square openings are open for air to pass
through. If ash is accumulating, use the
brush to clear off visible flyash.
NOTE: To thoroughly clean the
combustor, use an ash vacuum to pull
flyash from the combustor (see page 29).
Combustor

20 Operating Your Appliance
© Travis Industries 100-01383 4140402
Starting a Fire
Use of the optional GreenStart igniter will greatly simplify this process. See page 37.
Since the dawn of time man has debated the best way to start a fire. Some use the boy-scout "tee-pee"; some
prefer the "tic-tac-toe" stack. Either way, review the hints and warnings below to ensure proper fire starting.
Make sure the air control is pulled out. If additional air is needed, open the door 1/4" during the first
five minutes of startup.
Make sure the bypass is pulled out.
Do not use colored paper or any material other than newspaper and cord wood to start a fire.
This may damage the post combustor.
Never use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter fluid, or similar liquids to start
or "freshen up" a fire in this stove. Keep all such liquids well away from the stove while it is in use.
DO NOT USE CHEMICALS OR FLUIDS TO START THE FIRE. DO NOT BURN GARBAGE OR
FLAMMABLE FLUIDS SUCH AS GASOLINE, NAPHTHA OR ENGINE OIL. Do not place such fuel
within space heater installation clearances or within the space required for charging and ash removal.
If using a fire-starter, use only products specifically designed for stoves - follow the manufacturer's
instructions carefully.
HOT WHILE IN OPERATION. KEEP CHILDREN, CLOTHING AND FURNITURE AWAY. CONTACT
MAY CAUSE SKIN BURNS.
Do not open the ash pan when the stove is lit. An extreme fire hazard will result.
If the smoke does not pass up the chimney, ball up one sheet of newspaper, place it in the center of the
firebox and light it. This should start the chimney drafting (this eliminates "cold air blockage").
Use plenty of kindling to ensure the stove reaches a proper temperature. Once the kindling is burning
rapidly, place a few larger pieces of wood onto the fire.
This manual suits for next models
1
Table of contents
Other Lopi Wood Stove manuals

Lopi
Lopi M-520 User manual

Lopi
Lopi Endeavor User manual

Lopi
Lopi Liberty Wood Stove User manual

Lopi
Lopi Leyden 028-S-75-2 User manual

Lopi
Lopi Cape Cod User manual

Lopi
Lopi Endeavor User manual

Lopi
Lopi Leyden Wood Stove User manual

Lopi
Lopi Answer User manual

Lopi
Lopi Answer User manual

Lopi
Lopi Greenfield GSR2 User manual
Popular Wood Stove manuals by other brands

RAIS
RAIS attika NEXO 100 GAS installation guide

WoodPro
WoodPro WS-TS-1500 owner's manual

Contura
Contura C 586W installation instructions

Palazzetti
Palazzetti EVA GENERAL INFORMATION - WARNINGS - INSTALLATION - MAINTENANCE

Panadero
Panadero CAPRI 3V Usage and maintenance instructions

Ventis
Ventis HES350 owner's manual