I545 GB D 09 17 31100384
1
WARNING!
– Carefully read the manual before the installation or use.
– This equipment is to be installed by qualified personnel, complying to current standards, to avoid damages or safety
hazards.
– Remove eventual dangerous voltage from the product before any maintenance operation on it.
– The manufacturer cannot be held responsible for electrical safety in case of improper use of the equipment.
– Products illustrated herein are subject to alteration and changes without prior notice. Technical data and descriptions
in the documentation are accurate, to the best of our knowledge, but no liabilities for errors, omissions or
contingencies arising therefrom are accepted.
– A circuit breaker must be included in the electrical installation of the building. It must be installed close by the
equipment and within easy reach of the operator.
It must be marked as the disconnecting device of the equipment: IEC/EN 61010-1 § 6.11.
– Fit the instrument in an enclosure or cabinet with minimum IP51 degree protection.
– Clean the instrument with a soft dry cloth, do not use abrasives, liquid detergents or solvents.
INTRODUCTION
The DME D122MID is a single-phase active and reactive energy meter for direct connection, for currents up to 63A,
equipped with a built-in M-BUS serial interface.
The energy accuracy is compliant with standard EN50470-3 class B.
Apart from energy metering, it can measure additional indications, for a total of 14 measurements that can be visualized on
the backlighted LCD display.
The DME D122MID has a standard 2U (36mm wide) modular housing and is supplied with sealable terminal blocks.
DESCRIPTION
– Modular DIN-rail housing, 2U (36mm wide).
– Direct connection for currents up to 63A.
– Active energy measure complies EN50470-3 class B.
– LCD display with backlight.
– Counter with 6+1 digits.
– Button for measure selection and programming.
– Total active and reactive energy meters.
– Partial active and reactive energy meters, resettable.
– Hour counter, total and partial.
– Pulse LED for active energy consumption.
– Indication of instantaneous consumption (active power).
– M-BUS interface.
SELECTION OF READINGS
– Pressing briefly the button it is possible to select the readings on the display, following the sequence in the table
reported below.
– Each measure is indicated by the correspondent icon in the lower part of the display.
– After one minute has elapsed after the last keystroke, the display moves automatically back to the total active energy
screen.
ACHTUNG!!
– Diese Betriebsanleitung vor Gebrauch und Installation aufmerksam lesen.
– Zur Vermeidung von Personen- und Sachschäden dürfen diese Geräte nur von qualifiziertem Fachpersonal und unter
Befolgung der einschlägigen Vorschriften installiert werden.
– Vor jedem Eingriff eventuell am Gerät anliegende gefährliche Spannungen trennen.
– Bei zweckwidrigem Gebrauch der Vorrichtung übernimmt der Hersteller keine Haftung für die elektrische Sicherheit.
– Die in dieser Broschüre beschriebenen Produkte können jederzeit weiterentwickelt und geändert werden. Die im
Katalog enthaltenen Beschreibungen und Daten sind daher unverbindlich und ohne Gewähr.
– In die elektrische Anlage des Gebäudes ist ein Ausschalter oder Trennschalter einzubauen. Dieser muss sich in
unmittelbarer Nähe des Geräts befinden und vom Bediener leicht zugänglich sein. Er muss als Trennvorrichtung für das
Gerät gekennzeichnet sein: IEC/ EN 61010-1 § 6.11.
– Das Instrument in einem Gehäuse und/oder in einer Schalttafel mit Mindestschutzart IP51 installieren.
– Das Instrument mit einem weichen Tuch reinigen, keine Scheuermittel, Flüssigreiniger oder Lösungsmittel verwenden.
VORWORT
Der DME D122MID ist ein einphasiger Energiezähler mit Direktanschluss für Ströme bis zu 63A und serieller
M-Bus-Schnittstelle.
Die Energiemessung erfüllt die Bestimmungen der Norm EN 50470-3 Klasse B.
Neben der Energiemessung liefert das Gerät weitere Angaben für insgesamt 14 Messungen, die auf dem großen
LCD-Bildschirm mit Hintergrundbeleuchtung angezeigt werden können.
Der DME D122MID hat ein modulares Standardgehäuse der Breite 2U (36 mm) und ist serienmäßig mit plombierbaren
Klemmenabdeckungen ausgestattet.
BESCHREIBUNG
– Modulare Ausführung 2U (36mm) für DIN-Schiene.
– Direktanschluss für max. Ströme 63A.
– Wirkenergiemessung gemäß EN 50470-3 Klasse B.
– LCD-Bildschirm mit Hintergrundbeleuchtung.
– Zähler mit 6+1 Ziffern.
– Taste für die Wahl der Messungen und Programmierung.
– Wirk- und Blindenergiezähler (Gesamt).
– Energiezähler (Teil, rücksetzbar).
– Gesamt- und Teilstundenzähler.
– Impulsgesteuerte, frontseitige LED für die verbrauchte Wirkenergie.
– Anzeige Momentanverbrauch (Wirkleistung).
– M- BUS-Schnittstelle.
WAHL DER MESSUNGEN
– Durch kurzes Drücken der Taste können die Messungen auf dem Bildschirm des Instruments gemäß der in der
nachstehenden Tabelle angegebenen Sequenz gewählt werden.
– Jede Wahl wird mit der jeweiligen Maßeinheit vom entsprechenden Symbol im unteren Bildschirm-Abschnitt angezeigt.
– Nachdem die Taste an der Vorderseite eine Minute lang nicht gedrückt wurde, wechselt die Messung wieder auf den
Gesamt-Wirkenergiezähler.
Icon Measurement Format
kWh Total active energy 000000,0
kWh + Part Partial active energy 000000,0
kvarh Total reactive energy 000000,0
kvarh + Part Partial reactive energy 000000,0
V Voltage 000,0
A Current 00,00
kW Active power 00,00
kvar Reactive power 00,00
PF Power factor 0,00
Hz Frequency 00,0
h ∂ Hour counter (hhhhh.mm) 00000,00
h + Part ∂ Partial hour counter (hhhhh.mm) 00000,00
kW +d ∑ Average active power (15 min demand) 00,00
kW+d+∑ Max avg. active power (max demand) 00,00
Symbol Messung Format
kWh Gesamtwirkenergie 000000,0
kWh + Part Teilwirkenergie 000000,0
kvarh Gesamtblindenergie 000000,0
kvarh + Part Teilblindenergie 000000,0
V Spannung 000,0
A Strom 00,00
kW Wirkleistung 00,00
kvar Blindleistung 00,00
PF Leistungsfaktor 0,00
Hz Frequenz 00,0
h ∂ Stundenzähler (hhhhh.mm) 00000,00
h + Part ∂ Teilstundenzähler (hhhhh.mm) 00000,00
kW +d ∑ Durchschn. Wirkleistung (Leistung in 15 Min.) 00,00
kW+d+∑ Max. durchschn. Wirkleistung (max. Leistung) 00,00
∂ These measurements are shown only enabling parameter P-08
∑ These measurements are shown only enabling parameter P-09
∂ Diese Messungen sind nur sichtbar, wenn der Parameter P-08 aktiviert wird
∑ Diese Messungen sind nur sichtbar, wenn der Parameter P-09 aktiviert wird
DME D122MID
GB
EINPHASIGER ENERGIEZÄHLER MIT DIREKTANSCHLUSS MIT M-BUS-SCHNITTSTELLE
Installationshandbuch
D
LOVATO ELECTRIC S.P.A.
24020 GORLE (BERGAMO) ITALIA
VIA DON E. MAZZA, 12
TEL. 035 4282111
TELEFAX (Nazionale): 035 4282200
TELEFAX (International): +39 035 4282400
E-mail info@LovatoElectric.com
Web www.LovatoElectric.com
SINGLE-PHASE DIRECT CONNECTION ENERGY METER WITH M-BUS INTERFACE
Installation manual
METROLOGICAL LED
– The red LED on the front emits 1000 pulses for every kWh of consumed Energy (that is, one pulse every Wh).
– The pulsing frequency of the LED gives an immediate indication of the energy flowing in every moment.
– The pulse duration, LED colour and intensity are compliant with the reference standards that define its utilization in
order to verify the accuracy of the energy meter.
ENERGY FLOW INDICATION
– When the device detects a flow of active energy to the load, it shows a rotating icon in the top-right part of the display.
– When there is no active energy consumption or when the load draws less than the starting current the rotating icon
disappears.
M-BUS
– DME D122MID supports two addressing ways: primary address from 1 to 250 and secondary address from 00000000
to 99999999.
– Baud rates: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 bps.
– Refer to the electrical schemes at the end of the manual to connect DME D122MID to the bus in the proper way.
– For reference tables and application notes go to www.lovatoelectric.com to get the M-BUS guide (instruction number:
I513).
PROGRAMMABLE LIMIT THRESHOLD
– Through parameters from P-02 to P-07 it is possible to define the behaviour of a programmable limit threshold, whose
status can be read from the communication protocol (see modbus addresses table).
– The activation of the programmable limit threshold is shown on the display through the icon.
– Note: During parameter setting (setup) the status of the programmable limit threshold is not updated.
INCORRECT WIRING INDICATION
– In case of incorrect wiring, when the device detects a reverse energy flow, the display shows the blinking code Err 3.
– This error is caused by either reverse connection of current wires (terminals Land L) or reverse voltage wiring
(terminals N - L).
– In these conditions, the energy is not counted.
METROLOGISCHE LED AN DER VORDERSEITE
– Die rote LED an der Vorderseite gibt 1000 Impulse pro kWh verbrauchte Energie ab (d.h. 1 Impuls pro Wh).
– Die Blinkfrequenz der LED liefert eine unmittelbare Angabe über den Umfang der in einem bestimmten Augenblick
angeforderten Leistung.
– Die Dauer des Blinkimpulses sowie die Farbe und Leuchtstärke der LED entsprechen den Normen, die ihre Verwendung
zwecks metrologischer Überprüfung der Genauigkeit des Energiezählers vorschreiben.
ENERGIEFLUSSANZEIGE
– Wenn das Instrument einen Energiefluss zur Last misst, erscheint auf dem Bildschirm in der rechten oberen Ecke ein
drehendes Symbol.
– Wenn die Last keine Wirkenergie erfordert, oder wenn die Stromaufnahme geringer als der Anlaufstrom ist,
verschwindet das drehende Symbol.
M-BUS
– DME D122MID unterstützt zwei Arten der Adressierung: Primäradresse von 1 bis 250 und Sekundäradresse von
00000000 bis 99999999.
– Einstellbare Geschwindigkeiten: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 bps.
– Für den korrekten Anschluss des DME D122MID an den Bus bitte die Anschlusspläne am Ende des Handbuchs
beachten.
– Für die Bezugstabellen und Hinweise wird auf die M-Bus-Anleitung verwiesen, die auf der Website
www.lovatoelectric.com eingesehen werden kann (Nummer der Anleitung: I513).
PROGRAMMIERBARER GRENZWERT
– Über die Parameter von P-02 bis P-07 kann das Verhalten eines programmierbaren Grenzwerts festgelegt werden,
dessen Status über das Kommunikationsprotokoll abgelesen werden kann (siehe Tabelle der Modbus-Adressen).
– Die Aktivierung des programmierbaren Grenzwerts wird mit dem Symbol auf dem Bildschirm angezeigt.
– Hinweis: Während der Parametereinstellung (Setup) wird der Status des programmierbaren Grenzwerts nicht
aktualisiert.
ANZEIGE FALSCHER ANSCHLUSS
Wenn das Gerät falsch angeschlossen wurde und ein Energiefluss in die falsche Richtung erfasst wird, wird die
blinkende Anzeige Err 3 aktiviert.
Dieser Fehler kann durch Vertauschen des Stromanschlusses (Klemmen Lund L) oder durch Vertauschen der
Spannungsklemmen (N - L) verursacht werden.
Unter diesen Bedingungen wird die Energie nicht gezählt.
UE declaration: http://www.lovatoelectric.com/DMED122MID/DMED122MID/snp EU-Erklärungen: http://www.lovatoelectric.com/DMED122MID/DMED122MID/snp