LOVATO ELECTRIC DMED100T1MID User manual

I304 GB I 05 21 31100138
1
DMED100T1MID
WARNING!
– Carefully read the manual before the installation or use.
– This equipment is to be installed by qualified personnel, complying to current standards, to avoid damages or safety
hazards.
– Remove eventual dangerous voltage from the product before any maintenance operation on it.
– The manufacturer cannot be held responsible for electrical safety in case of improper use of the equipment.
– Products illustrated herein are subject to alteration and changes without prior notice. Technical data and descriptions
in the documentation are accurate, to the best of our knowledge, but no liabilities for errors, omissions or
contingencies arising therefrom are accepted.
– A circuit breaker must be included in the electrical installation of the building. It must be installed close by the
equipment and within easy reach of the operator.
It must be marked as the disconnecting device of the equipment: IEC/EN 61010-1 § 6.11.3.1.
– Fit the instrument in an enclosure or cabinet with minimum IP51 degree protection.
– Clean the instrument with a soft dry cloth, do not use abrasives, liquid detergents or solvents.
INTRODUCTION
The DMED100T1 is a single-phase active and reactive energy meter for direct connection, for currents up to 40A.
The energy accuracy is compliant with EN 50470-3 (MID class B).
The DMED100T1 has a standard 1U (18mm wide) modular housing and is supplied with sealable terminal blocks.
DESCRIPTION
– Modular DIN-rail housing, 1U (18mm wide).
– Direct connection for currents up to 40A.
– Total active energy metering complies EN 50470-3 class B.
– Available in standard version (code DMED100T1) and in MID-certified version (code DMED100T1MID).
– LCD display with 5+1 digits counter.
– Pulse LED for active energy consumption.
– Static pulse output for remote energy counting.
METROLOGICAL LED
– The red LED on the front emits 1000 pulses for every kWh of consumed energy (that is, one pulse every Wh).
– The pulsing frequency of the LED gives an immediate indication of the energy flowing in every moment.
– The pulse duration, LED colour and intensity are compliant with the reference standards that define its utilization in
order to verify the accuracy of the energy meter.
INSULATED STATIC OUTPUT
– The static output on the upper terminals sends 10 pulses per kWh.
– It can be used as a pulse output for remote energy counting towards:
•
an external data concentrator (like DMECD)
•
a remote electromechanical counter
•
a PLC or other device.
– The connection can be done in PNP or NPN mode. See schematic diagrams and technical characteristics for details on
the wiring and on the rating.
INCORRECT WIRING INDICATION
– In case of incorrect wiring, when the device detects a reverse energy flow, the display shows the blinking code Error 3.
– This error is caused by either reverse connection of current wires (terminals L↑and L↓) or reverse voltage wiring
(terminals N - L↑).
– In these conditions the energy is not counted.
METROLOGICAL SEALING AND MARKINGS
– The MID certified device is identified by the appropriate markings on the side (see picture) and by the product code
DMED100T1MID written on the front panel and on the side of the enclosure.
– It is equipped with some anti-tampering solutions like:
•
two anti-tampering labels that seals the enclosure, that avoid the possibility to access the internal circuitry
•
sealable terminal covers that, when installed with proper sealing eliminate the possibility to access terminals and
wiring.
– The sealings on the device must appear intact, otherwise the MID certification is void.
– The serial number of the device is placed on a label on the side.
ATTENZIONE!!
– Leggere attentamente il manuale prima dell’utilizzo e l’installazione.
– Questi apparecchi devono essere installati da personale qualificato, nel rispetto delle vigenti normative impiantistiche,
allo scopo di evitare danni a persone o cose.
– Prima di qualsiasi intervento sull’apparecchio, rimuovere eventuali tensioni pericolose dall’apparecchio
– Il costruttore non si assume responsabilità in merito alla sicurezza elettrica in caso di utilizzo improprio del dispositivo.
– I prodotti descritti in questo documento sono suscettibili in qualsiasi momento di evoluzioni o di modifiche. Le
descrizioni ed i dati a catalogo non possono pertanto avere alcun valore contrattuale.
– Un interruttore o disgiuntore va compreso nell’impianto elettrico dell’edificio. Esso deve trovarsi in stretta vicinanza
dell’apparecchio ed essere facilmente raggiungibile da parte dell’operatore. Deve essere marchiato come il dispositivo
di interruzione dell’apparecchio: IEC/EN 61010-1 § 6.11.3.1.
– Installare lo strumento in contenitore e/o quadro elettrico con grado di protezione minima IP51.
– Pulire lo strumento con panno morbido, non usare abrasivi, detergenti liquidi o solventi.
INTRODUZIONE
Il DMED100T1 è un contatore di energia monofase per inserzione diretta, per correnti fino a 40A.
La misurazione dell’energia è conforme alla norma EN 50470-3 (MID classe B).
Il DMED100T1 ha un contenitore modulare standard di larghezza 1U (18mm) ed è fornito di serie di coprimorsetti piombabili.
DESCRIZIONE
– Esecuzione modulare 1U (18mm) per guida DIN.
– Inserzione diretta per correnti max 40A.
– Contatore di energia attiva totale conforme a EN 50470-3 classe B.
– Disponibile in versione standard (cod. DMED100T1) e in versione omologata MID (cod. DMED100T1MID)
– Display LCD con 5+1 cifre.
– LED frontale a impulsi per energia attiva consumata.
– Uscita statica a impulsi per remotazione conteggio.
LED METROLOGICO FRONTALE
– Il LED rosso frontale emette 1000 impulsi per ogni kWh di energia consumata (ovvero 1 impulso per ogni Wh).
– La frequenza di lampeggio del LED dà una immediata indicazione dell’entità della potenza richiesta in un determinato
istante.
– La durata del lampeggio, il colore e l’intensità del LED sono conformi alle norme che prescrivono il suo utilizzo ai fini
di una verifica metrologica della accuratezza dell’energy meter.
USCITA STATICA ISOLATA
– L’uscita statica disponibile sui morsetti superiori emette 10 impulsi per kWh.
– Essa può essere utilizzata come uscita ad impulsi per la remotazione del conteggio verso:
•
un concentratore dati esterno (tipo DMECD);
•
un contatore elettromeccanico remoto;
•
un PLC o altra apparecchiatura.
– Il collegamento può essere effettuato in modo PNP o NPN. Vedere schemi di collegamento e caratteristiche tecniche
per dettagli sulla portata.
INDICAZIONE DI COLLEGAMENTO ERRATO
– In caso di collegamento errato, quando l’apparecchio rileva un flusso di energia di direzione contraria, viene attivata
l’indicazione Error 3.
– Questo errore può essere provocato dalla inversione del collegamento della corrente (morsetti L↑e L↓) oppure dalla
inversione della tensione (N - L↑).
– In queste condizioni l’energia non viene conteggiata.
SIGILLI METROLOGICI E MARCATURE
– L’apparecchio certificato MID è identificabile per la presenza degli opportuni marchi sulla targa (vedere figura), nonché
del codice DMED100T1MID riportato sul fronte e sul lato del contenitore.
– Esso è dotato di alcuni accorgimenti che ne impediscono la manomissione:
•
2 sigilli laterali (etichette antimanomissione) che impediscono l’apertura del contenitore e l’accesso ai circuiti interni;
•
coprimorsetti piombabili che quando installati con gli opportuni sigilli impediscono l’accesso ai morsetti e cablaggi.
– I sigilli sull’ apparecchio devono presentarsi intatti, altrimenti la certificazione MID dell’apparecchio è da considerarsi
decaduta.
– Il numero di serie dell’apparecchio è posto su una apposita etichetta laterale.
SINGLE-PHASE DIRECT CONNECTION ENERGY METER
Instruction manual
GB
CONTATORE DI ENERGIA MONOFASE A INSERZIONE DIRETTA
Manuale operativo
I
LOVATO ELECTRIC S.P.A.
24020 GORLE (BERGAMO) ITALIA
VIA DON E. MAZZA, 12
TEL. +39 035 4282111
E-mail info@
L
ovato
E
lectric.com
Web www.
L
ovato
E
lectric.com
MECHANICAL DIMENSIONS [mm] AND WIRING DIAGRAMS
63
90
45
98.3
104.7
17.9
43.7
Ø4.2mm
DIMENSIONI MECCANICHE [mm] E SCHEMI DI COLLEGAMENTO
LL
SO+
N
SO-
N
LL
SO+ SO-
NN
N
SO+
LL
SO-
N
O1-O1+
Static output
30VDC 50mA max
_
+
NN
LL
LOAD
LINE
NPN out PNP out
UE declarations: http://www.lovatoelectric.com/DMED100T1MID/DMED100T1MID/snp Dichiarazioni UE: http://www.lovatoelectric.com/DMED100T1MID/DMED100T1MID/snp
DME D100 T1 MID
Energy meter
LL
O1+O1-
METER
NN
Static output
30V - 50mA
230V∼50Hz
0.25-5 (40)A CL B
t = -25° to +55°
MADE IN
ITALY
M19
065/MID
0051
LOVATO ELECTRIC S.P.A.
Via Don E. Mazza, 12
24020 GORLE (Bergamo) Italy
2
I304 GB I 05 21 31100138
GB
TECHNICAL CHARACTERISTICS
Voltage
Rated voltage Us 230V

Operating voltage range 187...264V

Rated frequency 50Hz
Operating frequency range 45...66Hz
Power consumption/dissipation 6.6VA / 0.45W
Current
Minimum current (Imin) 0.25A
Transition current (Itr) 0.5A
Reference current (Iref - Ib) 5A
Max current (Imax) 40A
Start current (Ist) 20mA
Accuracy
Active Energy EN50470-3 Class B
LED pulse
Number of pulses 1000 pulses / kWh
Pulse length 30ms
Static output
Number of pulses 10 pulses / kWh
Pulse length 100ms
External voltage 10...30VDC
Max current 50mA
Ambient conditions
Mounting Indoor use only
Operating temperature -25...+55°C
Storage temperature -25...+70°C
Relative humidity <90% non-condensing
(IEC/EN 60068-2-78)
Maximum pollution degree 2
Overvoltage category III
Altitude ≤2000m
Climatic sequence Z/ABDM (IEC/EN 60068-2-61)
Shock resistance 10g (IEC/EN 60068-2-27)
Vibration resistance 0.7g (IEC/EN 60068-2-6)
Mechanical environment Class M1
Electromagnetic environment Class E2
Insulation
Rated insulation voltage Ui 250V

Rated impulse withstand voltage Uimp 6kV
Power frequency withstand voltage 4kV
Supply / measure connections
Type of terminal Screw (fixed)
Number of terminals 4
Conductor cross section (min...max) 1.5...10mm2(15...7AWG)
Tightening torque 1.5Nm (13.3lb.in)
Pulse output connections
Type of terminal Screw (fixed)
Number of terminals 2
Conductor cross section (min...max) 0.2...4.0mm2(24...12AWG)
Tightening torque 0.8Nm (7lb.in)
Housing
Version 1 module (DIN 43880)
Mounting 35mm DIN rail (EN60715)
or by screw using extractible clips
Material Polyamide RAL 7035
Degree of protection IP40 on front 
IP20 terminals
Weight 85g
Certifications and compliance
Certifications obtained MID Class B (EN 50470-1, EN 50470-3), certifications for
module B (type approval) and per module D (production
process), EAC, RCM
Comply with standards EN 50470-1, EN 50470-3, TR 50579

To comply with the protection requirements, the meter must be mounted in a class IP 51 enclosure or better (IEC 60529).
I
CARATTERISTICHE TECNICHE
Tensione
Tensione nominale Us 230V

Limiti di funzionamento 187...264V

Frequenza nominale 50Hz
Limiti di funzionamento 45...66Hz
Potenza assorbita/dissipata 6,6VA / 0,45W
Corrente
Corrente minima (Imin) 0,25A
Corrente di transizione (Itr) 0,5A
Corrente di riferimento (Iref - Ib) 5A
Corrente massima (Imax) 40A
Corrente di start (Ist) 20mA
Accuratezza
Energia attiva EN50470-3 Classe B
Impulso LED
Numero di impulsi 1000imp / kWh
Durata impulso 30ms
Uscita statica
Numero di impulsi 10 impulsi / kWh
Durata impulso 100ms
Tensione esterna 10...30VDC
Corrente massima 50mA
Condizioni ambientali
Installazione Solo per uso interno
Temperatura d’impiego -25...+55°C
Temperatura di stoccaggio -25...+70°C
Umidità relativa <90% non condensante
(IEC/EN 60068-2-78)
Grado di inquinamento ambiente massimo 2
Categoria dì sovratensione III
Altitudine ≤2000m
Sequenza climatica Z/ABDM (IEC/EN 60068-2-61)
Resistenza agli urti 10g (IEC/EN 60068-2-27)
Resistenza alle vibrazioni 0,7g (IEC/EN 60068-2-6)
Ambiente meccanico Classe M1
Ambiente elettromagnetico Classe E2
Isolamento
Tensione nominale d’isolamento Ui 250V

Tensione nom. di tenuta a impulso Uimp 6kV
Tensione di tenuta a frequenza d’esercizio 4kV
Connessioni circuito alimentazione / misura
Tipo di morsetti A vite (fissi)
Numero di morsetti 4
Sezione conduttori (min...max) 1,5...10mm2(15...7AWG)
Coppia di serraggio morsetti 1,5Nm (13.3lb.in)
Connessioni uscita impulsi
Tipo di morsetti A vite (fissi)
Numero di morsetti 2
Sezione conduttori (min...max) 0,2...4,0mm2(24...12AWG)
Coppia di serraggio morsetti 0,8Nm (7lb.in)
Contenitore
Esecuzione 1 modulo (DIN 43880)
Montaggio Guida 35mm (EN60715)
o a vite a mezzo clip estraibili
Materiale Poliammide RAL 7035
Grado di protezione IP40 sul fronte 
IP20 connessioni
Peso 85g
Omologazioni e conformità
Omologazioni ottenute MID Classe B (EN 50470-1, EN 50470-3), certificati per
modulo B (conformità del progetto tecnico) + modulo D
(conformità della qualità del processo di produzione),
EAC, RCM
Conformi alle norme EN 50470-1, EN 50470-3, TR 50579

Per garantire la protezione richiesta, lo strumento deve essere installato in contenitore con grado di protezione minimo
IP51 (IEC 60529).

This manual suits for next models

1

Other LOVATO ELECTRIC Measuring Instrument manuals

LOVATO ELECTRIC LOVATO ELECTRIC User manual

LOVATO ELECTRIC

LOVATO ELECTRIC LOVATO ELECTRIC User manual

LOVATO ELECTRIC LAWN DME D121 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC LAWN DME D121 User manual

LOVATO ELECTRIC DME D310 T2 MID User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DME D310 T2 MID User manual

LOVATO ELECTRIC DMED300T2UL User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DMED300T2UL User manual

LOVATO ELECTRIC DMG900 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DMG900 User manual

LOVATO ELECTRIC DME D110T1 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DME D110T1 User manual

LOVATO ELECTRIC EXP10 40 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC EXP10 40 User manual

LOVATO ELECTRIC DMED302MID User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DMED302MID User manual

LOVATO ELECTRIC DME D305T2MID User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DME D305T2MID User manual

LOVATO ELECTRIC DMED301MID User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DMED301MID User manual

LOVATO ELECTRIC DME D121 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DME D121 User manual

LOVATO ELECTRIC DMG300 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DMG300 User manual

LOVATO ELECTRIC DME D120 T1 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DME D120 T1 User manual

LOVATO ELECTRIC DME D310 T2 MID User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DME D310 T2 MID User manual

LOVATO ELECTRIC DME D330MID User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DME D330MID User manual

LOVATO ELECTRIC DME D111 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DME D111 User manual

LOVATO ELECTRIC DME D305T2 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DME D305T2 User manual

LOVATO ELECTRIC DME D130 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DME D130 User manual

LOVATO ELECTRIC EXS4000 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC EXS4000 User manual

LOVATO ELECTRIC EXP10 04 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC EXP10 04 User manual

LOVATO ELECTRIC DMG900L01 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DMG900L01 User manual

LOVATO ELECTRIC DMK 15 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DMK 15 User manual

LOVATO ELECTRIC DMG600 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DMG600 User manual

LOVATO ELECTRIC DME D300T2 User manual

LOVATO ELECTRIC

LOVATO ELECTRIC DME D300T2 User manual

Popular Measuring Instrument manuals by other brands

Minebea MIS-202-PT instruction manual

Minebea

Minebea MIS-202-PT instruction manual

Bartec SYSCOM ROCK user manual

Bartec

Bartec SYSCOM ROCK user manual

Thermokon LCF02 5DO RS485 Modbus manual

Thermokon

Thermokon LCF02 5DO RS485 Modbus manual

PCB Piezotronics 354C02 Installation and operating manual

PCB Piezotronics

PCB Piezotronics 354C02 Installation and operating manual

RFL 904 instructions

RFL

RFL 904 instructions

DENT Instruments ELITEpro ELOG 15 quick start guide

DENT Instruments

DENT Instruments ELITEpro ELOG 15 quick start guide

Hilti PR 2-HS A12 instructions

Hilti

Hilti PR 2-HS A12 instructions

Hach HIAC 9705 Operator's manual

Hach

Hach HIAC 9705 Operator's manual

ProMinent DULCOMETER D2C operating instructions

ProMinent

ProMinent DULCOMETER D2C operating instructions

Zip ASSIST WiFi Installation and service manual

Zip

Zip ASSIST WiFi Installation and service manual

Chauvin Arnoux Y4N user manual

Chauvin Arnoux

Chauvin Arnoux Y4N user manual

daviteq MBRTU-TBD user guide

daviteq

daviteq MBRTU-TBD user guide

Omega DP41-B Series Operation manual

Omega

Omega DP41-B Series Operation manual

sauermann MP 210 user manual

sauermann

sauermann MP 210 user manual

Tektronix Keithley 4200A-SCS-PKA quick start guide

Tektronix

Tektronix Keithley 4200A-SCS-PKA quick start guide

Keysight B2980B Series user guide

Keysight

Keysight B2980B Series user guide

ETAS MDA V8.5 user guide