Lovato DME D120 T1 User manual

I331 GB I 08 18 31100158
1
LOVATO ELECTRIC S.P.A.
24020 GORLE (BERGAMO) ITALIA
VIA DON E. MAZZA, 12
TEL. 035 4282111
FAX (Nazionale): 035 4282200
FAX (International): +39 035 4282400
E-mail info@LovatoElectric.com
Web www.LovatoElectric.com
DME D120 T1
WARNING!
– Carefully read the manual before the installation or use.
– This equipment is to be installed by qualified personnel, complying to current standards, to avoid
damages or safety hazards.
– Remove eventual dangerous voltage from the product before any maintenance operation on it.
– The manufacturer cannot be held responsible for electrical safety in case of improper use of the
equipment.
– Products illustrated herein are subject to alteration and changes without prior notice. Technical data
and descriptions in the documentation are accurate, to the best of our knowledge, but no liabilities for
errors, omissions or contingencies arising therefrom are accepted.
– A circuit breaker must be included in the electrical installation of the building. It must be installed
close by the equipment and within easy reach of the operator.
It must be marked as the disconnecting device of the equipment: IEC /EN 61010-1 § 6.11.
– Fit the instrument in an enclosure or cabinet with minimum IP51 degree protection.
– Clean the instrument with a soft dry cloth, do not use abrasives, liquid detergents or solvents.
INDEX PAGE
Introduction ........................................................................................................................................ 1
Description .......................................................................................................................................... 1
Selection of readings........................................................................................................................... 2
Metrological LED................................................................................................................................. 2
Energy flow indication........................................................................................................................ 2
Programmable static output................................................................................................................ 2
Incorrect wiring indication................................................................................................................... 2
Navigation with front key ................................................................................................................... 2
Advanced functions............................................................................................................................. 3
Parameter setting (setup).................................................................................................................... 4
Setup parameter table ......................................................................................................................... 4
Mechanical dimensions (mm) ............................................................................................................. 5
Wiring diagrams.................................................................................................................................. 5
Technical characteristics...................................................................................................................... 6
INTRODUCTION
The DME D120T1 is a single-phase active and reactive energy meter for direct connection, for currents
up to 63A.
The energy accuracy is compliant with reference standard IEC/EN 62053-21 Class 1.
Apart from energy metering, it can measure additional indications, for a total of 14 measurements that
can be visualized on the large backlighted LCD display.
The DME D120 T1 has a standard 2U (36mm wide) modular housing and is supplied with sealable
terminal blocks.
DESCRIPTION
– Modular DIN-rail housing, 2U (36mm wide)
– Direct connection for currents up to 63A
– Active energy measure complies IEC/EN 62053-21 Class 1
– LCD display with backlight
– Counter with 6+1 digits
– Button for measure selection and programming
– Total active and reactive energy meters
– Partial active and reactive energy meters, resettable
– Hour counter, total and partial
– Pulse LED for active energy consumption
– Indication of instantaneous consumption (active power)
– Programmable static output, for pulse or alarm threshold.
ATTENZIONE!!
– Leggere attentamente il manuale prima dell’utilizzo e l’installazione.
– Questi apparecchi devono essere installati da personale qualificato, nel rispetto delle vigenti normative
impiantistiche, allo scopo di evitare danni a persone o cose.
– Prima di qualsiasi intervento sull’apparecchio, rimuovere eventuali tensioni pericolose
dall’apparecchio
– Il costruttore non si assume responsabilità in merito alla sicurezza elettrica in caso di utilizzo
improprio del dispositivo.
– I prodotti descritti in questo documento sono suscettibili in qualsiasi momento di evoluzioni o di
modifiche. Le descrizioni ed i dati a catalogo non possono pertanto avere alcun valore contrattuale.
– Un interruttore o disgiuntore va compreso nell’impianto elettrico dell’edificio. Esso deve trovarsi in
stretta vicinanza dell’apparecchio ed essere facilmente raggiungibile da parte dell’operatore. Deve
essere marchiato come il dispositivo di interruzione dell’apparecchio: IEC/ EN 61010-1 § 6.11.
– Installare lo strumento in contenitore e/o quadro elettrico con grado di protezione minima IP51.
– Pulire lo strumento con panno morbido, non usare prodotti abrasivi, detergenti liquidi o solventi.
INDICE PAGINA
Introduzione ........................................................................................................................................ 1
Descrizione ......................................................................................................................................... 1
Selezione misure ................................................................................................................................. 2
LED metrologico.................................................................................................................................. 2
Indicazione flusso energia ................................................................................................................... 2
Uscita statica programmabile.............................................................................................................. 2
Indicazione collegamento errato.......................................................................................................... 2
Navigazione tramite tasto frontale ....................................................................................................... 2
Funzioni avanzate ................................................................................................................................ 3
Impostazione parametri (setup) .......................................................................................................... 4
Tabella parametri di setup ................................................................................................................... 4
Dimensioni meccaniche (mm)............................................................................................................. 5
Schemi di collegamento ...................................................................................................................... 5
Caratteristiche tecniche ....................................................................................................................... 7
INTRODUZIONE
Il DME D120T1 è un contatore di energia monofase per inserzione diretta, per correnti fino a 63A.
La misurazione dell’energia è conforme alla norma IEC/EN 62053-21 classe 1.
Oltre alla misurazione dell’energia, è in grado di fornire ulteriori indicazioni, per un totale di 14 misure,
che possono essere visualizzati sull’ampio display LCD retroilluminato.
Il DME D120 T1 ha un contenitore modulare standard di larghezza 2U (36 mm) ed è fornito di serie di
coprimorsetti piombabili.
DESCRIZIONE
– Esecuzione modulare 2U (36mm) per guida DIN.
– Inserzione diretta per correnti max 63A.
– Misura energia attiva conforme a IEC/EN 62053-21 classe 1.
– Display LCD retroilluminato.
– Contatore con 6+1 cifre.
– Tasto per la selezione delle misure e programmazione.
– Contatori di energia attiva e reattiva totali.
– Contatori di energia parziali azzerabili.
– Contaore totale e parziale.
– LED frontale a impulsi per energia attiva consumata.
– Indicazione consumo istantaneo (potenza attiva).
– Uscita statica programmabile per impulsi o soglia di allarme.
SINGLE-PHASE DIRECT CONNECTION ENERGY METER
Instruction manual
GB
CONTATORE DI ENERGIA MONOFASE A INSERZIONE DIRETTA
Manuale operativo
I

I331 GB I 08 18 31100158
2
SELECTION OF READINGS
– Pressing briefly the button it is possible to select the readings on the display, following the
sequence in the table reported below.
– Each measure is indicated by the correspondent icon in the lower part of the display.
– After one minute has elapsed after the last keystroke, the display moves automatically back to the
total active energy screen.
These measurements are shown only enabling parameter P-08
These measurements are shown only enabling parameter P-09
METROLOGICAL LED
– The red LED on the front emits 1000 pulses for every kWh of consumed Energy (that is, one pulse
every Wh).
– The pulsing frequency of the LED gives an immediate indication of the energy flowing in every
moment.
– The pulse duration, LED colour and intensity are compliant with the reference standards that define its
utilization in order to verify the accuracy of the energy meter.
ENERGY FLOW INDICATION
– When the device detects a flow of active energy to the load, it shows a rotating icon in the top-right
part of the display.
– When there is no active energy consumption or when the load draws less than the starting current
the rotating icon disappears.
PROGRAMMABLE INSULATED STATIC OUTPUT
– The static output on the upper terminals can be used either as a pulse output or as a measure
threshold output.
– The connection can be done in PNP or NPN mode. See schematic diagrams and technical
characteristics for details on the wiring and on the rating.
– The activation of the static output is shown on the display through the icon.
– When the output is programmed as a pulse generator, it allows connecting the energy meter to:
• An external data concentrator (like DME CD)
• A remote electromechanical counter
• A PLC or other device
– When it works as an alarm threshold, it can be used for:
• Disconnection of non-priority loads
• Alarm signalling
NOTE: During parameter setting (setup) the status of the static output is not updated.
INCORRECT WIRING INDICATION
– In case of incorrect wiring, when the device detects a reverse energy flow, the display shows the
blinking code Err 3.
– This error is caused by either reverse connection of current wires (terminals L↑and L↓) or reverse
voltage wiring (terminals N - L↑).
– In these conditions, the energy is not counted.
NAVIGATION WITH FRONT KEY
– To move through menus use the following rules:
– A short click of the front button, indicated by , changes the present selection, shown on the
display, with a new one (the following).
– Pressing the button for a long time (> 3s), that is indicated with symbol , is used to confirm the
present selection.
– Symbol indicates when the user must wait for the display to move to a new selection.
– To quit a menu, select the --ESC-- option.
1
Queste misure sono visibili solo abilitando il parametro P-08
Queste misure sono visibili solo abilitando il parametro P-09
LED METROLOGICO FRONTALE
– Il LED rosso frontale emette 1000 impulsi per ogni kWh di energia consumata (ovvero 1 impulso per
ogni Wh).
– La frequenza di lampeggio del LED dà una immediata indicazione dell’entità della potenza richiesta in
un determinato istante.
– La durata del lampeggio, il colore e l’intensità del LED sono conformi alle norme che prescrivono il
suo utilizzo ai fini di una verifica metrologica della accuratezza dell’energy meter.
INDICAZIONE FLUSSO DI ENERGIA
– Quando lo strumento sta rilevando un flusso di energia verso il carico, il display visualizza nell’angolo
in alto a destra una icona rotante.
– Quando il carico non richiede energia attiva oppure quando la corrente assorbita è inferiore alla
corrente di avviamento, l’icona rotante scompare.
USCITA STATICA ISOLATA PROGRAMMABILE
– L’uscita statica disponibile sui morsetti superiori può essere utilizzata sia come uscita ad impulsi che
abbinata ad una soglia.
– Il collegamento può essere effettuato in modo PNP o NPN. Vedere schemi di collegamento e
caratteristiche tecniche per dettagli sulla portata.
– L’attivazione dell’uscita statica è visualizzata tramite l’icona sul display.
–
Quando l’uscita statica è configurata come generatore di impulsi consente di collegare l’energy meter a:
• un concentratore dati esterno (tipo DME CD)
• un contatore elettromeccanico remoto
• un PLC o altra apparecchiatura
– Quando invece lavora abbinata ad una soglia, può essere utilizzata:
• per scollegare carichi non prioritari
• per segnalazioni di allarme
NOTA: Durante l’impostazione dei parametri (Setup) lo stato dell’uscita statica non viene aggiornato.
INDICAZIONE DI COLLEGAMENTO ERRATO
– In caso di collegamento errato, quando l’apparecchio rileva un flusso di energia di direzione contraria,
viene attivata l’indicazione lampeggiante Err 3.
–
Questo errore può essere provocato dalla inversione del collegamento della corrente (morsetti L↑e L↓)
oppure dalla inversione dei morsetti della tensione (N - L↑).
– In queste condizioni l’energia non viene conteggiata.
NAVIGAZIONE TRAMITE TASTO FRONTALE
– Per muoversi fra i menu si usano le seguenti regole:
– Una breve pressione del tasto frontale, che indicheremo con , viene utilizzata per cambiare la
selezione attualmente visualizzata con una diversa, successiva.
– Una pressione prolungata (> 3s), che indicheremo con , viene invece utilizzata per confermare la
selezione visualizzata.
– Il simbolo indica quando è necessario attendere perché il display proponga una nuova scelta.
– Per uscire da un menu, selezionare --ESC--.
1
Icon Measure Format
kWh Total active energy 000000,0
kWh + Part Partial active energy 000000,0
kvarh Total reactive energy 000000,0
kvarh + Part Partial reactive energy 000000,0
VVoltage 000,0
ACurrent 00,00
kW Active power 00,00
kvar Reactive power 00,00
PF Power factor 0,00
Hz Frequency 00,0
hHour counter (hhhhh.mm) 00000,00
h + Part Partial hour counter (hhhhh.mm) 00000,00
kW +d Average active power (15 min demand) 00,00
kW+d+ Max avg. active power (max demand) 00,00
SELEZIONE MISURE
– Premendo brevemente il pulsante è possibile selezionare le misure sul display dello strumento,
secondo la sequenza indicata nella tabella riportata sotto.
– A ciascuna selezione corrisponde un’icona nella parte bassa del display, con l’unità di misura
selezionata.
– Dopo un minuto senza premere il pulsante frontale, la misura si riposiziona sul contatore totale di
energia attiva.
Icona Misura Formato
kWh Energia attiva totale 000000,0
kWh + Part Energia attiva parziale 000000,0
kvarh Energia reattiva totale 000000,0
kvarh + Part Energia reattiva parziale 000000,0
VTensione 000,0
ACorrente 00,00
kW Potenza attiva 00,00
kvar Potenza reattiva 00,00
PF Fattore di potenza 0,00
Hz Frequenza 00,0
hContaore (hhhhh.mm) 00000,00
h + Part Contaore parziale (hhhhh.mm) 00000,00
kW +d Potenza attiva media (demand su 15 min) 00,00
kW+d+ Max potenza attiva media (max demand) 00,00

I331 GB I 08 18 31100158
3
ADVANCED FUNCTIONS
– To access the advanced functions, use the following procedure:
1. Starting from any visualization screen, press . If the password protection is disabled (factory
default, password = 0000), display jumps directly to point 4, otherwise it will show PASS to inform
that the access code must be entered first.
2. Release the button. The display now waits for the password and indicates 0000. The single digits are
flashing sequentially. Pressing while a digit is flashing, that digit is incremented. Waiting for
some seconds, the selection moves to the next digit. After having entered the right password code,
press to confirm.
3. If the entered password is wrong, the display shows PASS Er and goes back to normal visualization.
If instead the code is correct, it proceeds to next point.
FUNZIONI AVANZATE
– Per accedere alle funzioni avanzate utilizzare la seguente procedura:
1. Partendo da una qualsiasi visualizzazione, premere . Se la protezione da password è disattivata
(default di fabbrica, password = 0000) il display salta direttamente al punto 4, altrimenti indica PASS
per evidenziare la necessità di inserire la password.
2. Rilasciare il tasto. Il display ora attende l’inserimento della password e indica 0000. Le singole cifre
lampeggiano a rotazione. Premendo mentre una cifra sta lampeggiando, essa viene
incrementata. Attendendo qualche secondo, la cifra successiva inizia a lampeggiare. Dopo avere
inserito la password premere il tasto per confermare.
3. Se la password inserita non è corretta il display mostra PASS Er e torna alla visualizzazione
normale. Se invece è corretta, si passa al punto successivo.
4. The display shows the first item of the following list. To move through the list, click
• CLEAR P = clearing of partial energy meters
• CLEAR h = clearing of partial hour counter (if enabled)
• CLEAR d = clearing of max demand values (if enabled)
• SETUP = parameter programming (setup)
• INFO = revision and checksum of internal software
• --ESC-- = returns to normal operation
5. To select a function, press while the required function is displayed.
6. If the button is never pressed for 60 consecutive seconds, the display goes back automatically to
normal operation.
LOST OR FORGOTTEN PASSWORD
If password is lost or forgotten, after three consecutive faulty attempts to enter the password, the display
reporting this unlock code. The right password will be provided. The user is then free to change setting it
as required in the usual way (parameter P.01).
4. Il display indica la prima delle scelte nella seguente lista. Per passare da una scelta alla successiva
premere
• CLEAR P = azzeramento contatori di energia parziali
• CLEAR h = azzeramento contaore parziale (se abilitato)
• CLEAR d = azzeramento max demand (se abilitato)
• SETUP = programmazione parametri
• INFO = revisione software e checksum interno
• --ESC-- = ritorno al funzionamento normale
5. Per selezionare una funzione premere mentre viene visualizzata la funzione desiderata.
6. Se non vengono premuti tasti per 60 secondi l’apparecchio ritorna automaticamente al funzionamento
normale.
PASSWORD DIMENTICATA O PERSA
Se la password viene dimenticata o persa, dopo tre tentativi consecutivi di inserimento password non
corretta, il display visualizza un codice di sblocco di 6 cifre. Contattare l’ufficio Customer Service Lovato
password per l’accesso. L’utente è poi libero di re-impostarla a piacimento (tramite il parametro P.01).
Password entry
Inserimento password
Advanced functions
Funzioni avanzate
1

I331 GB I 08 18 31100158
4
PARAMETER SETTING (SETUP)
– While display is showing SETUP, press .
– The display shows the first parameter code P-01.
– Short-click to move to next parameters P-02, P-03… etc use .
– When the display indicates the code of the parameter that needs to be modified, press .
• If it is a numeric parameter (password, thresholds, delays) the display shows its present value.
The single digits are flashing sequentially. Pushing while a digit is flashing, that digit is
incremented. Waiting for some seconds, the selection moves to the next digit.
• If instead the parameters provides selection among different functions (e.g. output functions,
measure etc), pressing it is possible to sequentially select the desired one.
• Confirm with to go back to parameter code selection.
– After last parameter code, display shows --ESC--. Pressing button in this moment, parameters
are saved and system goes back to normal operation.
IMPOSTAZIONE PARAMETRI (SETUP)
– Con il display che indica SETUP, premere .
– Il display indica il codice del primo parametro P-01.
– Per selezionare i parametri successivi P-02, P-03 … usare .
– Quando il display indica il codice del parametro che si desidera modificare, premere .
• Se si tratta di un parametro numerico (password, soglie, ritardi), il display indica il valore attuale
dell’impostazione del parametro. Le singole cifre lampeggiano a rotazione. Premendo mentre
una cifra sta lampeggiando, essa viene incrementata. Attendendo, comincia a lampeggiare la cifra
successiva.
• Se invece il parametro prevede la scelta fra diverse opzioni (funzione uscita, misura) premendo
si può selezionare a rotazione la funzione voluta.
• Confermando con si può tornare alla selezione parametri.
– Dopo l’ultimo codice parametro il display visualizza --ESC--. Premendo il tasto in questo
momento, i parametri vengono salvati e si torna al funzionamento normale.
Code Description Default Range
P-01 Password 0000 0000 - 9999
P-02 Output function 10 PUL / 1000 PUL - 100 PUL -
kWh 10 PUL - 1 PUL - THR
P-03 Threshold measure kW 01=kW - 02=kvar - 03=V
04=A - 05=Hz - 06=kWh Part
07=h Part – 08 kW demand
P-04 ON threshold 100.00 0.00 – 999.99
P-05 ON delay 5 s 0 – 9999 sec.
P-06 OFF threshold 50.00 0.00 – 999.99
P-07 OFF delay 5 s 0 – 9999 sec.
P-08 Hour counter enable OFF OFF-ON-THR
P-09 Enable demand measures OFF OFF-ON
SETUP PARAMETER TABLE
P-01 – If set to 0000 (default) the password protection is disabled.
P-02 – Defines the function of the static output from the following list:
100 PUL …1 PUL – Static outputs operates as a pulse emitter for active energy count. These
selections define the number of pulses sent for every kWh.
THR - The static output becomes an alarm threshold for maximum or minimum limit, depending on
values programmed in P-04 and P-06.
If P-04 > P-06, then output activates when the measure defined by P-03 is higher than P-04, end de-
activates when its value becomes less than P-06 (maximum limit with hysteresis.
If P-04 < P-06, then output activates when the measure defined by P-03 is lower than P-04, end activates
when its value becomes higher than P-06 (minimum limit with hysteresis).
P-03 – Selection of measure to compare with thresholds.
P-04 e P-05 – Threshold and delay for output activation. Note: The measurements are updated every 1
second, that means that the variability of this delay is in the range from 0 to + 1 second.
P-06 e P-07 – Threshold and delay for output de-activation.
P-08 – Defines the hor counter operation:
OFF – hour counter disabled. It is not shown on the display.
ON – The hour counter is incremented as long as the energy meter is supplied.
THR – The hour counter is incremented as long as the threshold defined with previous parameter ( P-02,
P-03, P-04 e P-05) is active.
P-09 – Enable of calculation and visualization of active energy demand and max demand.
Code Description Default Range
P-01 Password 0000 0000 - 9999
P-02 Scelta funzione uscita 10 PUL / 1000 PUL - 100 PUL -
kWh 10 PUL - 1 PUL - THR
P-03 Misura per soglia kW 01=kW - 02=kvar - 03=V
04=A - 05=Hz - 06=kWh Part
07=h Part – 08 kW demand
P-04 Soglia ON 100.00 0,00 – 999,99
P-05 Ritardo soglia ON 5 sec. 0 – 9999 sec.
P-06 Soglia OFF 50.00 0,00 – 999,99
P-07 Ritardo soglia OFF 5 sec. 0 – 9999 sec.
P-08 Abilitazione contaore OFF OFF-ON-THR
P-09 Abilitazione misure demand OFF OFF-ON
TABELLA PARAMETRI DI SETUP
P-01 – Se impostato a 0000 (default) la protezione da password è disabilitata.
P-02 – Definisce la funzione dell’uscita statica programmabile:
100 PUL …1 PUL – L’uscita statica funziona come emettitore di impulsi per il conteggio dell’energia
attiva. Con queste selezioni si definisce il numero di impulsi per per ogni kWh.
THR - programma l’uscita come soglia di allarme di massima oppure di minima, a seconda dei valori
impostati in P-04 e P-06.
Se P-04 > P-06, allora l’uscita si attiva con la misura di P-03 > P-04, e si disattiva quando ritorna ad
essere < P-06 (funzione di soglia massima con isteresi).
Se P-04 < P-06, allora l’uscita si attiva con la misura di P-03 < P-04, e si disattiva quando ritorna ad
essere > P-06 (funzione di soglia minima con isteresi).
P-03 – Selezione misura alla quale vengono applicate le soglie.
P-04 e P-05 – Soglia e relativo ritardo per attivazione uscita. Nota: le misure vengono aggiornate ed
integrate 1 volta al secondo, quindi questo ritardo ha una variabilità da 0 a + 1 secondo.
P-06 e P-07 – Come sopra, per disattivazione uscita.
P-08 – Definisce il funzionamento del contaore:
OFF – Contaore disabilitato, non viene visualizzato.
ON – Il contaore si incrementa fintanto che l’energy meter è alimentato.
THR – Il contaore si incrementa fintanto che la soglia definita con i parametri precedenti ( P-02, P-03,
P-04 e P-05) è attivata.
P-09 – Abilitazione misura e visualizzazione potenza attiva integrata attuale e massima (max demand).
Parameter programming (Setup)
Impostazione parametri (Setup)
2

I331 GB I 08 18 31100158
5
MECHANICAL DIMENSIONS [mm]
543.7
63
35.8
90
44.7
92.5
DIMENSIONI MECCANICHE [mm]
WIRING DIAGRAMS
O1-O1+
Static output
30VDC 50mA max
LL
N
O1-O1+
L
LOAD
N
L
LINE
N
LL
NO1+ O1-
LL
O1+
NO1-
_
NPN out
+
PNP out
SCHEMI DI COLLEGAMENTO

I331 GB I 08 18 31100158
GB
Insulation
Rated insulation voltage Ui 250V
Rated impulse withstand voltage Uimp 6kV
Power frequency withstand voltage 4kV
Connections
Type of terminals Screw (fixed)
Number of terminals 3 for Aux supply / measure
Conductor cross section (min… max) 2.5 - 16 mm2(see below for AWG)
Tightening torque 2 - 2.2 Nm (26.5lbin)
Pulse output connections
Type of terminals Screw (fixed)
Number of terminals 2
Conductor cross section (min… max) 0.5 - 4 mm2(20-10 AWG)
Tightening torque 1.3 Nm (12.1lbin)
Housing
Version 2 modules (DIN 43880)
Mounting 35mm DIN rail (IEC/EN 60715)
or by screw using extractible clips
Material Polyamide RAL 7035
Degree of protection IP40 on front
IP20 terminals
Weight 148 g
Certifications and compliance
Certifications cULus, EAC, RCM
UL marking Supply/measure connections AWG Range: (14 - 6 AWG - stranded)
(14 - 10 AWG - solid)
Field wiring terminals tightening torque: (26.5lb.in)
Pulse output connections AWG range: (20 - 10AWG)
Field wiring terminals tightening torque: (12.1lb.in)
Comply with standards IEC/EN 61010-1, IEC/EN 61010-2-030, EN 50470-1,
UL 61010-1, CSA C22.2 n° 61010-1
To comply with the protection requirements the meter must be mounted in a class IP51 enclosure or better.
(IEC/EN 60529).
TECHNICAL CHARACTERISTICS
Standard version
Rated voltage Us 220 - 240V
Operating voltage range 187 - 264V
Rated frequency 50 - 60Hz
Operating frequency range 45 - 66Hz
Power consumption/dissipation 7VA / 0.45W
A120 version
Rated voltage Us 110 - 120V
Operating voltage range 93 - 132V
Rated frequency 60Hz
Operating frequency range 54 - 66Hz
Power consumption/dissipation 7VA / 0.45W
Current
Minimum current (Imin) 0.5A
Transition current (Itr) 1A
Reference current (Iref - Ib) 10A
Max current (Imax) 63A
Start current (Ist) 40 mA
Accuracy
Active energy (IEC/EN 62053-21) Class 1
LED pulse
Integration constant 1000 pulses / kWh
Pulse length 30ms
Static output
Number of pulses Programmable 1-10-100-1000 pulses / kWh
Pulse length 100ms
External voltage 10 - 30VDC
Max current 50mA
Ambient conditions
Mounting Indoor use only
Operating temperature -25...+55°C
Storage temperature -25...+70°C
Relative humidity <80% non-condensing (IEC/EN 60068-2-78)
Maximum pollution degree 2
Overvoltage category III
Altitude ≤2000m
Climatic sequence Z/ABDM (IEC/EN 60068-2-61)
Shock resistance 10g (IEC/EN 60068-2-27)
Vibration resistance 0.7g (IEC/EN 60068-2-6)
Mechanical environment Class M1
Electromagnetic environment Class E1
6

I331 GB I 08 18 31100158
I
Isolamento
Tensione nominale d’isolamento Ui 250V
Tensione nominale di tenuta a impulso Uimp 6kV
Tensione di tenuta a frequenza d’esercizio 4kV
Connessioni
Tipo di morsetti A vite (fissi)
N° morsetti 3 per alimentazione / misura
Sezione conduttori (min e max) 2,5 - 16 mm2(vedi sotto per AWG)
Coppia di serraggio morsetti 2 - 2,2 Nm (26,5lbin)
Connessioni uscita impulsi
Tipo di morsetti A vite (fissi)
N° morsetti 2
Sezione conduttori (min e max) 0,5 - 4 mm2(20-10 AWG)
Coppia di serraggio morsetti 1,3 Nm (12,1lbin)
Contenitore
Esecuzione 2 moduli (DIN 43880)
Montaggio Guida 35mm (IEC/EN 60715)
o a vite a mezzo clip estraibili
Materiale Poliammide RAL 7035
Grado di protezione IP40 sul fronte
IP20 connessioni
Peso 148 g
Omologazioni e conformità
Omologazioni cULus, EAC, RCM
UL marking Supply/measure connections AWG Range: (14 - 6 AWG - stranded)
(14 - 10 AWG - solid)
Field wiring terminals tightening torque: (26.5lb.in)
Pulse output connections AWG range: (20 - 10AWG)
Field wiring terminals tightening torque: (12.1lb.in)
Conformi a norme IEC/EN 61010-1, IEC/EN 61010-2-030, EN 50470-1,
UL 61010-1, CSA C22.2 n° 61010-1
Per garantire la protezione richiesta, lo strumento deve essere installato in contenitore con grado di protezione minimo
IP51 (IEC/EN 60529).
CARATTERISTICHE TECNICHE
Versione standard
Tensione nominale Us 220 - 240V
Limiti di funzionamento 187 - 264V
Frequenza nominale 50 – 60Hz
Limiti di funzionamento 45 - 66Hz
Potenza assorbita/dissipata 7VA / 0,45W
Versioni A120
Tensione nominale Us 110 - 120V
Limiti di funzionamento 93 - 132V
Frequenza nominale 60Hz
Limiti di funzionamento 54 - 66Hz
Potenza assorbita/dissipata 7VA / 0,45W
Corrente
Corrente minima (Imin) 0,5A
Corrente di transizione (Itr) 1A
Corrente di riferimento (Iref - Ib) 10A
Corrente massima (Imax) 63A
Corrente di start (Ist) 40 mA
Accuratezza
Energia attiva (IEC/EN 62053-21) Classe 1
Impulso LED
Costante di integrazione 1000 imp / kWh
Durata impulso 30ms
Uscita statica
Numero di impulsi Progr. 1-10-100-1000 impulsi / kWh
Durata impulso 100ms
Tensione esterna 10 - 30VDC
Corrente massima 50mA
Condizioni ambientali
Installazione Solo per uso interno
Temperatura di impiego -25...+55°C
Temperatura di stoccaggio -25...+70°C
Umidità relativa <80% non condensante (IEC/EN 60068-2-78)
Grado di inquinamento ambiente massimo 2
Categoria dì sovratensione III
Altitudine ≤2000m
Sequenza climatica Z/ABDM (IEC/EN 60068-2-61)
Resistenza agli urti 10g (IEC/EN 60068-2-27)
Resistenza alle vibrazioni 0,7g (IEC/EN 60068-2-6)
Ambiente meccanico Classe M1
Ambiente elettromagnetico Classe E1
7
Table of contents
Other Lovato Measuring Instrument manuals

Lovato
Lovato DME D122MID User manual

Lovato
Lovato DMG110 User manual

Lovato
Lovato DME D120 T1 MID User manual

Lovato
Lovato DMED301 User manual

Lovato
Lovato DMED301MID User manual

Lovato
Lovato DMG900 User manual

Lovato
Lovato DMG7000 User manual

Lovato
Lovato DMG900 User manual

Lovato
Lovato DME D305T2MID User manual

Lovato
Lovato DME D111 MID User manual
Popular Measuring Instrument manuals by other brands

SUTO
SUTO S 120 Instruction and operation manual

Chauvin Arnoux
Chauvin Arnoux F205 Start guide

ASM
ASM NMG2 Installation and operation manual

Raytech
Raytech Micro Junior 2 instruction manual

WAGNER
WAGNER TITANUS SUPER-SENS Technical manual

RKC INSTRUMENT
RKC INSTRUMENT LE100 Communication instruction manual