Lumel N32P User manual

N32P-09 User's manual 1
DIGITAL PANEL METER
N32P
SERVICE MANUAL

N32P-09 User's manual 2
Contents
1 Application.......................................................................................................................................3
2 Meter set...........................................................................................................................................5
3 Basic requirements, operational safety.............................................................................................5
4 Installation........................................................................................................................................6
4.1 Installation method...................................................................................................................6
4.2 xternal connection diagram....................................................................................................7
5 Service............................................................................................................................................10
5.1 Description of the frontal plate...............................................................................................10
5.2 Buttons' functions...................................................................................................................12
5.3 Programming meter parameters..............................................................................................13
5.3.1 How to change quantity of a selected parameter............................................................15
5.3.2 Programmable meter parameters, default parameters.....................................................16
5.4 Meter functions.......................................................................................................................22
5.4.1 Measurement...................................................................................................................22
5.4.1.1 Averaging the measuring quantities.........................................................................23
5.4.1.2 Minimum and maximum measuring values............................................................24
5.4.2 Analog output..................................................................................................................25
5.4.3 Alarm outputs..................................................................................................................26
5.4.4 Binary output...................................................................................................................27
5.5 RS-485 interface.....................................................................................................................28
5.5.1 Connection......................................................................................................................28
5.5.2 Description of the MODBUS protocol implementation.................................................29
5.5.3 Implemented functions of MODBUS protocol...............................................................29
5.5.4 Map of the registers.........................................................................................................30
5.5.4.1 Registers 3000 – 3127.............................................................................................30
5.5.4.2 Registers 4000 – 4054.............................................................................................31
5.5.4.3 Registers 4200 – 4261.............................................................................................36
5.5.4.4 Registers 7500 – 7559 and 7000 – 7119.................................................................38
5.5.4.5 Registers 7600 – 7677 and 7200 – 7355.................................................................40
6 rror codes......................................................................................................................................41
7 Technical data.................................................................................................................................42
8 Ordering code.................................................................................................................................45

N32P-09 User's manual 3
1 Application
The N32P meter is a digital panel meter adapted to be fixed to the panel. The N32P
meters are designed to measure voltage, current, power and energy in A circuits. Voltage
and current measurement can be dome directly or using an external current and voltage
transformers. The parameters of the transformers used can be configured in the N32P
meter, so the indicated measuring values will correspond to the actual measuring values
on the primary of the transformers. The N32P meters also enable to measure only a single
parameter, e.g. only current, where the meter operation is synchronized with the current
signal waveform.
Additionally, the meter supports the programmable alarms with the delay activation and
deactivation function as well as a memory of the alarm event. The functionality of the
meter is complemented by a programmable analog output - RS-485 interface.
The user interface consists four buttons and the high contrast L D display with backlight.
Thanks to the two-line display, it is possible to set the selected unit, display simultaneously
the measuring value and the current time, as well as a clear and user friendly menu with
simultaneously visible the parameter name and its value.
Features of the N32P meter:
•Wide range of measured voltages.
•Programmable current range of 1 A or 5 A.
•Possibility to synchronize the zero crossing detector with the current signal.
•High sampling frequency of the measuring signals.
•Wide measuring ranges including high peak of the current values and large values
of exceeding the measuring range.
•Programmable parameters of external current and voltage transformers.
•Galvanic separation between the voltage measurement and the current
measurement circuits.
•Measurement of voltage and current harmonics.
•High contrast L D display with built-in backlight.
•Two-line display.
•Automatic selection of the unit of the measured (displayed) value.
•Measuring value preview mode.
•Possibility to simultaneously display two selected measuring quantities or a
measuring quantity and e.g. a unit or time.

N32P-09 User's manual 4
•Programmable display precision with the function of automatic setting of the
decimal point and the multiplier (kilo, mega) displayed with the unit.
•Possibility to program the measuring range (narrowing) for the selected displayed
value.
•Additional measurement of minimum and maximum values during the moving
window, with the possibility of programming one of these values to be displayed as
the main one.
•Selection of the period and averaging method with the possibility of synchronizing
the average value with the built-in real-time clock.
•Programmable alarms with the functions of programmable delays of alarm
activation and deactivation, triggered by a specific controlling value. Up to 4 relays,
including up to 3 relays with a switching contact. Possibility to configure each of the
alarms to work in a selected mode and to react to any measuring quantity including
the current time.
•Possibility to control the alarm outputs (relay) via the RS-485 interface.
•Programmable standard analog outputs enabling the retransmission of a selected
measuring quantity or a selected parameter. Freely programmable output type and
conversion range.
•Built-in by default RS-485 interface with MODBUS RTU protocol support.
•Built-in real-time clock with a built-in automatic change of DST and inversely. The
clock can be a parameter which controls the alarms and the value of the analog
output signal.
•Possibility to password protect the settings against unauthorized modification.
•Monitoring of set parameters.
•Programmed averaging time - averaging algorithm in a specified time using
standard averaging (determining the number of measurements to be averaged) and
averaging based on the moving window algorithm with a given averaging time.
•Signaling of alarm operation by highlighting the number of the active alarm.
•Registration of minimum and maximum measuring values.
•Galvanic separation of the connections: alarm, measurement, analog outputs,
auxiliary supply outputs, RS-485 interface and supplying input.
•Protection degree from the front IP65.
•Meter overall dimensions 96 x 48 x 100 (with the terminals).

N32P-09 User's manual 5
•The casing is made of a self-extinguishing plastics.
•Wide range of supply voltages.
The view of the N32P meter is shown in Fig. 1.
2 Meter set
The meter set includes:
•Meter N32P – 1 pc
•User's manual – 1 pc
•lamps to fix in the panel – 4 pcs
•Seal – 1 pc
3 Basic requirements, operational safety
In terms of a user safety, the N32P meter meets the requirements of the EN61010-1
standard for the devices intended for use in facilities compliant with the third category of
installations.
Comments concerning safety
•Assembly and installation of the electrical connections should conducted only by a
person authorised and certificated to perform assembly of electric devices.
•Always check the connections before turning the meter on.
•The meter is designed to installation and usage in the industrial electromagnetic
environment.
•A switch or a circuit-breaker should be installed in the building or facility. The switch
Fig. 1: View of the N32P meter.

N32P-09 User's manual 6
should be located near the device, easily accessible by the operator and suitably
marked.
•Removal of the meter electronics during the warranty period voids the warranty.
4 Installation
4.1 Installation method
The N32P meters are designed to be mounted in a panel. Prior to installation a 92 +0.6 x
45+0.6 mm slot must be made in the panel. The maximum thickness of the panel material
cannot exceed 6 mm. The meter should be mounted from the front of the panel with
disconnected meter connection strips.
Before inserting the meter into the panel check the correct position of the meter seal and
make sure that the edges of the panel are not sharp what could damage the seal. After
inserting the meter into the slot, mount it with the mounting brackets provided in the meter
set (Fig. 2).
Electrical connections of the meter should be made with the wires with the cross-section
up to 2.5 mm2. Detachable sockets with the plugs of 5.08 mm pitch can be used for the
connections.
Fig. 2: Meter fi ing.

N32P-09 User's manual 7
The external dimensions of the meter are shown in Fig. 3.
4.2 E ternal connection diagram
The N32P meter has three detachable terminal strips to connect the wires of a cross-
section up to 2.5 mm2. The view of the meter from the connectors' side is shown in Fig. 5.
The upper terminal strip is optional and depends on the accessories of the meter.
The circuits of successive groups of the terminals are separated from each other, as
shown in Fig. 4.
Note: Unused terminals of the terminal strips (NC) must not be connected to any signals.
Fig. 3: Meter overall dimensions.
Fig. 4: Galvanic isolation of the N32P meter.

N32P-09 User's manual 8
Detailed description of the signals is shown in the table below, and the connection of the
measuring signals is shown in Fig. 6.
Terminal Function Description
2, 4, 5, 6 Measuring inputs The measuring inputs for connecting the measuring
voltage and current or for connecting the external
transformers. Examples of the connections are shown in
Fig. 6.
9, 10, 11 RS-485 RS-485 interface signals
12, 13 Alarm 1 Alarm output 1, which is NO relay contact.
15, 16 Power supply Meter power supply connection. Range of supply voltages
supported by the meter depends on the ordering code. It
is required to check if the rated range of the meter
corresponds to the installation to which the meter will be
connected before installing the meter.
Fig. 5: Signals on the terminal strips.

N32P-09 User's manual 9
20…28 Alarms 2, 3, 4
(optional)
The alarm outputs 2, 3 and 4 use a relay with a switching
contact.
30...33 Analog output Analog output. The output must be properly connected
according to the type of output selected in the
configuration (voltage or current): the terminals 30 and 31
for the current output or the terminals 32 and 33 for the
voltage output. It is not possible to use the voltage and
current outputs at the same time - the correct value in
accordance with the configuration, will be available only
for the selected output type.
34, 35 Binary output Open collector binary output. Pulse output of the imported
or exported energy counter.
3, 7, 14,
29
N Unused terminals. Should be left unconnected.
The connection of the basic measured signals is shown below. The N32P meter can also
be used to measure only voltage or only current.
Fig. 6: Connection of the N32P meter,

N32P-09 User's manual 10
5 Service
The N32 meter user interface includes an L D display and the buttons which enable to
display the measuring value, a full configuration and setting of the meter or modification of
the parameters.
After turning the meter on the display shows the name of the meter and the software
version. If there is no error during meter initialization process, the meter will switch to
displaying the measuring value. If during the initialization any irregularities or deviations
are detected, than a message with information about a detected error will be displayed
(see point 6 - Error codes).
5.1 Description of the frontal plate
View of the front panel of the meter is shown in Fig. 6. The L D display with backlight and
4 buttons are on the front panel. The description of the display fields is shown below. The
button functions are shown in the section 5.2.
Designation Description
L1 The upper (main) line of the display has 6 characters used to display a
measuring value or a parameter value during the meter configuration.
L2 The lower (auxiliary) line of the display has 5 characters used to display a
measuring value, not converted by the individual characteristic or,
according to configuration, a unit or current time.
k The kilo symbol means that the displayed value is divided by a thousand,
e.g. when the setting is displayed, the illuminated symbol means that the
given value is a thousand times greater. For example, 1.2 kA means 1200
A.
Z1 Measuring value averaging indicator. Illuminated averaging indicator
informs that the set measuring value averaging period has not elapsed yet.
M The mega symbol means that the displayed value is divided by a million,
e.g. when the setting is displayed, the illuminated symbol means that the
given value is a million times greater. For example, 3.5 MW means
Fig. 7: Front panel of the meter.

N32P-09 User's manual 11
3,500,000 W.
ALI Alarm status field. This field contains the indicator informing about the
alarm status. Illuminated alarm indicator means that an alarm event is in
progress and the relay corresponding to the alarm is activated. Flashing
symbol means that the alarm state is saved (if the alarm memory is
activated).
B1...B4 Meter operation buttons. The description of the button functions and their
various combinations are shown in section 5.2.
The lower line of the display can be configured to display the unit, where the unit is
automatically adapted to the displayed value of measured quantity and depends on set
indication range. For example, if a transformer with a rated range greater than 1000 A is
connected, the current will be displayed in kilo amperes (kA).
Additionally, the lower line can display a selected value of measured quantity (measured or
calculated quantities) or the current time.
5.2 Buttons' functions
Cancel button:
•Exiting the menu and exit to the main screen.
•Exiting a lower level of the menu and return to a higher level.
•anceling changing the set value (when editing the parameter value)
•Entering the measuring value preview mode - hold down the button for
at least 3 seconds.
Digit change button:
•Navigating the menu - decreasing the items of the menu.
•Decreasing the controlled quantity while editing a parameter and
setting selection from the list of settings, e.g. alarm type.
•hanging the controlled digit when setting numerical parameters.
•Pressing the button during a normal operation displays a minimum
value for 2 seconds, then the display returns to displaying a measuring
value.
Increase value button:
•Navigating the menu - increasing the items of the menu.
•Increasing the value of the selected parameter or increasing the value
of a digit when changing the numerical value.
•Pressing the button during a normal operation displays a maximum
value for 2 seconds, then the display returns to displaying a measuring
value.

N32P-09 User's manual 12
Confirm button:
•Entering the programming mode (holding down the button for at least 3
seconds).
•Navigating the menu - entering the parameter value editing mode or
entering the selected lower level of the menu.
•Accepting the changed parameter value.
•Viewing the measuring values in the preview mode.
Deleting minimum value. DELMIN message is displayed after deleting. To avoid
accidentally exit the menu in the preview mode, it is recommended to press first
the button , and then the button and holding them until
DELMIN message is displayed.
Deleting maximum value. DELMAX message is displayed after deleting. To
avoid accidentally exit the menu in the preview mode, it is recommended to
press first the button , and then the button and holding them
until DELMIN message is displayed.
Deleting alarm memory - hold down the buttons for 3 seconds. lrAL message
will be displayed after deleting alarm memory.
All the events of deleting of saved minimum, maximum values and alarm activation
memory are indicated by the meter by displaying an appropriate message.
5.3 Programming meter parameters
Programming meter parameters is possible via the RS485 interface and by direct edition of
the parameters using the buttons and the meter display.
Direct programming process is easy thanks to meter menu, which includes the settings
grouped into sections with all parameters related to a given functionality, e.g. all
parameters of the serial interface are grouped in the menu .
Pressing and holding the confirm button for at least 3 seconds allows to switch from a
normal operation to meter menu . If access to change the parameters is password
protected, the user will be requested to enter the access password before entering the
menu. Entering an incorrect password will allow to enter the menu but it will be not
possible to change the parameters - parameters monitoring mode. Entering a correct
password will allow to move to a programming matrix, the menu after entering the
programming mode is shown below.

N32P-09 User's manual 13
While navigating the meter main menu with the groups of the parameters, the upper line of
the display shows the name of the group and the lower line continuously displays the word
MENU. After entering the group of the parameters (after pressing the confirm button), the
upper line displays the value of a given setting and the lower line shows the name of the
parameter which value is displayed in the upper line. Sample view of the selection of the
measured input signal type is shown in Fig. 9.
The buttons allow to navigate the menu of the meter. After selecting the
group of the parameters which configuration is to be changed, press the confirm button to
move to the parameters of the group. The parameter which value is to be modified is
selected the same way as the selection of the group. To cancel the parameter change,
press the cancel button to exit the parameter changing mode or the parameter
group. The meter will automatically exit the programming mode and return to displaying
the measuring value if no button is pressed for 30 seconds during programming. The
programming matrix is shown below.
Voltage measuring
range selection.
urrent
measurement range
selection
Selection of the
synchronization
source
Rated voltage of the
voltage transformer
primary
Rated voltage of the
voltage transformer
secondary
Rated voltage of the
current transformer
primary
Rated voltage of the
current transformer
secondary
Single measurement
time as a multiple of
100 milliseconds.
Selection of
measuring quantities
values averaging
method (standard or
moving window
method).
Measuring quantities
values averaging
period in minutes.
Averaging
synchronization with
the time clock.
Value entered into
the import energy
counter when
resetting the counter.
Value entered into
the export energy
counter when
resetting the counter.
Pulse weight on a
binary output
Selection of the
counter controlling
the binary output
Fig. 8: View of meter menu.
Fig. 9: View of menu when setting a parameter.
Parameter
which can be configured
Current value
of a setting

N32P-09 User's manual 14
Reset (enter initial
value) energy
counter.
Selection of main
displayed value.
Minimum value on
the display. For
values lower than
this value, a lower
overrun message is
displayed.
Maximum value on
the display. For
values higher than
this value, an upper
overrun message is
displayed.
Resolution - position
of the decimal point.
Function of a lower
line of the display -
selection of a
quantity displayed in
the lower line.
Selection of quantity
controlling the alarm
state.
Selection of alarm
type.
Alarm state change
lower threshold.
Alarm state change
upper threshold.
Alarm activation
delay.
Alarm deactivation
delay.
Active alarm
memory.
Meter network
address.
Transmission frame
type - data format.
Baud rate.
Selection of the type
of analog output
used.
Selection of value
controlling the
analog output.
Value of the
controlling quantity
for which the output
will have a minimum
value, in accordance
with the selected
output type.
Value of the
controlling quantity
for which the output
will have a rated
value, in accordance
with the selected
output type.
Value on the analog
output in case of
manual control or an
error on the
measuring input.
urrent time
according to the
internal clock.
urrent date
according to the
internal clock.
Automatic change of
DST and inversely
Password to protect
against settings
modification.
Restore default
settings
5.3.1 How to change quantity of a selected parameter
To increase the value of the selected parameter, press the button . Pressing the
button will increases the currently set digit by 1 and after reaching the value 9, pressing
the button will set the value 0. After setting the required value of a digit, move to the next
digit by pressing the button . After setting the required parameter value, press the
confirm button to accept the entered value or the cancel button to cancel
the parameter change and return to the previous value of the parameter. It is possible to
change a sign of the entered value during setting the last digit (most significant).
There are three steps to change the floating point values. The first step is to set the digits
and a sign in accordance with the algorithm described above. The second step is set the
position of the decimal point after pressing the confirm button. The buttons
are used to set the position of the decimal point. After setting the decimal point position as
required, press the confirm button to move to the third step - setting the multiplier of kilo,
mega or no multiplier. Symbol of the multiplier value is shown on the left side of the

N32P-09 User's manual 15
display.
Entering an incorrect value of a given parameter causes that the new value is not
accepted and the parameter will automatically have the previous value.
To change the parameters other than numerical select the appropriate setting from the
parameter list using the buttons . After selecting the appropriate setting,
press the confirm button to download the setting or the cancel button to
return to the previous value and exit the parameter change mode.
5.3.2 Programmable meter parameters, default parameters
The N32U meters have a number of programmable parameters, which enable the meter to
be adapted to the requirements of application. The parameters grouped according to the
menu are shown in the tables below.
Table
Parameter
symbol Description Range of changes
Voltage measurement range in voltage
measurement loop
Default : 230V
100V – rated measurement range 100 V
230V – rated measurement range 230 V
400V – rated measurement range 400 V
urrent measurement range in current
measurement loop
Default : 5A
1A – rated current measurement range 1 A
5A – rated current measurement range 5 A
Selection of the measurement synchronization
source - the quantity controlling the zero
crossing detector
Default : YN U
YN U – measurement synchronization with measuring
voltage.
YN I – measurement synchronization with measuring
current.
Note: The measurement synchronization with measuring
current is recommended only when the meter is used only for
current measurement, because the current waveform has
higher variability and the current waveform may be highly
distorted.
Rated primary voltage of the connected
voltage transformer in volts
Default : 100
0…200000
Note: UPRIM and USEC define the voltage ratio that directly
affects the measuring values of the parameters measured by
the meter The parameters UPRIM and USEC should be set
to the same value, if the voltage transformer is not used in
the system
Rated secondary voltage of the connected
voltage transformer in volts
Default : 100
0…200000
Rated primary current of the connected current
transformer in amperes
Default : 5
0…200000

N32P-09 User's manual 16
Note: IPRIM and ISEC define the current ratio that directly
affects the measuring values of the parameters measured by
the meter The parameters IPRIM and ISEC should be set to
the same value, if the current transformer is not used in the
system
Rated secondary current of the connected
current transformer in amperes
Default : 5
0…200000
Time of a single measurement as a multiple of
100 ms
Default : 10
1…600
Method of calculating the average value
Default : MOVING
MOVING – the average values of voltage, current and power
are calculated based on a moving window method, where the
average value is updated after each measurement. Note: The
average value can be updated every few measurements in
case of long averaging times or short measurement time, due
to the length of the measurement table with maximum of
1800 elements.
tAnd – the average value is calculated after each lapse of
set averaging time. The previous average value (for the
previous period) is displayed until the averaging time is
completed.
Averaging period of the measured voltage,
current and power values in minutes.
Default : 15
1…60
Synchronization of counting the average value
with the internal time clock.
Default : OFF
OFF – Synchronization is disabled.
ON – Synchronization internal real time clock is enabled. This
setting takes effect only if the set averaging period is 60
minutes divider, e.g. 10, 15, 20, etc.
Initial value of the import energy counter. The
value is assigned to the energy counter during
a reset/setting the counter.
Default : 0
-99999E+6...999999E+6
Initial value of the export energy counter. The
value is assigned to the energy counter during
a reset/setting the counter.
Default : 0
-99999E+6...999999E+6
Pulse weight in kWh, portion of an energy
corresponding to one pulse on the binary
output.
The EP W value determines at what change of
the energy counter one pulse will be assigned
to the binary output.
Default : 1
0.001...999999 [kWh]
Selection of the energy counter controlling the
binary output.
Default : EN_PO
EN PO – pulse output represents counting energy by the
import energy counter.
EN PO – pulse output represents counting energy by the
export energy counter.
Reset / set energy counter
Default : OFF
OFF – Do nothing
ON – Reset a counter. The parameter is automatically set to
OFF after resetting the counter (setting the values from ERV
P and ERV N parameters); during the reset, content of the
active energy counters is set based on ERV P and ERV N
parameters, and the reactive and apparent energy counters
are reset.

N32P-09 User's manual 17
Table 2
Parameter
symbol Description Range of changes
Selection of the main value displayed on the
top line of the display.
Default : U
U – currently measured voltage value.
I – currently measured current value.
P – currently measured active power value.
Q – currently measured reactive power value.
– currently measured apparent power value.
PF – power factor as the P/S power ratio calculated based on
the power triangle.
tAN – angle tangent as the Q/P power ratio calculated based
on the power triangle.
FREQ – currently measured frequency.
En P – import energy counter.
En N – export energy counter.
En QC – import reactive energy counter which has flowed
through the circuit - it is the absolute value (module) of
reactive energy counter.
En Q – export reactive energy counter which has flowed
through the circuit - it is the absolute value (module) of
reactive energy counter.
En – apparent energy counter which identifies the actual
energy demand of the circuit.
AVG U – voltage mean value in a given averaging period.
AVG I – current mean value in a given averaging period.
AVG P – active power mean value in a given averaging
period.
AVG Q – reactive power mean value in a given averaging
period.
AVG – apparent power mean value in a given averaging
period.
MIN U – voltage minimum value in a given averaging period.
MAX U – voltage maximum value in a given averaging
period.
MIN I – current minimum value in a given averaging period.
MAX I – current maximum value in a given averaging period.
MIN P – active power minimum value in a given averaging
period.
MAX P – active power minimum value in a given averaging
period.
MIN Q – reactive power minimum value in a given averaging
period.
MAX Q – reactive power minimum value in a given averaging
period.
MIN – apparent power minimum value in a given averaging
period.
MAX – apparent power minimum value in a given
averaging period.
Note: The averaging period is defined by AVGPE setting.
Display narrowing lower threshold. If the value
to be displayed is below the threshold, the
lower limit symbol is displayed
.
Default : -99999
-99999M...999999M
Display narrowing upper threshold. If the value
to be displayed is above the threshold, the
upper limit symbol is displayed
.
Default : -99999
-99999M...999999M
Resolution, display format as the position of
the decimal point.
Default : 0000.00
000000
00000.0
0000.00
000.000
00.0000

N32P-09 User's manual 18
0.00000
AUTO – automatic position of the decimal point for maximum
possible resolution.
Selection of the parameter displayed in the
lower line of the display.
Default : UNIt
UNIt – unit
U – currently measured voltage value.
I – currently measured current value.
P – currently measured active power value.
Q – currently measured reactive power value.
– currently measured apparent power value.
PF – power factor as the P/S power ratio calculated based on
the power triangle.
tAN – angle tangent as the Q/P power ratio calculated based
on the power triangle.
FREQ – currently measured frequency.
En P – import energy counter.
En N – export energy counter.
En QC – import reactive energy counter which has flowed
through the circuit - it is the absolute value (module) of
reactive energy counter.
En QC – export reactive energy counter which has flowed
through the circuit - it is the absolute value (module) of
reactive energy counter.
En – apparent energy counter which identifies the actual
energy demand of the circuit.
AVG U – voltage mean value in a given averaging period.
AVG I – current mean value in a given averaging period.
AVG P – active power mean value in a given averaging
period.
AVG Q – reactive power mean value in a given averaging
period.
AVG – apparent power mean value in a given averaging
period.
MIN U – voltage minimum value in a given averaging period.
MAX U – voltage maximum value in a given averaging
period.
MIN I – current minimum value in a given averaging period.
MAX I – current maximum value in a given averaging period.
MIN P – active power minimum value in a given averaging
period.
MAX P – active power minimum value in a given averaging
period.
MIN Q – reactive power minimum value in a given averaging
period.
MAX Q – reactive power minimum value in a given averaging
period.
MIN – apparent power minimum value in a given averaging
period.
MAX – apparent power minimum value in a given
averaging period.
clock – current time.
Note: The averaging period is defined by AVGPE setting.

N32P-09 User's manual 19
Table 3
, , ,
Parameter
symbol Description Range of changes
Input value controlling the alarm.
Default : U
U – currently measured voltage value.
I – currently measured current value.
P – currently measured active power value.
Q – currently measured reactive power value.
– currently measured apparent power value.
PF – power factor as the P/S power ratio calculated based on
the power triangle.
tAN – angle tangent as the Q/P power ratio calculated based
on the power triangle.
FREQ – currently measured frequency.
En P – import energy counter.
En N – export energy counter.
En QC – import reactive energy counter which has flowed
through the circuit - it is the absolute value (module) of
reactive energy counter.
En QC – export reactive energy counter which has flowed
through the circuit - it is the absolute value (module) of
reactive energy counter.
En – apparent energy counter which identifies the actual
energy demand of the circuit.
AVG U – voltage mean value in a given averaging period.
AVG I – current mean value in a given averaging period.
AVG P – active power mean value in a given averaging
period.
AVG Q – reactive power mean value in a given averaging
period.
AVG – apparent power mean value in a given averaging
period.
tIME – current time.
Note: The averaging period is defined by AVGPE setting.
Alarm type (see section 5.4.3)
Default : H-oFF
n-on – normally enabled
n-oFF – normally disabled
on – enabled
oFF – disabled
H-on – permanently enabled (manually)
H-oFF – permanently disabled (manually)
REG – the state controlled by the MODBUS protocol register.
Alarm state change lower threshold. Default : 10
-99999…999999
Alarm state change upper threshold. Default : 20
-99999…999999
Alarm activation delay - the duration in
seconds of the alarm state before activating
the alarm relay.
Default : 0
0…900
Alarm deactivation delay - the duration in
seconds the state without the alarm before
deactivating the alarm relay.
Default : 10
0…900
Alarm signalization latch. When the function is
enabled, after the alarm event ends, the
display indicator informing about the alarm
status will be flashing signaling the alarm until
it is canceled by a combination of buttons
or via the RS-485 interface.
Default : OFF
ON – alarm memory is activated.
OFF – alarm memory is deactivated.

N32P-09 User's manual 20
Table 4
Parameter
symbol Description Range of changes
MODBUS network meter address
Default : 1
1…247
The transmission frame type of RS-485
interface. Setting the parity bits and the
number of stop bits.
Default : F8N1
F8N1
F8N2
F8O1
F8E1
RS-485 interface baud rate.
Default : 9.6k
2.4k – 2400 b/s
4.8k – 4800 b/s
9.6k – 9600 b/s
14.4k – 14400 b/s
19.2k – 19200 b/s
28.8k – 28800 b/s
38.4k – 38400 b/s
57.6k – 57600 b/s
115.2k – 115200 b/s
Table 5
Parameter
symbol Description Range of changes
Selection of the operating mode and the type
of analog output used with the option of
switching off the output and manual setting the
output value.
Default : OFF
OFF – Output support is disabled.
4 20MA – current output 4...20 mA.
0 20MA – current output 0...20 mA.
0 10V – voltage output 0...10 V.
MAN I – current output. The output value corresponds to the
AnMAN setting.
MAN U – voltage output. The output value corresponds to the
AnMAN setting.
Input quantity controlling the analog output Default : U
U – currently measured voltage value.
I – currently measured current value.
P – currently measured active power value.
Q – currently measured reactive power value.
– currently measured apparent power value.
PF – power factor as the P/S power ratio calculated based on
the power triangle.
tAN – angle tangent as the Q/P power ratio calculated based
on the power triangle.
FREQ – currently measured frequency.
En P – import energy counter.
En N – export energy counter.
En QC – import reactive energy counter which has flowed
through the circuit - it is the absolute value (module) of
reactive energy counter.
En QC – export reactive energy counter which has flowed
through the circuit - it is the absolute value (module) of
reactive energy counter.
En – apparent energy counter which identifies the actual
energy demand of the circuit.
AVG U – voltage mean value in a given averaging period.
AVG I – current mean value in a given averaging period.
AVG P – active power mean value in a given averaging
period.
Table of contents
Other Lumel Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

P3 International
P3 International P4460 Operation manual

SATA
SATA AE5809 user manual

ASCO POWER TECHNOLOGIES
ASCO POWER TECHNOLOGIES SIGMA Hand-held quick start guide

VOLTCRAFT
VOLTCRAFT VC-330 operating instructions

Rhopoint
Rhopoint NOVO-GLOSS operating instructions

LumaSense technologies
LumaSense technologies IMPAC IN 9 plus manual