R3-NC3
EM-8422 Rev.9P. 1 / 7
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
the contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Network interface module .......................................... (1)
Terminating resistor (110Ω, 0.25W) .......................... (1)
■ MODEL NO.
Check that model No. described on the specification label is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, including installation, connection and basic
maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EC DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrated in
a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■ POWER INPUT RATINGS
Operational range & power consumption: Check the power
rating for the unit on the specification label.
Rating 100 – 120V AC: 85 – 132V, 47 – 66 Hz, approx. 20VA
Rating 200 – 240V AC: 170 – 264V, 47 – 66 Hz, approx. 20VA
Rating 24V DC: 24V ±10%, approx. 12W
■ UNPLUGGING THE UNIT
Before you remove the unit from its base or mount it, turn off
the power supply for safety.
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ventila-
tion.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH in
order to ensure adequate life span and operation.
■ WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
INSTRUCTION MANUAL
MODEL R3-NC3
CC-Link INTERFACE MODULE
(CC-Link Ver.2)
■ AND ....
The unit is designed to function as soon as power is supplied,
however, a warm up for 10 minutes is required for satisfying
complete performance described in the data sheet.
INSTALLATION
Use the Installation Base Model R3-BSx, or Model R3-BSWx
for free I/O address capability.
Before mounting the Network Interface Module onto the
Base, be sure to configure the module as explained below.
■ DATA ALLOCATION
The setting determines the data area size assigned to each I/
O module mounted on the base.
The data sent/received via CC-Link is mapped according to
this setting.
See "DATA DESCRIPTION" in Page 4.
■ NODE ADDRESS & BAUD RATE
See "COMPONENT IDENTIFICATION" in Page 2.
■ NETWORK SLOTS ON THE BASE
With Model R3-BSx base, mount the I/O Modules from the
left end (I/O 1) to the right in order that the Network Module
assigns data areas from I/O 1.
Network Module(s) and Power Module are mounted basically
at the right end though technically they could be mounted in
any position.
With Model R3-BSWx base, there is no limitation in mount-
ing positions as I/O address can be assigned freely to each
module using rotary switches equipped on the base.
I/O 1 I/O 2 I/O n