
10
SC100/200 Series Function Block Application Manual EM-6460-C
GROUP [04] SCxxx Extension Field Terminal 1 ★: Setting data
ITEM MDFY DATA INPUT DISPLAY (e.g.) CONTENTS
10 IND 12 MD: 12 EXTENSION FIELD TERMINAL 1 (model)
ANALOG OUTPUT CONNECTION TERMINAL
★25 ▲GGNN M1#: 0225 Mv 1 connection terminal (error if not connected)
GG: Group No. NN : terminal No.
PV / MV SETTING
★30 ▲-15.00 – 115.00 % PH1: 115.00 Pv 1 high alarm setpoint (for error judgment)
★31 ▲-15.00 – 115.00 % PL1: -15.00 Pv 1 low alarm setpoint (for error judgment)
★34 ▲0.00 – 115.00 % ML1: 115.00 Mv 1 deviation alarm setpoint (for error judgment)
GROUP [02, 03] Basic PID ◆: Automatically changeable parameters ★: Setting data
ITEM MDFY DATA INPUT DISPLAY (e.g.) CONTENTS
★10 ▲21 MD: 21 BASIC PID (model) ‘-’ to clear.
PROCESS VALUE (PV)
★15 ▲GGNN P#: 0421 PV connection terminal
GG: Group No. NN: terminal No.
◆★19 ●-15.00 – 115.00 % PH: 95.00 PV high alarm setpoint
◆★20 ●-15.00 – 115.00 % PL: 5.00 PV low alarm setpoint
◆★21 ●0.00 – 115.00 % HS: 1.00 Hysteresis (deadband)
SETPOINT VALUE (SP)
★24 ▲GGNN (No connection) CAS connection terminal
◆★27 ●-15.00 – 115.00 % SP: 50.00 Local SP %
★29 ▲0, 1 SM: 0 Setting mode (0: local, 1: cascade/local)
DEVIATION
◆★34 ●0.00 – 115.00 % DL: 115.00 Deviation alarm setpoint (hysteresis (deadband) in ITEM 21)
CONTROL
★ 40 ▲0, 1 DR: 1 Control direction
(0: direct, 1: reverse [MV decreases with PV increase])
★ 41 ▲0, 1 DM: 0 Derivative method (0: PV derivative, 1: deviation derivative)
◆★42 ●1 – 1000 % PB: 30 Proportional band
◆★43 ●0.00 – 100.00 min. TI: 2.00 Integral time (0: no integral action)
◆★44 ●0.00 – 10.00 min. TD: 1.50 Derivative time (0: no derivative action)
★45 ▲1, 2, 4, 8, 16, 32, 64 CP: 1 Control cycle (multiple of basic control cycle)
CONTROL OUTPUT MV
◆★50 ●±115.00 % MH: 100.00 Output high limit
◆★51 ●±115.00 % ML: 0.00 Output low limit
52 ▲0, 1 08: 0 Preset value SW (1: preset)
SUPERVISORY INDICATION USE
★80 ▲alphanumeric TG: TIC-101 Tag name (10 characters max.)
★81 ▲alphanumeric TC: TANK TEMP Tag comment (16 characters max.)
★82 ▲±32000 MH: 800 Upper range (in engineering unit)
★83 ▲±32000 ML: 0 Lower range (in engineering unit)
★84 ▲0, 1, 2, 3, 4, 5 DP: 1 Decimal point position (from rightmost digit)
★85 ▲alphanumeric TU: C Engineering unit (8 characters max.)
GROUP [81 – 92] Sequential Control Program ★: Setting data
ITEM MDFY DATA INPUT DISPLAY (e.g.) CONTENTS
★10 ▲95 MD: 95 SEQUENTIAL CONTROL PROGRAM (model) ‘-’ to clear.
★11 ▲CCGGNN 010201 PV high alarm (Group 02, Terminal 01)
★12 ▲CCGGNN 070501 Output at Do 1