M1EXV-4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-6040-B Rev.2 P. 10 / 37
• Parameters
MODE ITEM SETTING PARAMETER RANGE UNIT INITIAL VALUE
Ch1 Setting 01 Lockout setting Lock / Unlock – Lock
02 Ch1 Enable Disable / Enable – Enable
11 Ch1 Input range 0 – 20 mA
-5 – +5 V
-10 – +10 V
– -5 – +5 V
12 Ch1 0% Input setting 0.000 – 19.000
-5.000 – 4.750
-10.000 – 9.000
mA
V
V
1.000
13 Ch1 100 % Input setting 1.000 – 20.000
-4.750 – 5.000
-9.000 – 10.000
mA
V
V
5.000
14 Ch1 0 % Input scaling -99999 – 999999 – 0.00
15 Ch1 100 % Input scaling -99999 – 999999 – 100.00
16 Ch1 Input decimal point No decimal point
The number of decimal places: 1 – 5
– 2 places of decimals
17 Ch1 Unit (INP Scaling) Choose from 68 types – %
61 Ch1 Output range 0 – 20 mA
-5 – +5 V
-10 – +10 V
– 0 – 20 mA
62 Ch1 0 % Output setting 0.000 – 19.000
-5.000 – 4.750
-10.000 – 9.000
mA
V
V
4.000
63 Ch1 100 % Output setting 1.000 – 20.000
-4.750 – 5.000
-9.000 – 10.000
mA
V
V
20.000
71 Ch1 Filter time constant 0 – 30 sec. 0
81 Ch1 Input zero fine adjust -5.000 – 5.000 % 0.000
82 Ch1 Input span fine adjust 95.000 – 105.000 % 100.000
91 Ch1 Output zero fine adjust -5.000 – 5.000 % 0.000
92 Ch1 Output span fine adjust 95.000 – 105.000 % 100.000
95 Ch1 User’s table linearization Cancel / Set – Cancel
98 Ch1 Loop test -5.00 – 105.00 % Cancel
[01] Lockout setting
Enable / disable Lockout setting.
SETTING VALUE DESCRIPTION INITIAL VALUE
Lock Enable Lockout setting Lock
Unlock Disable Lockout setting
When Lockout setting is enabled, it is possible to shift to
each setting mode and confirm the setting value of each
setting parameter item. Each parameter item display in-
dicates ‘DATA (Locked)’ when set to ‘Lock’, and indicates
‘DATA’ when set to ‘Unlock’.
[02] Ch1 Enable
Enable / disable Ch1.
No output signal or present value is displayed for the disa-
bled channel in Measuring Mode.
SETTING VALUE DESCRIPTION INITIAL VALUE
Disable Disable Ch1 Enable
Enable Enable Ch1
Even when Ch1 is disabled, parameter settings for Ch1 can
be performed.
[11] Ch1 Input range
Set the input range.
SETTING VALUE DESCRIPTION INITIAL VALUE
0 – 20 mA Input: 0 – 20 mA DC
-5 – +5 V-5 – +5 V Input: -5 – +5 V DC
-10 – +10 V Input: -10 – +10 V DC
When the input range is changed, turn the power off, and
change the connection to the input terminal of the unit ac-
cordingly. Note that input setting values are changed to the
initial values.
[12] Ch1 0 % Input setting
Set the 0 % input setting value.
Setting range differs according to input range.
INPUT RANGE
SETTING RANGE
MIN. SPAN
INITIAL VALUE
0 – 20 mA 0.00 – 19.00 1.00 4.00
-5 – +5 V -5.000 – 4.750 0.250 1.000
-10 – +10 V -10.000 – 9.000 1.000 -10.000
Set as follows.
[12] 0 % input setting < [13] 100 % input setting
[13] Ch1 100 % Input setting
Set the 100 % input setting value.
Setting range differs according to input range.
INPUT RANGE
SETTING RANGE
MIN. SPAN
INITIAL VALUE
0 – 20 mA 1.00 – 20.00 1.00 20.00
-5 – +5 V -4.750 – 5.000 0.250 5.000
-10 – +10 V -9.000 – 10.000 1.000 10.000
Set as follows.
[12] 0 % input setting < [13] 100 % input setting
[14] Ch1 0 % Input scaling
Set the display value of 0 % input setting.
SETTING RANGE INITIAL VALUE
-99999 – 999999 0.00
[15] Ch1 100 % Input scaling
Set the display value of 100 % input setting.
SETTING RANGE INITIAL VALUE
-99999 – 999999 100.00