Eng-13
2303N22HHZA0013
The following system conguration
can be created. Connect the necessary
parts.
1When connecting with remote controller (PZ-62DR-EA/EB)
2When interlocked with indoor unit of air conditioner or other external
device including other manufactures
3When operating multiple Lossnay units
4Signal output from Lossnay unit
5When switching fan speed externally (when a sensor or other
device is connected)
6When switching By-pass externally
7To change fan speed by 0 - 10 VDC input
8When using the remote/local switching and the ON/OFF input (level
signal)
9When connecting to the City Multi or Mitsubishi Electric Air-
Conditioner Network System (MELANS)
0To start/stop Lossnay stand-alone operation without using the
remote control
aControl via Wi-Fi interface or MELCOBEMS MINI
bWhen connecting CO2sensor PZ-70CSD-E or PZ-70CSW-E
CAUTION
• When connecting external devices (electric heater, damper,
lamp, monitoring unit, etc.) using output signals of the Lossnay
unit, be sure to install safety equipment for the external
devices.
(It could cause re, damage, etc. without safety equipment.)
• Seal the opening between the bushing and the cables in order
not to intrude insects.
1When connecting with remote controller (PZ-62DR-EA/EB)
* When controlling Lossnay units with MELANS, connect wires
according to 9.
Securely connect the transmission cable from the remote controller to
1and 2of the input terminal block (TM4). (No polarity)
Wire type: two-core sheathed cable
Wire diameter: 0.3 mm2
•
If there are two remote controllers, connect them in the same way.
• Keep the overall length of the transmission cable between Lossnay
and the remote controller within 200 m.
Note
• Do not tighten screws of terminal block with a torque larger
than 0.5 N・m. It could damage the circuit board.
• Take care not to connect the power supply cable or M-NET
transmission cable.
• When connecting multiple cables to the terminal, use round
terminal.
• Solid wire (single-stranded wire) cannot be connected.
• PZ-61DR-E is not available.
CAUTION
TM4, TB5
1
2
Remote controller input terminal
Transmission cables
✓
Power supply Up to two remote controllers
Lossnay
2When interlocked with indoor unit of air conditioner or
other external device including other manufactures
CAUTION
• The connection may vary according to the output signal type of
the external unit.
• Do not press the terminal with a force of more than 19.6 N when
connecting the cable to TM2.
When using Mitsubishi Mr. Slim air conditioner with MA
Remote controller
Conrm that the pulse input switch (SW2-2) is set to “OFF”.
(Factory setting is “OFF”.) (Refer to function settings
)
Connect the Slim-Lossnay connection cable connector side to CN2L
on the circuit board for the Mr. Slim indoor unit, then connect the
lead wire side to the 1and 2of the input terminal block (TM2) for
the Lossnay external controller input. (No polarity)
• Always separate the power supply cable and the Slim-Lossnay
connection cable by 5 cm or more to prevent the unit from
malfunctioning.
• The Slim-Lossnay connection cable is 100 mm long. When wiring,
extend it as far as necessary.
Note
• Use MA remote controller of Mr. Slim for switching Lossnay ON/
OFF or the fan speed.
• The ventilation mode is xed to “automatic ventilation” from
MA remote controller.
• Ensure that all connections are secure and that the appropriate
insulation is provided.
Use extension cable sheathed PVC cable or cable 0.5 mm2to
1.5 mm2.
• Only one Lossnay and one Mr. Slim unit can be interlocked.
Multiple units interlock is not possible.
• Lossnay can not be connected M-NET in this case.
[SW2-2] setting vary depending on the types of output signal of
external device.
When the external device has a charged operating signal of
12 VDC or 24 VDC
• If the input is pulse signal, move the pulse input switch [SW2-2] to
the ON position. (Refer to function settings
)
• When level signal is selected, the signal width has to be more
than 10 seconds for ON and OFF .
• When pulse signal is selected, a pulse width has to be at least 200
m sec. to turn Lossnay ON, and 10 sec. interval is necessary to
next output.
• The wiring should be as shown by the following picture.
Operating switch for
external device
Power supply
External
device
Lossnay
Power supply TM2
Y Z
1 2
Lossnay external
control input
(TM2)
Slim-Lossnay connection cable
(Accessory parts)
Printed circuit board
Maximum 50 m
CN2L
Mr. Slim (Indoor unit)
Y Z
1 2
Lossnay external
control input
(TM2) 0.5 mm2to 1.5 mm2sheathed PVC cable
External device
12 or 24 VDC
Overall connection extension length
(Follow the operation manual for the external equipment.)