LOSSNAY HEAT RECOVERY VENTILATOR SYSTEM COMPONENT
Filter name MODEL
MODEL CODE
Applicable model Location to use
Replacement lter P-250F-E 5KB010
VL-250CZPVU-R-E/VL-250CZPVU-L-E
RA, OA
L Type
R Type
RA: Return Air
OA: Outdoor Air
SA: Supply Air
P-350F-E 5KB016
VL-350CZPVU-R-E/VL-350CZPVU-L-E
Standard lter P-250SF-E 5KB011
VL-250CZPVU-R-E/VL-250CZPVU-L-E
RA, OA
SA
P-350SF-E 5KB017
VL-350CZPVU-R-E/VL-350CZPVU-L-E
Medium eciency lter P-250MF-E 5KB012
VL-250CZPVU-R-E/VL-250CZPVU-L-E
RA, OA
SA
P-350MF-E 5KB018
VL-350CZPVU-R-E/VL-350CZPVU-L-E
PM2.5 lter P-250PF-E 5KB013
VL-250CZPVU-R-E/VL-250CZPVU-L-E
RA, OA
SA
P-350PF-E 5KB019
VL-350CZPVU-R-E/VL-350CZPVU-L-E
NOx lter P-250NF-E 5KB014
VL-250CZPVU-R-E/VL-250CZPVU-L-E
SA
P-350NF-E 5KB020
VL-350CZPVU-R-E/VL-350CZPVU-L-E
* When a NOx lter and an optional dust catch lter (P-250/350SF-E, P-250/350MF-E, P-250/350PF-E) are used together, make sure
to install a NOx lter on the SA side and a dust catch lter on the OA side.
* Install any of the lters other than NOx lter on the OA and RA side to protect the product.
Instruction Manual For Customer
This lter is a part to replace the lter installed in Lossnay.
- Make sure to read this manual carefully before using the product.
Safety precautions
The types and levels of danger that may arise if the product
is handled improperly are described with the warning symbols
shown below.
WARNING
This applies to mishandling or misoperation of the product which may
lead to a fatal or serious injury.
Follow
instructions
Before replacement, make sure to turn o the
controller and the distribution panel circuit breaker.
Electric shock and burns could result if power is owing.
CAUTION
This applies to mishandling or misoperation of the product, which will
lead to an injury or damage to your home, household eects, etc.
Follow
instructions
Always wear gloves during replacement.
Injury could result.
Securely install the parts.
Injury could result if the product falls.
Do not use an unstable stand for replacement.
Injury could result from falling over.
Outline drawings and Materials
Unit: mm
MODEL A B
P-250F-E 302 178
P-250SF-E
P-250MF-E
P-250PF-E
P-250NF-E
306 177
P-350F-E 377 178
P-350SF-E
P-350MF-E
P-350PF-E
P-350NF-E
382 177
Materials are shown below, please dispose properly according to
the laws of each country.
MODEL Main material
P-250/350F-E PET, acrylic ber
P-250/350PF-E
P-250/350MF-E
P-250/350SF-E
Polypropylene, polyester
P-250/350NF-E Pulp
Filtration specication
MODEL ISO16890: 2016 EN779: 2012
P-250/350F-E Coarse 55% G3
P-250/350SF-E Coarse 90% G4
P-250/350MF-E ePM10 80% M6
P-250/350PF-E ePM2.5 50% M6
P-250/350NF-E: Exclusion rate of NO2is 90%.
* The ltration specications other than the specications of
P-250/350NF-E are results of tests conducted by third-party certication
bodies and are not a guaranteed value.
* The ltration specications of P-250/350NF-E are measured by the
manufacturer and are not a guaranteed value.
A
B
15
OA
SA
RA
RA
SA
OA
2011876H07701