(4)Trouble Mode 4: The Lossnay does not operate or operates irregularly.
1Lossnay checklist (Table 4).
1
No.
The fan does not operate.
The fan does not operate
normally.
«Connectors for the fan connection or connec-
tors for the control circuit section connection
are not secure.
«Power supply is not supplied to the Lossnay, or
power outside specifications is connected.
«Lossnay group setting is not made by using the
M-NET. (LED2 lights)
«Check the lead wire connectors
and the control circuit section
connectors.
«Check the power supply
«
Check the Lossnay address and
the group setting (LED2 lights when
not using M-NET. This is no error.)
3 Fan will not stop. «The trial operation switch (SW 2-1) is ON. «Check the test operation switch
(SW2-1).
4 Lossnay operates when
main power is turned on.
«The PZ-41SLB-E is being used.
«
By using the M-NET, the power supply ON/OFF
setting is set to ON at the function select switch
(SW 2-6) on the Lossnay circuit board.
«
By using the M-NET, the automatic recovery fol-
lowing power supply interruption (refer to page
168) setting is made at the function select
switch (SW 5-4) on the Lossnay circuit board.
«
When the main power supply is
turned off while the Lossnay is
operating from the remote con-
troller, the Lossnay will resume
operation when the main power is
turned back on (this is no error).
«Check the power supply ON/OFF
setting of the function select
switch (SW2-6).
«Check the automatic recovery
following power supply interrup-
tion setting of the function select
switch (SW5-4).
2 Interlocked operation
with external device
(air conditioner) does not
occur.
«The type of external signal does not match the
connected terminal unit (charged, uncharged,
Mr. Slim signal).
«The type of external signal does not match the
pulse input switch (SW2-2) setting (level sig-
nal, pulse signal).
«The external device signal is not being input.
«The external device and signal cable wiring is
longer than specifications
(12V DC, 24V DC:
Longer than limitations
of external device
Uncharged a-contact: Longer than 1640 ft
Mr. Slim signal: Longer than 1640 ft)
«The Delayed Start mode is set at the remote
controller (PZ-41SLB-E) or the function select
switch (SW 5-1) on the Lossnay circuit board.
«The ON Interlocked Operation mode or OFF
Interlocked Operation mode is set at the
remote controller (PZ-41SLB-E) or the function
select switch (SW 5-7,8) on the Lossnay circuit
board.
«When using multiple Lossnay units, the exter-
nal control input signal is connected to a unit
with the “Sub”setting made.
«In a group of multiple Lossnay units with the M-
NET, the external control input signal is con-
nected to a Lossnay unit other than the one
with the smallest address.
«There is a communication error with the
remote controller or controller.
Symptom Cause Corrective action
«Check the external signal type
and the external control input ter-
minal (TM2) connection.
«Check the external signal type
and the pulse input switch (SW2-
2) setting.
«Check the external device.
«Check the wiring length of the
signal cable.
«
Check the delayed start settings of
the remote controller (PZ41SLB-E)
and the function select switch
(SW5-1).
«
Check the interlocked operation
mode settings of the remote con-
troller (PZ41SLB-E) and the func-
tion select switch (SW5-7, 8).
«Connect the external control
input signal to the Lossnay set to
“Main.”
«Connect the external control
input signal to the Lossnay in the
group with the lowest address.
«Check the remote controller or
controller.