MR tapcon 240 User manual

Voltage regulator TAPCON® 240
Quick reference guide 230/05

© All rights reserved by Maschinenfabrik Reinhausen
Copying and distribution of this document and utilization and communication of its contents are strictly prohibited
unless expressly authorized.
Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent,
utility model or ornamental design registration.
The product may have been modified after this document went to press.
We expressly reserve the right to make changes to the technical data, the design or the scope of delivery.
Generally, the information provided and the arrangements agreed during processing of the relevant quotations
and orders are binding.
The original operating instructions were drawn up in German.

Table of Contents
© Maschinenfabrik Reinhausen 2010 230/05 EN TAPCON® 240 3
Table of Contents
1Introduction .................................................................................. 5
1.1Manufacturer.............................................................................................5
1.2Completeness ...........................................................................................5
1.3Supporting documents ..............................................................................6
1.4Safekeeping ..............................................................................................6
2Safety ............................................................................................ 7
3Product description ..................................................................... 9
3.1Operation and indicator elements ...........................................................10
3.2Description of the display........................................................................11
3.3Description of key functions ....................................................................13
3.4Description of LEDs ................................................................................14
4Functions and settings.............................................................. 15
4.1Key lock ..................................................................................................15
4.2Activating key lock ..................................................................................15
4.3Setting the language ...............................................................................16
4.4NORMset ................................................................................................17
4.4.1Entering NORMset desired value 1 .................................................................... 18
4.4.2Setting the primary voltage ................................................................................. 19
4.4.3Setting the secondary voltage ............................................................................ 21

Table of Contents
4 TAPCON® 240 230/05 EN © Maschinenfabrik Reinhausen 2010
4.5Parameters ............................................................................................. 22
4.5.1Setting desired value 1 ....................................................................................... 22
4.5.2Bandwidth ........................................................................................................... 24
4.5.3Setting delay time T1 .......................................................................................... 28
4.5.4Activate/deactivate delay time T2....................................................................... 29
4.5.5Setting delay time T2 .......................................................................................... 30
4.6Configuration .......................................................................................... 31
4.6.1Transformer data ................................................................................................ 31
4.6.2General ............................................................................................................... 40
4.7Displaying the info screen ...................................................................... 42
5MR worldwide ............................................................................. 45

1 Introduction
© Maschinenfabrik Reinhausen 2010 230/05 EN TAPCON® 240 5
1 Introduction
This technical file contains information for quick start-up of the voltage regula-
tor. It does not provide comprehensive operating instructions.
This technical file is intended solely for specially trained and authorized per-
sonnel.
1.1 Manufacturer
The product is manufactured by:
Maschinenfabrik Reinhausen GmbH
Falkensteinstrasse 8
93059 Regensburg
Tel.: (+49) 9 41/40 90-0
Fax: (+49) 9 41/40 90-7001
E-mail: sales@reinhausen.com
Further information on the product and copies of this technical file are availa-
ble from this address if required.
1.2 Completeness
This technical file is only complete in conjunction with the supporting docu-
mentation.

1 Introduction
6 TAPCON® 240 230/05 EN © Maschinenfabrik Reinhausen 2010
1.3 Supporting documents
The following documents apply to this product:
Operating instructions
Commissioning instructions
Quick reference guide
Connection diagrams
All documents form part of the scope of delivery.
In addition, generally applicable legal and other binding regulations of Euro-
pean and national law and the regulations for accident prevention and envi-
ronmental protection in force in the country of use must be complied with.
1.4 Safekeeping
This technical file and all supporting documents must be kept ready to hand
and accessible for future use at all times.

2 Safety
© Maschinenfabrik Reinhausen 2010 230/05 EN TAPCON® 240 7
2 Safety
This technical file does not replace the operating instructions for the voltage
regulator. The quick reference guide contains information that will provide a
rapid introduction to operating the voltage regulator.
For detailed operation and safety information please read carefully through
the voltage regulator operating instructions.
Pay particular attention to the information in the chapter on safety in the
operating instructions.


3 Product description
© Maschinenfabrik Reinhausen 2010 230/05 EN TAPCON® 240 9
3 Product description
Figure 1 Front view of voltage regulator
1 19-inch plug-in housing (in accordance with DIN 41494 Part 5)
2 Operating panel with display and LEDs
3 Assembly for optional add-ons (e.g. TAPCON 240 LV)

3 Product description
10 TAPCON® 240 230/05 EN © Maschinenfabrik Reinhausen 2010
3.1 Operation and indicator elements
The front of the voltage regulator is split into different areas for operating the
device and displaying information. Below you can see an overview of the indi-
vidual elements.
Figure 2 Voltage regulator operating panel
1 LEDs
2 Keys for parameterization and configuration
3 Serial interface COM1 (RS232)
4 Keys for operating the device
5 Labeling strip for LEDs
6 Setting options for display contrast

3 Product description
© Maschinenfabrik Reinhausen 2010 230/05 EN TAPCON® 240 11
3.2 Description of the display
Figure 3 Main screen
1 Status line
2 Measured voltage Vactual
3 Desired voltage Vdesired
4 Other measured values (use or to switch between them)
5 Tap position (n-1, n, n+1)
6 Bandwidth (upper and lower limit)
7 Time bar for delay time T1
8 Highlighting for desired voltage
9 Highlighting for measured voltage
10 Remaining delay time T1

3 Product description
12 TAPCON® 240 230/05 EN © Maschinenfabrik Reinhausen 2010
In auto and manual mode the measured value display can be set using the
or keys. The following measured values can be displayed:
Control deviation (dV:)
Current (I:)
Apparent power (Powr.:)
Active power (P:)
Reactive power (Q:)
Phase angle (Phase:)
Cosine (Cos:)
In the case of an event or a setting, the comments linked to this are displayed
in the status line (display text "Messages").

3 Product description
© Maschinenfabrik Reinhausen 2010 230/05 EN TAPCON® 240 13
3.3 Description of key functions
Key Symbol Function
RAISE
In manual mode the motor-drive unit can be operated directly
using the RAISE key.
Using RAISE, the motor-drive unit changes the on-load tap-
changer and therefore the step voltage.
LOWER
In manual mode the motor-drive unit can be operated directly
using the LOWER key.
Using LOWER, the motor-drive unit changes the on-load tap-
changer and therefore the step voltage.
REMOTE
In the "Remote" operating mode, commands from an external
control interface are executed. In this mode, manual operation
of the RAISE, LOWER, MANUAL and AUTO keys is disabled.
MANUAL
Manual mode. For manual control of the motor-drive unit and
parameterization of the voltage regulator.
AUTO
Auto mode. Voltage is controlled automatically.
Arrow keys
NEXT/ PREV
In auto and manual mode, the measured value display can be
set using the arrow keys.
They can also be used to switch between windows in the
submenus.
ENTER
Confirms or saves a changed parameter in the parameter
menu.
ESC
Pressing the ESC key takes you to the menu level above, in
other words, always back one menu level.
MENU
Pressing this key displays the menu selection window.
F1-F5
The function keys are menu selection keys. They are also
used to scroll through the menu subgroups and input screens
and to highlight decimal points which can be set by the user.
The parameters can only be changed in manual mode, see key in the
table above.

3 Product description
14 TAPCON® 240 230/05 EN © Maschinenfabrik Reinhausen 2010
3.4 Description of LEDs
The voltage regulator has 10 LEDs above the display. These indicate various
operating statuses or events.
Figure 4 Description of LEDs
1 Green Operating display
2 Red Overcurrent blocking
3 Red Undervoltage blocking
4 Red Overvoltage blocking
5 Green Parallel operation On
6 Green NORMset On
7 Yellow Freely configurable (LED1)
8 Yellow Freely configurable (LED2)
9 Yellow Freely configurable (LED3)
10 Green/yellow/red Freely configurable (LED4)

4 Functions and settings
© Maschinenfabrik Reinhausen 2010 230/05 EN TAPCON® 240 15
4 Functions and settings
This chapter gives a short summary of all the functions and possible settings
of the voltage regulator. For details, see the voltage regulator operating
instructions.
4.1 Key lock
The voltage regulator is equipped with a key lock for protection against unin-
tentional operation. Parameters can only be carried out in manual mode (MA-
NUAL) with deactivated key lock.
4.2 Activating key lock
To activate the key lock, proceed as follows:
►Press and at the same time.
A confirmation (see diagram) appears on screen
for a short period. The key lock is activated. Pa-
rameters can no longer be entered.

4 Functions and settings
16 TAPCON® 240 230/05 EN © Maschinenfabrik Reinhausen 2010
4.3 Setting the language
The required display language can be set or changed in any way. The follow-
ing languages are available:
English
German
French
Spanish
Italian
Portuguese
1. > Configuration > General.
<00> Language.
2. Press or to select the required lan-
guage.
3. Press .
The transformer secondary voltage is set.

4 Functions and settings
© Maschinenfabrik Reinhausen 2010 230/05 EN TAPCON® 240 17
4.4 NORMset
Instead of parameterizing the voltage regulator manually, NORMset mode
enables easy and user-friendly commissioning of the voltage regulator with a
limited set of parameters. When this mode is selected, the factory settings re-
quired for voltage regulation are adopted.
If NORMset is activated, the bandwidth and delay time settings will be un-
dertaken automatically by the voltage regulator.
The following control parameters must be set in NORMset mode:
Desired value 1
Primary voltage
Secondary voltage
The following parameters are not set automatically using the NORMset
mode:
Undervoltage limit
Overvoltage limit
Undercurrent limit
Overcurrent limit
If required, these parameters must be set manually.
1. > Normset.
<00> Normset activation.
2. To activate Normset, press or to
select "On".
3. Press .
4. Press or to perform a
manual tap-change operation.
The LED for the NORMset operating display lights
up. The Normset mode is activated.

4 Functions and settings
18 TAPCON® 240 230/05 EN © Maschinenfabrik Reinhausen 2010
4.4.1 Entering NORMset desired value 1
Desired values set in kV apply to the primary voltage of the connected voltage
transformer. Desired values set in kV apply to the secondary voltage of the
connected voltage transformer. All transformer data (see "Transformer da-
ta" on page 31) must be entered correctly.
Settings in kV are only possible if you have previously entered the parame-
ters for primary and secondary voltage.
Setting range Step size Factory setting
49 V…140 V 0.1 V 100 V
Table 1 Setting range for NORMset desired value 1 in V
Setting range Step size Factory setting
0 kV...9999 kV
0 kV...999.9 kV
0 kV...99.99 kV
1 kV
0.1 kV
0.01 kV
1 kV
Table 2 Setting range for NORMset desired value 1 in kV
To set desired voltage value 1, proceed as follows:
1. > Normset > 1x .
<01> Desired value 1.
2. Press to highlight a digit position.
The digit position you want is highlighted
and the value can be changed.
3. Press to increase the value or to
reduce it.
4. Press .
Desired value 1 is set.

4 Functions and settings
© Maschinenfabrik Reinhausen 2010 230/05 EN TAPCON® 240 19
4.4.2 Setting the primary voltage
In general, the regulator only indicates the secondary voltage in V if you have
not set the primary voltage. The primary voltage is only displayed if parameter
"Display V / kV" has been set to kV (see "Setting the voltage display
kV/V" on page 40).
Example:
Primary voltage Secondary voltage kV or V Display
No parameterization 100 V V 100 V
110 kV 100 V kV 110 kV
Table 3 Example of displayed values in V or kV
Setting range Step size Factory setting
0 kV...9999 kV
0 kV...999.9 kV
0 kV...99.99 kV
1 kV
0.1 kV
0.01 kV
0 kV
Table 4 Setting range for primary voltage in kV

4 Functions and settings
20 TAPCON® 240 230/05 EN © Maschinenfabrik Reinhausen 2010
To set the primary voltage, proceed as follows:
1. > Normset > 2x .
<02> Primary voltage.
2. Press to highlight the decimal place.
The decimal place is defined and the value
can be changed.
3. Press to highlight a digit position.
The digit position you want is highlighted
and the value can be changed.
4. Press to increase the value or to
reduce it.
5. Press .
The primary voltage is set.
Other manuals for tapcon 240
1
Table of contents
Other MR Controllers manuals
Popular Controllers manuals by other brands

Promation Engineering
Promation Engineering P1.A Series Installation & operation manual

REMEHA
REMEHA Celcia 20 FUNCTIONS

Greenheck
Greenheck HVLS Installation, operation and maintenance manual

Interroll
Interroll MultiControl instruction manual

Turbosmart
Turbosmart e-Boost 2 quick start guide

Mitsubishi
Mitsubishi FX3U-232-BD user manual

rotork
rotork LP/S Series Installation, Comissioning and maintenance manual

Mitsubishi
Mitsubishi MELSEC-L Series user manual

YASKAWA
YASKAWA CIMR-VC*****H**-00 series quick start guide

ICM Controls
ICM Controls ICM600 Application guide

TERSUS
TERSUS TC50 user manual

FrSky
FrSky Neuron 8A SBEC instruction manual