NAPCO StarLink SLE-LTEVI-FIRE User manual

StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions 1
ADDITIONAL COMPONENTS
In addition to the SLE-LTEVI-FIRE listed above, the fol-
lowing sub-assemblies are available:
SLE-WIFI-MODULE - Allows your Napco StarLink™device
to connect to the Internet by means of a wireless (Wi-Fi)
link, eliminating a wired Ethernet cable connection.
Note: 7AH battery required when using the SLE-
WIFI-MODULE. For more information, see WI2191.
SLE-DLCBL - Download Cable, 6 feet.
SLE-ANTEXT30 - Extended antenna with 30 feet of cable
SLE-ANTEXT50 - Extended antenna with 50 feet of cable
SLE-ANTEXT75 - Extended antenna with 75 feet of cable
(Any suitable external cellular antenna is permitted by
UL). Always follow the manufacturer's installation in-
structions. Note: Antennas are not Listed by UL. For
LTE radios where an External Antenna needs to be in-
stalled outside of the room in which the radio is installed
(maximum 30 meters (98 feet) in Residential applica-
tions), please use RF Transmitter Board
9SLELTEEXAPSLD available from our Customer Ser-
vice Department, if not provided. The
9SLELTEEXAPSLD is identified by "two red dots" locat-
ed on the lower right corner of the board. See WI2239
included with the 9SLELTEEXAPSLD for the simple in-
stallation procedure.
SPECIFICATIONS
Electrical Ratings for +12V / 24V (powered by the con-
trol panel)*
Input Voltage: 10-25VDC regulated (power-limited out-
put from Listed control panel).
Input Current:
10VDC standby: 162mA
12VDC standby: 125mA
15VDC standby: 110mA
24VDC standby: 100mA
25VDC standby: 100mA
Wi-Fi Module: (Optional) Add 40mA to the above.
(With peak RF transmission current of 300mA).
Electrical Ratings for the IN 1 Fire Input:
Input Voltage: 9-25VDC.
Maximum Input Current: Up to 2mA from FACP NAC
circuit
WI2326LF 12/18
333 Bayview Avenue, Amityville, New York 11701
For Sales and Repairs, (800) 645-9445
For Technical Service, (800) 645-9440 or visit us at
http://tech.napcosecurity.com/
(Note: Technical Service is for security professionals only)
Publicly traded on NASDAQ Symbol: NSSC
© NAPCO 2018
INTRODUCTION
The SLE-LTEVI-FIRE Dual-Path Alarm Communicator is
specifically designed to interface with FACP (Fire Alarm
Control Panels) and to comply with UL 864. The SLE-
LTEVI-FIRE is equipped with two dry relays, one for a
trouble output and one for an auxiliary output. The unit is
also equipped with four supervised inputs to report a Fire
Alarm, a Fire Trouble, a Water Flow Alarm and a Supervi-
sory Alarm, each triggered from the N/O and Common ter-
minals of the associated FACP output relays.
When connected to a FACP with one or two standard RJ-
45 telephone inputs, the SLE-LTEVI-FIRE provides two
RJ-45 outputs to satisfy both telephone inputs. The prima-
ry RJ-45 output is supervised and reports a trouble to the
central station upon any open or short on the primary RJ-
45 wires that prevent reporting. The secondary telephone
line is supervised by the FACP; when a line fault is detect-
ed, a trouble is reported to the central station through the
primary telephone line.
When connected to a FACP without digital dialing capabil-
ity, the StarLink™SLE-LTEVI-FIRE Dual-Path Commercial
Fire alarm capture radio communicator is a fully super-
vised, wireless digital two-way subscriber unit supported by
an extensive nationwide wireless network. The SLE-
LTEVI-FIRE is compatible with most 12 or 24VDC alarm
control panels (always adhere to the documentation provid-
ed by the control panel manufacturer). Mount the unit to a
single-, dual-, or three-gang electrical box and route the
wires through the back knockout(s), or as specified by local
codes. See WI2140 for programming information.
The SLE-LTEVI-FIRE communicator uses proprietary
data-capture technology that captures the alarm report
from the control panel and transmits the alarm signals to
the SLE Control Center; the alarm signals are then for-
warded to ANY central station via Contact ID or 4/2 via
DACT from the NOC or Sur-Gard System II, Sur-Gard Sys-
tem V, Bosch D6100IPV6 or Bosch D6600 Receiver (with
ITS-D6686 Ethernet Adapter) via TCP/IP using standard
line security. The SLE Control Center reports a trouble
signal in the event that the network does not receive the
expected supervision signal from the wireless communica-
tor. In addition, the SLE-LTEVI-FIRE is powered directly
from the control panel.
SLE-LTEVI-FIRE - Commercial / Residential Fire LTE Veri-
zon Network Compatible GSM alarm capture Communi-
cator. SIM card included. Red plastic enclosure. Rated
nominal 12/24VDC input.
StarLink™
Commercial SLE-LTEVI-FIRE
Dual-Path Alarm Communicator
INSTALLATION INSTRUCTIONS
*For Commercial Fire installations, a UL Listed Fire Alarm regulated power
supply or FACP regulated auxiliary output is required.
AGENCY LISTINGS
UL 864 Standard For Control Units and Accessories For
Fire Alarm Systems, 10th Edition

2 StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions
Electrical Ratings for IN 2, IN 3, IN 4, and IN 5:
(Inputs IN 2, IN 3, IN 4, and IN 5 are Class B)
Maximum Loop Voltage: 25VDC input.
Maximum Loop Current: 1.7mA
End of Line Resistor (EOLR) Value: 10K
Electrical Ratings for PGM3 Output:
Open Collector Output: Maximum Voltage 25VDC.
Maximum PGM Sink Current: 50mA (up to 15VDC),
25mA (15.1VDC - 25VDC)
Physical (W x H x D)
Plastic Housing: 8 x 5-29/64 x 1½" (20.3 x 13.9 x 3.8cm)
Mounting: Plastic housing includes three keyhole slots
for triple gang boxes (see scale template on page 13);
Environmental
Operating Temperature: 0°C - 49°C (32°F - 120°F)
Humidity: Maximum 93% Non-Condensing
Indoor / dry location use only
TERMINAL DESCRIPTIONS
Configure all inputs and outputs using the Management
Center screen (located at www.NapcoNOC.com). Located
at the bottom of the StarLink radio PC board, the terminals
are described as follows:
TB1: PWR (+10 - 25VDC)
(Refer to section "STEP 4: APPLY POWER")
TB2: PWR GND (–)
(Refer to section "STEP 4: APPLY POWER")
TB3: PGM3 (–): Open collector output. PGM3 is nor-
mally on (active low). When it is triggered (for exam-
ple, a trouble is detected) it becomes open collector/
high. To have a zone dedicated to an StarLink radio
trouble, insert one side of the end of line resistor into
this PGM3 terminal, and wire the other side of the
resistor to the positive terminal of the zone.
TB4: IN 1 (+): Smart Channel input. Active high input
for wiring to the control panel bell output. When this
input detects a pulsing temporal 3 high, it sends a
Fire alarm; a pulsing temporal 4 (CO Alarm), a CO
alarm is sent. When used, these conductors must
be run in conduit (max 20 feet for Commercial Fire,
and 3 feet for Residential Fire). For this input to
report to a central station, the StarLink radio must
be configured with the central station telephone
number and correct reporting formats and codes.
For more information, see WI2140 located at
www.NapcoNOC.com.
TB5: IN 2 (+): Fire Trouble input**. Wire to FACP
trouble relay N/O with parallel 10K EOLR at FACP.
Note: Inputs IN 2, IN 3, IN 4 and IN 5 can be su-
pervised end-of-line resistor inputs that can be trig-
gered with N/O or N/C relay contacts. Wire the
common ground terminal GND (terminal TB13) to
the relay common. For these inputs to report to a
central station, the radio must be configured with the
central station telephone number and correct report-
ing formats and codes.
TB6: IN 2 (–): See TB5, above.
TB7: IN 3 (+): Fire Alarm input**. Wire to FACP Fire
Alarm relay N/O with parallel 10K EOLR at FACP.
TB8: IN 3 (–): See TB5 and TB7, above.
Secondary Telephone: RJ-45 socket for FACP DACT
connection.
Primary Telephone: RJ-45 socket for FACP DACT con-
nection.
TB9: IN 4 (+): Supervisory Alarm input**. Wire to
FACP Supervisory relay N/O with parallel 10K
EOLR at FACP.
TB10: IN 4 (–): See TB5 and TB9, above.
TB11: IN 5 (+): Water Flow Alarm input**. Wire to
FACP Water Flow relay with parallel 10K EOLR at
FACP.
TB12: IN 5 (–): See TB5 and TB11, above.
TB13: GND: Earth ground terminal.
Ethernet: Connect the SLE Dual-Path radio communica-
tor to your broadband modem, router or switch.
Note: The cable modem/router and switch (if
Supervised Fire Input Wiring Option
10K
10K
CCN/O
Alarm
N/O
TBL*
To StarLink
Terminals
IN2 (TB5)
-or-
IN3 (TB7)
Radio GND
(TB6 and
TB88)
The EOLR must be installed and located within the control panel housing.
(Radio)
(Alarm Panel)
5 7
-or-
N/C
*Reverse polarity / energized state.
**Factory programmed options; may be changed at the NOC website (www.NapcoNOC.com)
6 8
-or-

StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions 3
any) at the premises requires standby power, there-
fore a UL 1481 / UL 864 or UL Listed ITE UPS must
be used at the premises to power these devices for
a minimum of 24 hours.
TB19: N/O OUT1: Normally open. Dry contact Form C
relay. Add shunt to lower two pins of JP1 for wet
contacts.
TB20: C OUT1: Common. Dry contact Form C relay.
Add shunt to lower two pins of JP1 for wet contacts
(connects relay Common to system ground). Relay
rated 30V AC/DC, 500mA.
TB21: N/C OUT1: Normally closed. Dry contact Form
C relay. Add shunt to lower two pins of JP1 for wet
contacts.
TB22: N/O OUT2: Normally open. Dry contact Form C
relay.
TB23: C OUT2: Common. Dry contact Form C relay.
Relay rated 30V AC/DC, 500mA.
TB24: N/C OUT2: Normally closed. Dry contact Form
C relay.
LED DESCRIPTIONS
The PC board contains several LED's, as follows:
GREEN RF SIGNAL STRENGTH LED
Labeled "D3", this LED is located at the lower right cor-
ner of the PC board.
Every 30 seconds, the StarLink radio receiver section
turns on and listens to the cell tower. Depending on the
signal strength detected, it will blink the Signal Strength
LED from 1 to 8 times, providing a signal strength indica-
tor that is updated constantly and is always displayed.
Refer to Coverage Table below.
Green LED Operation
Signal strength (as received by the radio) is displayed by
this LED blinking 1 to 8 times at a constant rate (with a
short delay between blink cycles). Acceptable power
level is greater than or equal to -91dBm (minimum 4
blinks at the mounting location).
YELLOW OPERATIONAL STATUS LED
Labeled "D4", this LED is located at the bottom right of
the PC board. Operation is as follows:
Normal Standby Condition:
Blinks on momentarily every 10 seconds: Unit is in
standby waiting for an alarm to report.
Processing Alarm Conditions:
When processing an alarm, this LED will blink variably
during each part of the process (dialing, handshaking,
data transmission, etc.).
GREEN RF SIGNAL STRENGTH LED
RADIO RECEIVER COVERAGE TABLE
LED Blinks 8 7 6 5 4 3 2 1
-55 -65 -75 -85 -91 -95 -99 -105
Power
(dBm)
LED LOCATIONS
D4 D3 D5
RED DIAGNOSTIC LED (Labeled "D7")
YELLOW OPERATIONAL STATUS LED (Labeled "D4")
GREEN RF SIGNAL STRENGTH LED (Labeled "D3")
RED TROUBLE LED (Labeled "D5")
FIRE PROGRAMMING OPTION PERMITTED IN
UL864? (Y/N) AVAILABLE SETTINGS REQUIRED UL 864 SETTINGS
Unattended Remote Downloading No Enable / Disable
Disabled (Jumper 1 installed). Also required for Commercial installations. Note:
See page 7 "Configuration Download / Firmware Updates" for jumper instruc-
tions.
IN2, IN3, IN4 and IN5 Unsupervised Yes Supervised / Unsupervised Unsupervised using conduit within 20 feet of FACP (default). If not using conduit,
install Jumpers 4 and 5 and EOL Resistors.
7 Day Supervision, Radio to NOC No
200 seconds, 5 minutes, 6
minutes, 60 minutes, 6
hours, 7 days
200 seconds, 5 minutes, 60 minutes. 6 Hours permitted in Commercial Fire UL
864 with Dual Path enabled.
Trouble on Radio or IP Path
(Annunciate / Report) Yes Either Path or Both Paths Either Path (annunciation and report of trouble).
NOTICE TO AUTHORITIES HAVING JURISDICTION, USERS, INSTALLERS,
DEALERS, AND OTHER AFFECTED PARTIES
Wi-Fi Module Yes Enable / Disable May be enabled as a primary reporting path for Fire.

4 StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions
YELLOW IP NETWORK STATE LED
Labeled "D15" (or DS15), this LED is located to the right
of the ETHERNET socket on the PC board. Operation
is as follows:
Off = No power
Steady with 1 quick blink off every 1.7 seconds
when reporting signal to NOC
Steady with 2 quick blinks off every 1.7 seconds
when downloading to control panel or the module
Slow Flashing:
1 Blink: Ethernet Available
2 Blinks: Wi-Fi Station Mode (normal operation)
SUPPLYING POWER
Control panels can provide power through their Auxiliary
Power terminals if the available standby current is reduced
by the SLE standby power (refer to Electrical Ratings for
+12V / 24V).
Note: The cable modem/router and switch (if any) at
the premises requires standby power, therefore a UL 1481
or UL 864 Listed UPS must be used at the premises to
power these devices for 24 hours (unless an engine driven
generator is provided on the premises, then only 4 hours of
UPS backup are required).
JUMPER DESCRIPTIONS
Jumper block labeled "X5"; from top to bottom, as detailed
in the following table. Note: Contact ID is always availa-
ble in response to a Contact ID handshake.
The SLE series radios are compatible with 4/2 Pulse Dial-
ing formats with 10pps, 20pps, and 40pps with and with-
out checksum, either 1400Hz or 2300Hz handshake /
kissoff. See table of formats on page 5.
Refer to WI2140 for selecting the required handshake /
kissoff frequency in the NOC (www.NapcoNOC.com) set-
up screens (as required by the control panel).
NETWORK COVERAGE
The StarLink radio constantly supervises the cell network
coverage. When the StarLink radio detects a loss in net-
RED TROUBLE LED
Labeled "D5", this LED is located at the bottom right of
the PC board. Operation is as follows:
1 Blink: Low Aux Power input voltage
2 Blinks: Battery trouble
3 Blinks: Alarm report Failed to Communicate
(will restore only when the radio path is restored)
4 Blinks: RF trouble (antenna connection or cellu-
lar registration)
5 Blinks: Radio poll or check-in failure (radio and/or
Ethernet). Either or both paths will trigger the trouble,
but for the trouble to clear, unit requires both IP and
radio polling/checkins to be operational
6 Blinks: Unit disabled (reporting or control panel
downloading not allowed)
7 Blinks: Unit was shutdown and has no function-
ality; requires a restart (full power down and full power
up sequence) to restore operation.
8 Blinks: Telco Line Cut (this is not the DACT in-
terconnect to the radio)
RED DIAGNOSTIC LED
Labeled "D7", this LED is located in the middle of the
PC board. One blink indicates a weak or non-existent
signal from the network (green LED is off). If this red
LED is blinking in any other manner, please contact
technical support.
GREEN IP NETWORK CONNECTION LED
Labeled "D14" (or DS14), this LED is located to the right
of the ETHERNET socket on the PC board. Operation
is as follows:
Off = No network cable detected
Fast Flash = No IP connection (Occurs just after
power on, while trying to obtain a IP address)
Slow Flash = Normal IP network operation
1 Blink: Static IP
2 Blinks: DHCP
3 Blinks: Auto IP (if unable to acquire DHCP ad-
dress, then after 5 minutes it will convert to Auto IP)
RED IP NETWORK TROUBLES LED
Labeled "D16" (or DS16), this LED is located to the right
of the ETHERNET socket on the PC board. Operation
is as follows:
Off = No troubles
Fast Flash = No IP connection (occurs just after
power on while trying to obtain a DHCP address)
Slow Flashing:
1 Blink: No network cable detected
2 Blinks: No access to the Internet
3 Blinks: Ethernet failed to communicate
4 Blinks: Ethernet poll / checkin fail
5 Blinks: Wi-Fi is enabled, but SLE-WIFI-MODULE
is not detected
6 Blinks: Wi-Fi no access to the Internet
7 Blinks: Wi-Fi failed to communicate
8 Blinks: Wi-Fi poll / checkin failure
9 Blinks: Wi-Fi serial data error or no serial data re-
sponse
10 Blinks: Wi-Fi Security / Authentication failed
Jumper Block "X5" Options
Jumper block labeled "X5" contains 5 jumper terminals; from top (labeled
"1") to bottom (labeled "5") as follows:
Jumper ON Jumper
Number Jumper OFF
Tech on site must temporarily
remove to download 1 Not permitted by UL 864
4/2 with Checksum Pulse Format* 2 4/2 Pulse Format*
Supervised inputs. EOLR(s)
required, see page 2 4 and 5
Not permitted by UL 864 (UL 864
permits use of conduit within 20
feet of FACP in lieu of Supervi-
sion)
*See table "NOTICE TO AUTHORITIES HAVING JURISDICTION..." on page 3.

StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions 5
work coverage, the StarLink radio must be configured to
prompt the control panel to announce a Telco Line Cut
failure trouble using the Management Center screen
(located at www.NapcoNOC.com).
INSTALLATION STEPS
STEP 1: ACCOUNT REGISTRATION
Create a new account and register specific StarLink radio
modules at www.NapcoComNet.com. Accounts and
modules registered via the Internet are enabled for activa-
tion within 24 hours.
STEP 2: SELECT A MOUNTING LOCATION
The mounting location should be indoors within the pro-
tected area and selected based on RF performance. It is
HIGHLY recommended that the installer carefully adhere
to the following recommendations BEFORE any wires are
installed.
Generally, high locations are best. DO NOT mount
radio in basements or below grade as unpredictable
performance may result.
DO NOT mount the radio in non-climate controlled en-
vironments (i.e. attics may become extremely hot in
summer, garages may become extremely cold in win-
ter).
Avoid mounting locations within 3 feet of AC power
lines, fluorescent light fixtures, or large metal objects
(air conditioners, metal garage doors, etc.) as these
locations have been shown to have a detrimental ef-
fect on signal strength.
NOC Originated
Alarms
Contact ID
Event Data
Sent
Pulse Format
Event Code
Sent
Initiated By Comments
Supervisory Fail E356 A00 Zn000 99
Automatically by NOC if fail to receive
any signal from StarLink radio within
Supervisory Timeout duration.
For Auto Enroll, uses captured telephone
number, Sub ID and format. For Dealer
Programmed, uses entered telephone
number, Sub ID and format.
Press to Send
Test Signal E601 A00 Zn000 98
Manually by dealer from the Manage-
ment Center Signal Log screen
(located at www.NapcoNOC.com).
Sends test into CS receiver.
Same comment as above.
Press to Send
Radio Test
Not Applicable
Nothing sent to
CS receiver
Not Applicable
Manually by dealer from the Manage-
ment Center Checkins screen (located
at www.NapcoNOC.com). Sends a
command to the StarLink radio to force
a check-in to the NOC.
----
SIGNALS ORIGINATED AT THE NOC
Cover Tamper Switch
The SLE series radios in the plastic housings are
provided with a front tamper switch. Note: The
tamper switch on the radio PC board is always
functional and requires no programming.
STARLINK RADIO RELATED EVENT
REPORT CODES (Contact ID by default)
EVENT AREA CONTACT ID PULSE
4/2**
CODE ZONE #
IN 1 Fire 0 E110 990 1A
IN 2 Trouble 0 E373 992 F2
IN 3 Fire 0 E110 993 1A
IN 4 Supervisory 0 E200 994 00
IN 5 Water Flow 0 E113 995 13
Low Battery/Voltage 0 E302 994 F4
Tamper Trouble 0 E341 995 F5
Line Cut 0 E352 996 F6
Reboot 0 E625 997 F7
IN 1 CO (Carbon Monoxide) 0 E162 998 18
Medical Alarm* E100
24 hour Aux. Alarm* E150
24 hour Aux. Restore* R150
Keypad Emergency Alarm* E140
A.C. Trouble* E301
Tel 1 Fail* E351
Fire Polling Report E780 999 F9
Supv Failure Report E788 000 D1 or D2
Tip/Ring Wiring Fault Report E789 000 F2
Path Test Report E602 890 77
*Not generated by the StarLink radio.
**See table "NOTICE TO AUTHORITIES HAVING JURISDICTION..." on page 3.

6 StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions
STEP 5: SIGNAL VERIFICATION
After triggering channels, use the StarLink radio Signal
Verification to ensure that the StarLink radio Network has
properly received the signals.
Verify Online: To verify that the signals have been
received by the StarLink radio GSM Network online, go
to www.NapcoNOC.com, log in with your Username and
Password, enter your Company ID number and the
StarLink GSM Radio Number, then click Signal Log.
IMPORTANT: Verify that the signals transmitted by the
StarLink radio have been properly received by your central
station before leaving the premises.
NOTE: This equipment has been tested and found to
comply with the limits for a Class B Unintentional Radiator,
pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful
interference in a residential installation. This equipment
generates, uses, and can radiate radio frequency energy
and, if not installed and used in accordance with the In-
struction Manual, may cause harmful interference to radio
communications. However, there is no guarantee that in-
terference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or tele-
vision reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to cor-
rect the interference by one of more of the following
measures: 1. Reorient or relocate the receiving antenna;
2. Increase the separation between the equipment and re-
ceiver; 3. Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected; 4.
Consult the dealer or an experienced radio/TV technician
for help.
NAPCO GEMINI C-SERIES (GEMC)
CONTROL PANEL PROGRAMMING
To program the central station receiver reporting format,
use PCD-Windows Quickloader download software. Open
the Digital Communications screen, Central Station Re-
ceivers tab, as shown in the following image:
A "Point ID" (also called "Contact ID") receiver format pro-
gramming example:
The radio can transmit to any central station capable of
receiving SIA Contact ID or 4/2 via DACR technology or
the DSC Sur-Gard Model System II or Sur-Gard System V
central station receivers, Bosch D6100IPV6 or Bosch
D6600 Receiver (with ITS-D6686 Ethernet Adapter) via
TCP/IP using standard line security.
Note: A receiver reporting format must be entered for
each telephone number used, but each telephone number
may be assigned a different format.
A fair amount of care may be required to mount the ra-
dio so as to achieve an optimal RF path. The installer
should spend as much time as needed to obtain the
highest signal level possible.
a. Before applying power, be sure to connect the
antenna. Temporarily connect power to the radio
from a fully charged 12V (4AH minimum) battery.
DO NOT mount the StarLink radio at this time. Press
Tamper switch to send a signal.
b. Position the unit in the desired mounting location,
with antenna oriented vertically. The signal strength
is displayed by the Green "Signal Strength LED" la-
beled "D3" (located at the lower right corner of the
PC board). The GSM radio tower signal strength
may fluctuate from day to day, therefore it is best to
try to find a mounting location where the LED pro-
vides a minimum of 4 blinks.
c. Once a location has been selected based on signal
coverage, permanently secure the unit using #8
screws (not supplied) in the two mounting holes.
WARNING: To ensure user safety and to satisfy FCC
RF exposure requirements, this unit must be installed so
that a minimum separation distance of 60cm (24") is al-
ways maintained between the antenna of the transmitting
device and nearby persons.
STEP 3: WIRING
22-gauge wire may be used if mounted up to 50 feet from
the control panel, and 18-gauge wire should be used for up
to 100 feet. Reference the wiring diagrams further in this
manual. See the section CONTROL PANEL PROGRAM-
MING further in this manual.
The wiring between the control panel and the StarLink ra-
dio is over several wires, as follows:
TB1: PWR
TB2: PWR GND (–)
TB21: N/C OUT1: Wired to the (+) of a zone dedi-
cated to monitoring the radio status. Should be pro-
grammed on Napco GEMC control panels as Monitor
or Supervisory Zone.
TELCO PRIMARY to FACP Telco 1 RJ-45 socket.
TELCO SECONDARY to FACP Telco 2 RJ-45 socket.
(Place JP1 shunt on bottom two pins)
Optional: Wire IN2 with a 10K EOLR in parallel with
the FACP trouble relay output Common and N/O (or in
series with Common and N/C).
Wiring Methods
Strip wire carefully to avoid exposed conductors after
installation, etc.)
Use of Listed wire, ensuring that all conductors are to be
insulated for the maximum voltage of any conductor in
the enclosure
All wiring methods must be performed in accordance
with NFPA70, Articles 725, and 800
STEP 4: APPLY POWER
Attach antennas before applying power !
Apply 12/24VDC to terminals 1 and 2.

StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions 7
relay. Wire this relay to the StarLink module IN 2 terminal;
by wiring the EOLR in parallel with Common and N/O of the
OUT1 relay. Note: We recommend using the text "GSM
Trouble" as the Zone Description.
StarLink Radio Supervision
If the two Telco wires (DACT interconnect wiring to the ra-
dio) between the StarLink radio and the control panel are
cut or otherwise disconnected, the control panel must de-
tect and generate a local trouble indication. The control
panel must trigger an output to activate the StarLink radio to
report this line cut fault to the central station. Program the
control panel for telephone supervision. Program the Star-
Link radio using the Management Center "Advanced Fea-
tures" screen (at www.NapcoNOC.com) to enable the Line
Cut feature on all troubles (therefore a dedicated zone is
not required). Note: Some control panels may require a
different duration than the default time of 3 minutes. See
also the alternate supervision method described on page
12, "Alternate Telco Line to Alarm Panel Supervision
(For Primary Mode Only)".
Supervision Time Schedule Considerations
If a status change (alarm trouble, etc.) is transmitted, the
radio supervision timer is restarted.
For example, if a status change is sent, the next regular
supervision transmission will occur at the interval deter-
mined by your rate plan.
Configuration Download / Firmware Updates
Technician on site required.
For Commercial Installations a technician is required to be
on site during any reprogramming of the radio or control
panel and must perform / re-perform acceptance testing.
To perform a download or update the radio firmware, jump-
er 1 must be removed. UL requires that the jumper be re-
placed after the download is complete. Failure to replace
the jumper would allow downloads to the radio without
a technician on-site.
For Residential installations jumper 1 may be removed to
permit uploading and downloading without a technician on
site, however, the dealer is responsible for ensuring the
system is operating correctly after any downloads or
changes to the system.
CAUTION: The installer should always be certain an
area code is programmed into the control panel.
Optional: If you wish the StarLink radio to report a code
and zone number (Contact ID by default) to the central sta-
tion in response to a triggered input event, see the table on
page 5. Note: These event codes and zone numbers can
be changed from the Management Center screen (located at
www.NapcoNOC.com).
Upon alarm, the NOC can optionally send an SMS message
to a third party that includes the appropriate Contact ID
alarm code, including the zone or user number, if applicable.
The "STARLINK RADIO RELATED EVENT REPORT
CODES" table also includes the most common Contact ID
alarm codes.
Programming StarLink Radio Troubles
It is required that if a StarLink radio or control panel trouble
is detected, that it is reported to the central station.
When the StarLink radio detects and sends a trouble to the
control panel, the control panel must be programmed to
annunciate this trouble. The radio can detect multiple trou-
bles as indicated by the "Red Trouble LED" ("D5"). For
these troubles to be annunciated at the control panel, there
are several methods, some of them are configurable at the
Management Center screen (www.NapcoNOC.com):
Wire the radio OUT1 relay to a dedicated control panel
zone (input) to annunciate the trouble. Two wiring options
are available:
Activate the trouble with an open by wiring the
EOLR in series with the Common and N/C of the
OUT1 relay;
Activate the trouble with a short by wiring the
EOLR in parallel with the Common and N/O of
the OUT1 relay
The radio must also report this trouble to the central station.
With Napco GEMC series control panels, wire the zone as
indicated in the wiring diagrams further in this manual.
Optionally, the FACP trouble relay can be used to trigger a
report to the central station.
Wire the FACP trouble relay to IN2; Common and N/O ter-
minals in parallel with a 10K EOLR. With Gemini C-Series
(GEMC) control panels, we recommend using the Fire Aux
Relay. Program the Fire Aux Relay to activate as a trouble

8 StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions
CONTROL PANEL PC BOARD
LOCAL
DOWNLOAD
TELCO
SECONDARY
TELCO
PRIMARY ETHERNET
1
(+)
2
(‒)
POWER PGM3 IN1 IN2 IN3
3
(‒)
4
(+)
5
(+)
6
(‒)
8
(‒)
7
(+)
9
(+)
10
(‒)
12
(‒)
11
(+)
13
EGND 19
N/O
21
N/C
20
C
IN4 IN5 OUT1
22
N/C
24
N/O
23
C
OUT2
Wiring Diagram for PRIMARY Reporting Configuration
for Generic FACPs without TELCO RJ Sockets
*Refer to section
"SUPPLYING POWER".
Note: Optionally
connect IN2 to a panel
output used for
identifying Telco line cut
(this is the DACT
interconnect wiring to the
radio).
PRIMARY TELCO SECONDARY TELCO
IN PHONES IN PHONES
22kΩ22kΩ
NC
RJ31X
RING TIP
AUX
POWER
(+) (‒)
ENERGIZED
TROUBLE
RELAY
C NO
GREENRED
WIRE DIRECTLY TO CONTROL
PANEL (USE FOR SHORTER DISTANCES)
OPTIONAL: WIRE TO RJ31X
(USE FOR LONGER DISTANCES)
10kΩ
(STARLINK RADIO HOUSING)
StarLink Radio Terminals
PC Board: All connections are power limited except AC Mains and battery terminals.
JP1
Shunt JP1 on
bottom 2 pins
**EOLR could
be placed in
parallel to
create a
supervisory
alarm.
Optional: Use 12
or 24VDC Listed
power supply*.
Note: Common
radio ground and
FACP ground.
GREEN
RED
(CONTROL PANEL HOUSING)
MONITOR ZONE
(+) DEDICATED
TO GPRS
SUPERVISION
2.2K**
10kΩ
10kΩ
10kΩ

StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions 9
CONTROL PANEL PC BOARD
LOCAL
DOWNLOAD
TELCO
SECONDARY
TELCO
PRIMARY ETHERNET
1
(+)
2
(‒)
POWER PGM3 IN1 IN2 IN3
3
(‒)
4
(+)
5
(+)
6
(‒)
8
(‒)
7
(+)
9
(+)
10
(‒)
12
(‒)
11
(+)
13
EGND 19
N/O
21
N/C
20
C
IN4 IN5 OUT1
22
N/C
24
N/O
23
C
OUT2
Wiring Diagram for PRIMARY Reporting Configuration
for Generic FACPs with TELCO RJ Sockets
*Refer to section
"SUPPLYING POWER".
Note: Optionally
connect IN2 to a panel
output used for identifying
Telco line cut (this is the
DACT interconnect wiring
to the radio).
NC
AUX
POWER
(+) (‒)
ENERGIZED
TROUBLE
RELAY
C NO
10kΩ
(STARLINK RADIO HOUSING)
StarLink Radio Terminals
PC Board: All connections are power limited except AC Mains and battery terminals.
JP1
Shunt JP1 on
bottom 2 pins
**EOLR could
be placed in
parallel to
create a
supervisory
alarm.
Optional: Use 12
or 24VDC Listed
power supply*.
Note: Common
radio ground and
FACP ground.
(CONTROL PANEL HOUSING)
MONITOR ZONE
(+) DEDICATED
TO GPRS
SUPERVISION
2.2K**
TELCO RJ SOCKET
10kΩ
10kΩ
10kΩ

10 StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions
CONTROL PANEL PC BOARD
LOCAL
DOWNLOAD
TELCO
SECONDARY
TELCO
PRIMARY ETHERNET
1
(+)
2
(‒)
POWER PGM3 IN1 IN2 IN3
3
(‒)
4
(+)
5
(+)
6
(‒)
8
(‒)
7
(+)
9
(+)
10
(‒)
12
(‒)
11
(+)
13
EGND 19
N/O
21
N/C
20
C
IN4 IN5 OUT1
22
N/C
24
N/O
23
C
OUT2
(STARLINK RADIO HOUSING)
StarLink Radio Terminals
PC Board: All connections are power limited except AC Mains and battery terminals.
JP1
Shunt JP1
on top 2 pins
EOLR and zone
could be placed
in parallel across
Cand N/O to
create a
supervisory
alarm.
Wiring Diagram for FACP Relay Trigger Input Reporting
*Refer to section "SUPPLYING POWER".
NC
AUX
POWER
(+) (‒)
NORMALLY
ENERGIZED
N/C TROUBLE
RELAY
C NO
10kΩ
Aux Power:
Regulated 12/24VDC or
optionally use 12 or 24VDC
Listed power supply*.
Note: Common radio
ground and FACP ground.
(CONTROL PANEL HOUSING)
MONITOR ZONE
DEDICATED TO
GPRS
SUPERVISION
FIRE ALARM
DRY RELAY
SUPERVISORY
ALARM DRY
RELAY
WATER FLOW
ALARM DRY
RELAY
10kΩ10kΩ10kΩ
NO
C NC NO
C NC NO
C NC
2.2K

StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions 11
(STARLINK RADIO HOUSING)
StarLink Radio Terminals
LOCAL
DOWNLOAD
TELCO
SECONDARY
TELCO
PRIMARY ETHERNET
1
(+)
2
(‒)
POWER PGM3 IN1 IN2 IN3
3
(‒)
4
(+)
5
(+)
6
(‒)
8
(‒)
7
(+)
9
(+)
10
(‒)
12
(‒)
11
(+)
13
EGND 19
N/O
21
N/C
20
C
IN4 IN5 OUT1
22
N/C
24
N/O
23
C
OUT2
Wiring Diagram for GEMC-32, GEMC-96,
GEMC-128 and GEMC-255 Control Panels
(CONTROL PANEL HOUSING)
**
GEMC Control Panel
PC Board
*Refer to section "SUPPLYING POWER".
**Program only TELCO 1 supervision.
***Remove J300 shunt
Note: Connect IN2 to a panel output
used for identifying Telco line cut (this is
the DACT interconnect wiring to the radio).
EOLR for telco line supervision
required when the feature "Tip/
Ring Wiring Fault Report" is
enabled in the NOC.
PC Board: All connections are power limited except AC Mains and battery terminals.
JP1
Shunt JP1 on
bottom 2 pins
(these
connections
to the relay
are
optional)***
Or use a
12V/24V UL
Listed
monitored
power supply*
Remove J300
shunt when
using the
wiring shown
in this diagram
(Optional, for remote
communication)
10KΩ
2.2K
2.2K
OPTIONAL
MONITOR
ZONE
MONITOR ZONE
(+) DEDICATED
TO GPRS
SUPERVISION

12 StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions
*Note: On line cut, PGM1 will activate.
Alternate Telco Line to Alarm Panel Supervision (For Primary Mode Only)
A 10K ohm resistor (5% tolerance) can be placed across the "house side" of the telephone line circuit (see
wiring diagrams). Use this resistor instead of using a relay on the alarm control panel to trip an input on the
radio to supervise the connection between the alarm control panel telco circuit and the radio. Note: In
installations where two telco lines are used, a 22K ohm resistor (5% tolerance) is required for each telco line
(see wiring diagrams).
REMEMBER: Enable the feature " Tip / Ring Wiring Fault Report" in the NOC (www.NapcoComNet.com)
to supervise the telephone line connection to the control panel.
REMINDER: Never use this option when the alarm control panel is connected to telephone service!

StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions 13
Housing Template (1:1 Scale)
Three-Gang Mounting
Double-Gang

14 StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions
This page intentionally left blank.

StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions 15
Name Format Type Handshake Frequency Speed
Ademco Slow 4/2 1400 Hz or 2300Hz 10pps
Ademco Slow 4/2 checksum 1400 Hz or 2300Hz 10pps
Radionics Slow 4/2 2300Hz 10pps
Radionics Slow 4/2 checksum 2300Hz 10pps
Silent Knight Fast 4/2 1400 Hz or 2300Hz 20pps
Silent Knight Fast 4/2 checksum 1400 Hz or 2300Hz 20pps
Radionics Fast 4/2 2300Hz 40pps
Radionics Fast 4/2 checksum 2300Hz 40pps
Universal High Speed 4/2 1400 Hz or 2300Hz 40pps
Universal High Speed 4/2 checksum 1400 Hz or 2300Hz 40pps
4/2 Pulse Dialing
Format
Compatibility
Note: The SLE Series Radios are
compatible with any Listed 4/2
Receiver such as the Ademco 685.
REN = 0. The Ringer Equivalence Number (REN) indicates the maximum number
of devices allowed to be connected to a telephone interface. The termination of an
interface may consist of any combination of devices subject only to the requirement that
the sum of the RENs of all the devices not exceed five (5).
To terminate more than two conductors or
conductors of different wire sizes to a terminal,
use the "pigtail" type wiring method as shown at
right. Use insulated wire for the pigtail, and firmly
secure the conductors to the pigtail using an ap-
propriate wire nut or crimp connector for the num-
ber and gauge of conductors used.
IMPORTANT WIRING METHODS
Incorrect
Correct -- Use pigtail and wire nut / crimp connector
PIGTAIL
WIRE NUT OR
CRIMP
CONNECTOR
PIGTAIL
For single-conductor terminal
blocks (like the type shown at
left), to terminate more than one
conductor to a terminal, use the
wiring methods shown at right:
WIRE NUT OR
CRIMP
CONNECTOR
PIGTAIL
Correct -- Single incoming and/or pigtail with wire nut / crimp connectors
In
For "barrier" type terminal
blocks (like the type shown at
left), to terminate two conductors
to a terminal, use the wiring meth-
ods shown at right: Correct -- Separate incoming and outgoing conductors
In Out
Incorrect
Incorrect
In Out

16 StarLink™SLE-LTEVI-FIRE Commercial Series Dual-Path Alarm Communicator -- Installation Instructions
NAPCO SECURITY SYSTEMS, INC. (NAPCO)
warrants its products to be free from manufacturing
defects in materials and workmanship for thirty-six
months following the date of manufacture. NAPCO
will, within said period, at its option, repair or replace
any product failing to operate correctly without
charge to the original purchaser or user.
This warranty shall not apply to any equipment, or
any part thereof, which has been repaired by others,
improperly installed, improperly used, abused,
altered, damaged, subjected to acts of God, or on
which any serial numbers have been altered,
defaced or removed. Seller will not be responsible for
any dismantling or reinstallation charges.
THERE ARE NO WARRANTIES, EXPRESS OR
IMPLIED, WHICH EXTEND BEYOND THE
DESCRIPTION ON THE FACE HEREOF. THERE IS
NO EXPRESS OR IMPLIED WARRANTY OF
MERCHANTABILITY OR A WARRANTY OF
FITNESS FOR A PARTICULAR PURPOSE.
ADDITIONALLY, THIS WARRANTY IS IN LIEU OF
ALL OTHER OBLIGATIONS OR LIABILITIES ON
THE PART OF NAPCO.
Any action for breach of warranty, including but
not limited to any implied warranty of merchantability,
must be brought within the six months following the
end of the warranty period. IN NO CASE SHALL
NAPCO BE LIABLE TO ANYONE FOR ANY
CONSEQUENTIAL OR INCIDENTAL DAMAGES
FOR BREACH OF THIS OR ANY OTHER
WARRANTY, EXPRESS OR IMPLIED, EVEN IF
THE LOSS OR DAMAGE IS CAUSED BY THE
SELLER'S OWN NEGLIGENCE OR FAULT.
In case of defect, contact the security professional
who installed and maintains your security system. In
order to exercise the warranty, the product must be
returned by the security professional, shipping costs
prepaid and insured to NAPCO. After repair or
replacement, NAPCO assumes the cost of returning
products under warranty. NAPCO shall have no
obligation under this warranty, or otherwise, if the
product has been repaired by others, improperly
installed, improperly used, abused, altered,
damaged, subjected to accident, nuisance, flood, fire
or acts of God, or on which any serial numbers have
been altered, defaced or removed. NAPCO will not
be responsible for any dismantling, reassembly or
reinstallation charges.
This warranty contains the entire warranty. It is
the sole warranty and any prior agreements or
representations, whether oral or written, are either
merged herein or are expressly cancelled. NAPCO
neither assumes, nor authorizes any other person
purporting to act on its behalf to modify, to change,
or to assume for it, any other warranty or liability
concerning its products.
In no event shall NAPCO be liable for an amount
in excess of NAPCO's original selling price of the
product, for any loss or damage, whether direct,
indirect, incidental, consequential, or otherwise
arising out of any failure of the product. Seller's
warranty, as hereinabove set forth, shall not be
enlarged, diminished or affected by and no obligation
or liability shall arise or grow out of Seller's rendering
of technical advice or service in connection with
Buyer's order of the goods furnished hereunder.
NAPCO RECOMMENDS THAT THE ENTIRE
SYSTEM BE COMPLETELY TESTED WEEKLY.
Warning: Despite frequent testing, and due to,
but not limited to, any or all of the following; criminal
tampering, electrical or communications disruption, it
is possible for the system to fail to perform as
expected. NAPCO does not represent that the
product/system may not be compromised or
circumvented; or that the product or system will
prevent any personal injury or property loss by
burglary, robbery, fire or otherwise; nor that the
product or system will in all cases provide adequate
warning or protection. A properly installed and
maintained alarm may only reduce risk of burglary,
robbery, fire or otherwise but it is not insurance or a
guarantee that these events will not occur.
CONSEQUENTLY, SELLER SHALL HAVE NO
LIABILITY FOR ANY PERSONAL INJURY,
PROPERTY DAMAGE, OR OTHER LOSS BASED
ON A CLAIM THE PRODUCT FAILED TO GIVE
WARNING. Therefore, the installer should in turn
advise the consumer to take any and all precautions
for his or her safety including, but not limited to,
fleeing the premises and calling police or fire
department, in order to mitigate the possibilities of
harm and/or damage.
NAPCO is not an insurer of either the property or
safety of the user's family or employees, and limits its
liability for any loss or damage including incidental or
consequential damages to NAPCO's original selling
price of the product regardless of the cause of such
loss or damage.
Some states do not allow limitations on how long
an implied warranty lasts or do not allow the
exclusion or limitation of incidental or consequential
damages, or differentiate in their treatment of
limitations of liability for ordinary or gross negligence,
so the above limitations or exclusions may not apply
to you. This Warranty gives you specific legal rights
and you may also have other rights which vary from
state to state.
NAPCO LIMITED WARRANTY
Other manuals for StarLink SLE-LTEVI-FIRE
1
Table of contents
Other NAPCO Cell Phone manuals

NAPCO
NAPCO Gemini GEM-P1632 Installation manual

NAPCO
NAPCO StarLink SLE Series User manual

NAPCO
NAPCO StarLink Full Data SL-1FD-T User manual

NAPCO
NAPCO StarLink SLE-LTE Commercial Series User manual

NAPCO
NAPCO StarLink SLE-LTEVI-FIRE User manual

NAPCO
NAPCO StarLink SLE-LTEV-SS User manual

NAPCO
NAPCO StarLink SLE Series User manual

NAPCO
NAPCO StarLink Connect Series User manual

NAPCO
NAPCO Gemini GEM-P816 User manual

NAPCO
NAPCO Gemini GEM-P1632 Installation manual