ARO Series Universal Room Controller
Specification and Installation Instructions
www.neptronic.com Page | 7
Step / Display Description Default Range / Offset Increment
57. BO1 Hyst Low Percnt If BO1 is set to HYST at step 54, select the
hysteresis low range percentage.
20% 0 to 100% 1%
58. BO1 Hyst High Percnt If BO1 is set to HYST at step 54, select the
hysteresis high range percentage.
80% 0 to 100% 1%
59. BO1 Fan Add fan to BO1 mode (step 52). OFF ON or OFF --
60. BO1 Cool Add cooling to BO1 mode (step 52). OFF ON or OFF --
61. BO1 Heat Add heating to BO1 mode (step 52). OFF ON or OFF --
62. BO1 Dehum Add dehumidification to BO1 mode (step 52). OFF ON or OFF --
63. BO1 Hum Add humidification to BO1 mode (step 52). OFF ON or OFF --
64. BO1 Co2 Add CO2 to BO1 mode (step 52). OFF ON or OFF --
65. BO1 VOC Add VOC to BO1 mode (step 52). OFF ON or OFF --
Binary Output 2 (BO2)
66. BO2 Mode Determines how the controller calculates
the BO2 ramp output value. The controller
compares all the enabled input values
(steps 73 to 79) and uses the highest
demand or the average of all demands.
HIGH HIGH (Highest value) or
AvrG (Average of all values)
--
67. BO2 DIREV Direction of the binary signal: NO
(Normally Open) or NC (Normally Closed).
NO NO (Normally open) or
NC (Normally closed)
--
68. BO2 TPM Hyst BO2 operates using hysteresis (step 71
and 72) or TPM (step 69).
HYST HYST (Hysteresis) or
TPM (Time proportional modulation)
--
69. BO2 TPM CPH If BO2 is set to TPM at step 68, select the
number of cycles per hour.
4 3, 4 or 8 CPH (Cycles per hour) --
70. BO2 Anti Cycle Sec Select the delay before activating or
re-activating the contact.
0 sec 0 to 300 sec 1 sec
71. BO2 Hyst Low Percnt If BO2 is set to HYST at step 68, select the
hysteresis low range percentage.
20% 0 to 100% 1%
72. BO2 Hyst High Percnt If BO2 is set to HYST at step 68, select the
hysteresis high range percentage.
80% 0 to 100% 1%
73. BO2 Fan Add fan to BO2 mode (step 66). OFF ON or OFF --
74. BO2 Cool Add cooling to BO2 mode (step 66). OFF ON or OFF --
75. BO2 Heat Add heating to BO2 mode (step 66) OFF ON or OFF --
76. BO2 Dehum Add dehumidification to BO2 mode (step 66). OFF ON or OFF --
77. BO2 Hum Add humidification to BO2 mode (step 66). OFF ON or OFF --
78. BO2 Co2 Add CO2 to BO2 mode (step 66). OFF ON or OFF --
79. BO2 VOC Add VOC to BO2 mode (step 66). OFF ON or OFF --
Analog and Binary Inputs (AI1 and BI1)
80. AI1 Mode Select the type of sensor and event
associated with input AI1.
OFF OFF (None), OAT (Outside Air
Temperature), OCC (Occupancy status),
nSb (Night set back status), dFt (Dirty
filter), FLS (Air Flow Switch), FLP (Air Flow
Protection/Lockout)
--
81. BI1 Mode Select the type of sensor and event
associated with input BI1.
OFF OFF (None), OCC (Occupancy status),
nSb (Night set back status), dFt (Dirty
filter), FLS (Air Flow switch), FLP (Air Flow
Protection/Lockout)
--
82. Extern Temp Offset The display shows the temperature read
by input AI1. Adjust the offset by
comparing it with a known value.
Current
value
-40ºF to 257ºF / offset: ±18ºF
(-40ºC to 125ºC / offset: ±10ºC)
0.2ºF
(0.1ºC)
Outside Air Temperature (OAT)
The following features apply only if OAT is selected for AI1 at step 80.
83. AO1 OAT Hi Temp AO1 no longer modulates and remains at
its minimum voltage if the OAT read at AI1
is higher than this value.
122ºF
(50ºC)
-40ºF to 257ºF
(-40ºC to 125ºC)
0.2ºF
(0.1ºC)