Universal Wall-Mount Controller
Modbus Communication Module User Guide
www.neptronic.com page | 9
1 = Temperature and Demand, 2 = Setpoint and Demand, 3 = Temperature Only,
4 = Setpoint Only, 5 = Off
Temperature control source.
1 = Network Temp, 2 = Intern Temp, 3 = Extern Temp
Network fallback timeout.
Unit: Minutes, Range: 0 to 60, Value/1 (e.g. 30 mins = 30)
Minimum occupancy/day setpoint.
Unit: ºC/ºF, Range: 10ºC to max or 50ºF to max
Value x 10 (e.g. 18°C = 180 or 60ºF = 600)
Maximum occupancy/day setpoint.
Unit: ºC/ºF, Range: min to 40ºC or min to 104ºF
Value x 10 (e.g. 18°C = 180 or 60ºF = 600)
Cooling temperature setpoint in unoccupied or night mode.
Unit: ºC/ºF, Range: 10ºC to 40ºC or 50ºF to 104ºF
Value x 10 (e.g.18°C = 180 or 60ºF = 600)
Heating temperature setpoint in unoccupied or night mode.
Unit: ºC/ºF, Range: 10ºC to 40ºC or 50ºF to 104ºF
Value x 10 (e.g. 18°C = 180 or 60ºF = 600)
Heating proportional band for ramp 1.
Unit: depends on system unit, 0.5ºC to 5ºC or 1ºF to 9Fº
Value x 10 (e.g. 1ºC = 10 or 2ºF = 20)
Heating proportional band for ramp 2.
Unit: depends on system unit, 0.5ºC to 5ºC or 1ºF to 9Fº
Value x 10 (e.g. 1ºC = 10 or 2ºF = 20)
Cooling proportional band for ramp 1.
Unit: depends on system unit, 0.5ºC to 5ºC or 1ºF to 9ºF
Value x 10 (e.g. 1ºC = 10 or 2ºF = 20)
Cooling proportional band for ramp 2.
Unit: depends on system unit, 0.5ºC to 5ºC or 1ºF to 9ºF
Value x 10 (e.g. 1ºC = 10 or 2ºF = 20)
Changeover proportional band.
Unit: depends on system unit, 0.5ºC to 5ºC or 1ºF to 9ºF
Value x 10 (e.g. 1ºC = 10 or 2ºF = 20)
Heating deadband for ramp 1.
Unit: depends on system unit, 0ºC to 5ºC or 0ºF to 9ºF
Value x 10 (e.g. 1ºC = 10 or 2ºF = 20)
Heating deadband for ramp 2.
Unit: depends on system unit, 0ºC to 5ºC or 0ºF to 9ºF
Value x 10 (e.g. 1ºC = 10 or 2ºF = 20)
Cooling deadband for ramp 1.
Unit: depends on system unit, 0ºC to 5ºC or 0ºF to 9ºF
Value x 10 (e.g. 1ºC = 10 or 2ºF = 20)
Cooling deadband for ramp 2.
Unit: depends on system unit, 0ºC to 5ºC or 0ºF to 9ºF
Value x 10 (e.g. 1ºC = 10 or 2ºF = 20)
Unit: depends on system unit, 0ºC to 5ºC or 0ºF to 9ºF
Value x 10 (e.g. 1ºC = 10 or 2ºF = 20)