Humidity Controller
Specification and Installation Instructions
www.neptronic.com Page | 4
2. “inside temper sensor offset”
Offset:
Max. ± 5%
Compare the displayed temperature reading with a known value from a thermometer. To offset or calibrate the sensor, use the
arrows key to set the desired temperature reading. This is useful for thermostats installed in areas where the temperature read
is slightly different than the room’s actual temperature. For example, a humidistat placed right under the air diffuser.
3.“adjust minimum user setpnt”
Range:
10 to 90% RH
In Operation Mode, you cannot decrease the setpoint to less than the value set as the minimum humidity setpoint. The
minimum value is restricted by the maximum value set in Step 4 “adjust maximum user setpnt”. In other words, the value that is
set as the minimum cannot be greater than the maximum value.
4. “adjust maximum user setpnt”
Default:
Range:
65% RH
10 to 90% RH
In Operation mode, you cannot increase the setpoint to more than the value set as the maximum humidity setpoint. The
maximum value is restricted by the minimum value set in Step 3 “adjust minimum user setpnt”. In other words, the value that is
set as the maximum cannot be less than the minimum value.
5. “user setpnt locked”
Range:
No (Unlocked), Yes (locked)
If set to No, the user setpoint option is not locked and the user can adjust the desired humidity setpoint. If set to Yes, the user
setpoint option is locked and the user cannot set the desired humidity setpoint. A lock symbol appears to indicate that the
setpoint is locked.
Humidity Settings
6. “adjust control mode”
Default:
Range:
Hu (humidify only)
Hu (humidify only), AuTo (Automatic humidify and dehumidify), dEHU (dehumidify only)
Select the control mode that you want to authorize to the user. To authorize all the available modes, select AuTo(Automatic
Mode).
If you selected dEHu at this step, go to Step 8 “adjust dehumi setpnt”.
7.“adjust humidty setpnt”
Range:
10 to 90% RH
Set the desired humidity setpoint within the defined range. If the setpoint option was locked at Step 5 “user setpnt locked”, a
lock symbol is displayed. The setpoint value is restricted by the minimum (Step 3 “adjust minimum user setpnt”) and
maximum (Step 4 “adjust maximum user setpnt”) values. In other words, the setpoint should be within the minimum and
maximum setpoint range.
If you selected Hu at Step 6 “adjust control mode”, go to Step 9 “enable on off control mode”.
8. “adjust dehumi setpnt”
Range:
10 to 90% RH
Set the desired dehumidify setpoint within the defined range. If the setpoint option was locked at Step 5 “user setpnt locked”, a
lock symbol is displayed. The setpoint value is restricted by the minimum (Step 3 “adjust minimum user setpnt”) and
maximum (Step 4 “adjust maximum user setpnt”) values. In other words, the setpoint should be within the minimum and
maximum setpoint range.