BBTS/050929 1
Actuator
Installation instruction
BBTS1000 BBTS1005 BBTS1021 BBTS1060 BBTS1065 BBTS1080
Technical Data BT000S BT005S BT020S BT060S BT065S BT080S
Auxiliary switches No No Yes (2) No No Yes (2)
Feedback No Yes No No Yes No
Fail safe - Enerdrive No Yes
Power consumption 6 VA 15VA Peak, 6VA
Control signal 3 wire / 2 position,
3 wire / 3 point floating 2 wire / 2 position,
4 wire / 3 point floating
Running time through
90º 90 - 110 sec
(Fail-safe20-30 sec)
Torque 50 in.lb. [5,6 Nm] at rated voltage
Power supply 22 to 26 VAC or 28 to 32 VDC
Electrical connection 18 AWG [0.8 mm2] minimum
Inlet bushing 2 inlet bushing of 5/8 in [15.9 mm] & 7/8 in [22.2 mm]
Angle of rotation 0 to 90 degrees, mechanically adjustable (factory set with 90º stroke)
Direction of rotation Reversible, Clockwise (CW) or Counterclockwise (CCW) (factory set with CW direction)
Ambient temperature 0ºF to +122ºF [-18º C to +50º C]
Storage temperature -22ºF to +122ºF [-30º C to +50º C]
Relative Humidity 5 to 95 % non condensing.
Weight 3 lbs. [1.4 kg]
Warning: Do not press the clutch when actuator is powered
Dimensions
A
B
C
D
Dimension Inches Metric (mm)
A 1.50 38.1
B 3.26 82.8
C 6.60 167.5
D 3.01 76.4
Caution
We strongly recommend that all neptronic® products be wired to a separate transformer and that transformer shall service only neptronic® products. This precaution will
prevent interference with, and/or possible damage to incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.
1Enerdrive System U.S.A. Patent #5,278,454
New Number
BBTS1000 BT000S
BBTS1005 BT005S
BBTS1021 BT020S
BBTS1060 BT060S
BBTS1065 BT065S
BBTS1080 BT080S
Feature:
•Mounts easy on round
& square shaft (with option –8).
•External clutch for manual adjustments.
•Maintenance free.
•Position indicator.
•Fail safe by Enerdrive System1
(on model 1060, 1065 & 1080).
•Auxiliary switches
(on model 1021 & 1080).