Co2(carbon dioxide)
BtN MM (Buttons)
Cyc (cool anti cycle)
OFF(Control mode)
Main Menu
APP MM
(Applications)
PrS MM (Pressure)
Hr2(heating ramp 2)
CH(auto/off)
Co (changeover ramp)
CH1 (cool/heat)
OFF(none of the above)
on (manual heat/cool)
NEt(network)
Main Menu
= select / set value
tS1(Internal tempsensor offset)
23.5°C/74°F
EtS(Externaltemp sensor offset)
0.0°C/0°F
StP(Min user setpoint)
15.0°C/59°F
StP(Max user setpoint)
30.0°C/86°F
Loc(User setpoint locked)
no(unlocked)
YES (locked)
StP(User setpoint)
22.0°C/72°F
tS(Temp control sensor)
ItS(internal sensor)
EtS(external sensor)
Go to “Mt" MM
Go to
“Mt" MM
tFs (Network timeout)
5 min (0-60 min)
(10-40°C/50-104°F), inc. 0.5°C (1°F)
(10-40°C / 50-104°F)
(10-40°C/50-104°F)
CL(cool/off)
CtL (Ctrl temp source)
Aut (automatic, all)
Ht(heat/off)
= select / set value
yES
NO
StP(setpoints)
t°C(°C/°F and %RH)
dIS (Display info)
t°C (°C/°F, %RH & demand)
StP (setpoints & demand)
FrE (Freeze protect)
no (Disabled)
yES (Enabled)
2 min (0-15 min)
Stc (Cool/Heat switch time)
0 min (0-7200 sec)
Int (H) (Heat integral time)
0 sec (0-250 sec)
Int (C) (Cool integral time)
0 sec (0-250 sec)
Go to
“rMP"
Pb0(Changeover prop band)
2.0°C/4.0°F (0.5-5°C/1-9°F)
db0 (Changeover dead band)
0.3°C/0.6°F (0-5°C/0-9°F)
Hr1(heating ramp 1)
Cr2(cooling ramp 2)
Cr1(cooling ramp 1)
CFG (Ramp settings)
CO(changeover)
= scroll menu items
Pb1 (Cool prop band1)
2.0°C/4.0°F (0.5-5°C/1-9°F)
db1 (Cl dead band1)
0.3°C/0.6°F (0-5°C/0-9°F)
Pb2 (Cool prop band2)
2.0°C/4.0°F (0.5-5°C/1-9°F) db2 (Cool dead band2)
0.3°C/0.6°F (0-5°C/0-9°F)
Pb1 (Heat prop band1)
2.0°C/4.0°F (0.5-5°C/1-9°F)
db1 (Heat dead band1)
0.3°C/0.6°F (0-5°C/0-9°F)
Go to “Cr1"
Go to “Cr2"
Go to “Hr1"
Go to “Hr2"
Sub Menu Configuration
rMP MM (Ramps)
NEt MM (Network)
HrS MM (Time & Date)
SEt MM (Settings)
Mt§ MM (Motor)
tNP MM
(Temperature)
OUT MM (Outputs)
InP MM (Inputs)
= scroll menu items
StF(setpnt airflow 0-10Vdc)*
Hr2 (heating ramp 2)
Hr1 (heating ramp 1)
Cr2 (coolingramp 2)
Cr1 (cooling ramp 1)
Mr (Motor signal ramp)
OFF~
= select / set value
Mr(Motor direction)
dIr (direct)
rEv(reverse)
Go to “SEt" MM
Air (Airflow integral time)
0 (0-60 min)
Pb2 (Heat prop band2)
2.0°C/4.0°F (0.5-5°C/1-9°F)
db2 (Heat dead band1)
0.3°C/0.6°F (0-5°C/0-9°F)
Go to “CO2"
AV.10
(± 5°C/± 10°F)
AV.11
(± 5°C / ± 10°F)
Appears only if AI1 = EtS
AV.16 AV.17
BV.2
AV.15
MSV.4
EtS appears only if AI1 or AI2
is set to EtS AV.145
MSV.35 BV.40
MSV.17 BV.3 MSV.95 BV.6
AV.51
AV.170 AV.106 AV.30 AV.50
AV.56 AV.57
AV.41 AV.42
AV.46 AV.47
AV.21 AV.22
AV.24 AV.25
* = StF not available on pressure
dependent model EVCBNDT4S
* = Airflow integral not available on
pressure dependent model EVCBNDT4S
ANLg (analog 0-10Vdc)
Go to
“rMp"
BV.100
OFF (follows NSB/NoOcc)
Fco (Fan Always On Mode) †
on(always on)
†= For fan powered box applications and
available only with models:
- EVCB14NIT4S
- EVCB14NDT4S
- EVCB14NIT4SF
The analog or Triac output ramps must be set
to “On”
On = Fan is always on (continuous).
Off = Fan is off if control mode is off or if there
is no demand when in NSB or No Occupancy
mode via digital input or schedule.
BV.100
*** You must press the button to save any changes ***
*** Pressing the button returns to the previous step without saving ***
Mt (Motor using control wires)
FL2 (Floating2 using TO3/TO4)
FLo (Pressure independentoutput)
= select / set value
FL1(Floating1 usingTO1/TO2)
MSV.40 Go to “Mr” (Motor sig nal ramp)
(model EVCB14NIT4X only)
Motor minimum and maximum voltage, and feedback minimum and maximum
voltage are only available for model EVCB14NIT4X.
Mr(Motor minimum voltage)
2 V (0V-AV.96) AV.95
Mr(Motor maximum voltage)
10 V (AV.95-10 V) AV.96
Mf(Motor feedback minimum voltage)
2 V (0V-AV.98) AV.97
Mf (Motor feedback maximum voltage)
10 V (AV.97-10 V) AV.98
Go to “SEt" MM
(model EVCB14NIT4X only)
* = Airflow integral is not functional on
pressure dependent models, ignore the
option.
-EVCB14NDT4S
-EVCB14NDT2
~ = available on model
EVCB14NIT4X only.
§ = Mt (Motor) is not
functional on motor less
models such as
EVCB14NDT2. Ignore
the option.
* = StF not available on
pressure dependent
modelS
- EVCB14NDT4S
- EVCB14NDT2
*
*
*
*
*
**** *
**
**
*
***
****
* * ***
****
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
CM(CO2 control mode)
OPn (o pen)
CtL (control)
BV.101
*
*Go to “NEt" MM
Pb4(CO2prop band)
100ppm (50-250 ppm)
AV.190 *db4(CO2dead band)
20ppm (10-50 ppm)
AV.191 Go to “NE t" MM
*