INSTRUCTIONS
1. Place wire to be monitored through aperture.
Ensure monitored current fl ow matches arrow on
sensor or as noted on fi gure on reverse side.
2. Mount the sensor.
3. Connect power and output wiring.
A. Use 30-12 AWG copper wires rated 75°C mini-
mum. Tighten terminals to 5-7 in-lbs torque.
B. For current output models, ensure output load
is no more than 500 .
C. For voltage output models, ensure output load
is at least 25 K for 5 VDC and 50 Kfor 10
VDC.
4. Connect Power.
A. Connect the appropriate power supply.
DT 0 - 420 - 24U - U - FL
OUTPUT:
005 - 0-5 VDC
010 - 0-10 VDC
020 - 0-20 mA
420 - 4-20 mA
RANGE:
0 - 0 to 5, 10 or 20 Amps DC
1 - 0 to 50, 75 or 100 Amps DC
2 - 0 to 100, 150 or 200 Amps DC
Model Number KeySpecifi cations
Quick “How To” Guide
POWER SUPPLY:
24U - 24 VAC or VDC (Universal)
120 - 120 VAC
Power Supply 24 VAC/VDC (22-26 V): Power input
and output signal are not isolated. Fuse
DC supply at 5 A, AC supply at 2.75 A.
120 VAC (108-132 V): Power input and
output signal are isolated. (See Note)
Power Consumption 2 VA
Output Signal 0-20 mA, 4-20 mA, 0-5 VDC or
0-10 VDC
Output Limit 0-20 mA, 4-20 mA: 23 mA; 500 Ω max
0-5 VDC: 5.75 VDC; 25 KΩ min
0-10 VDC: 11.5 VDC; 50 KΩ min
Accuracy 1% FS
Repeatability 1% FS
Linearity 0.75% FS
Frequency Range DC
Response Time 60 ms (to 90% of step change)
Isolation Voltage Tested to 3 KV (Monitored line
to output)
Sensing Aperture 0.75” (19.1 mm) diameter
Case UL94 V-0 Flammability rated
thermoplastic
Environmental -4 to 122°F (-20 to 50°C)
0-95% RH, Non-condensing
Pollution Degree 2
Altitude to 6561 ft (2000 meters)
Listings UL, cUL, CE
(Note: Not all models are UL/CE complaint. See product
label for UL/CE mark.)
3511 Charter Park Drive, San Jose, CA 95136
Phone: 800-959-4014 or 408-871-7510
Fax: 408-871-7515 FAX
[email protected], www.nktechnologies.com
Know Your Power
Other NK Technologies Products Include:
DC Current Switches, Ground Fault Sensors
AC & DC Current Switches, Power Transducers
Current & Potential Transformers (CTs & PTs)
POLARITY:
BP - Bipolar
U - Unipolar
DT SERIES Solid Core
0-20 or 4-20 mA; 0-5 or 0-10 VDC Outputs
SENSOR TYPE:
DT - DC current sensor with analog output
291004109 Rev 4
For products intended for the EU market, the following is appli-
cable to the CE compliance of the product:
The 24 V DT series comply with EN 61010-1 CAT III 300 V max mea-
surement category. Power source overvoltage category I as defi ned per
EN 61010-1.
Warning! Risk of danger
Safe operation can only be guaranteed if the
transducer is used for the purpose for which it
was designed and within the limits of the techni-
cal specifi cations. When this symbol is used,
it means you must consult all documentation to
understand the nature of potential hazards and the
action required to avoid them.
Warning! Risk of electrical shock
When operating the transducer certain parts
may carry hazardous live voltage (e.g. Primary
conductor, power supply). The transducer should
not be put into operation if the installation is not
complete.
Place wire to be monitored through sensor aperture. Care
should be taken to ensure current fl ow is in accordance with
any directional arrows on sensor and as noted in the fi gure,
above right.
DT Series transducers work in the same environment as
motors, contactors, heaters, pull-boxes, and other electrical
enclosures. They can be mounted in any position or hung
directly on wires with a wire tie. For optimal performance,
ensure unit has been energized for a period of 20 minutes
prior to sensing operation.
Description
Installation
Wiring & Mounting Information
Range Select
DT Series transducers feature factory calibrated, fi eld
selectable ranges.
1. Determine the normal operating amperage of moni-
tored circuit.
1. Output Signal Too Low
A. The jumper may be set in a range that is too high for
current being monitored. Move jumper to the correct
range.
B. Power supply is inadequate. Check power supply.
Make sure it is of suffi cient voltage with all loads at
maximum. DT Series consumes 2.0 VA.
C. Output load too high. Check output load, be sure it
is no more than 500  for mA output, more than 10
Kfor VDC output.
2. Output Signal is always at maximum
A. The jumper may be set in a range that is too low for
current being monitored. Move jumper to the correct
range.
3. Sensor has no output
A. Polarity is not properly matched. Check and correct
wiring polarity.
B. Monitored load is not DC or is not on. Check that
the monitored load is DC and that it is actually on.
Trouble Shooting
DT Series transducers combine a Hall Eff ect sensor and
a signal conditioner into a single package. This provides
higher accuracy, lower wiring costs, easier installation
and saves valuable panel space. DT Series are available-
with 0-20 mA, 4-20 mA, 0-5 VDC or 0-10 VDC outputs.
2. Select the range that is equal to or slightly higher than
the normal operating amperage.
3. Place the range jumper in the appropriate position.
Unipolar versus Bipolar Output
0-20 mA & 4-20 mA:
The current loop is powered by the DT Transducer.
Maximum loop impedance is 500 .
0-5 VDC & 0-10 VDC:
Signal is powered by the DT Transducer. Minimum
output load (impedance) is 25 Kfor 5 VDC and 50 K
for 10 VDC.
Current Direction:
Ensure the direction of monitored current is the same as
the direction shown on the diagram. The unit will not
operate properly if the current is opposite the direction of
the arrow.
Note: Unipolar transducers produce an output signal
with current fl owing in one direction only. Bipolar trans-
ducers produce an output with current fl owing in both
directions through the sensor.
291004109 Rev 4

Other NK TECHNOLOGIES Transducer manuals

NK TECHNOLOGIES AT 2 Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES AT 2 Series User manual

NK TECHNOLOGIES VTR Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES VTR Series User manual

NK TECHNOLOGIES VTD-BD Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES VTD-BD Series User manual

NK TECHNOLOGIES VTD Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES VTD Series User manual

NK TECHNOLOGIES VTU Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES VTU Series User manual

NK TECHNOLOGIES AT SERIES User manual

NK TECHNOLOGIES

NK TECHNOLOGIES AT SERIES User manual

NK TECHNOLOGIES VTU Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES VTU Series User manual

NK TECHNOLOGIES DT Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES DT Series User manual

NK TECHNOLOGIES DTC 2-420-24U-FL User manual

NK TECHNOLOGIES

NK TECHNOLOGIES DTC 2-420-24U-FL User manual

NK TECHNOLOGIES APS Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES APS Series User manual

NK TECHNOLOGIES ATQ Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES ATQ Series User manual

NK TECHNOLOGIES APS Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES APS Series User manual

NK TECHNOLOGIES AT-TH Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES AT-TH Series User manual

Popular Transducer manuals by other brands

HBM Z4A Mounting instructions

HBM

HBM Z4A Mounting instructions

Comet T4311 instruction manual

Comet

Comet T4311 instruction manual

M-system L3CK instruction manual

M-system

M-system L3CK instruction manual

SIAP+MICROS t033 TDV User manual and maintenance

SIAP+MICROS

SIAP+MICROS t033 TDV User manual and maintenance

Simrad SUPPORT BEAM DRILLING TEMPLATE - SCHEMA REV... Template

Simrad

Simrad SUPPORT BEAM DRILLING TEMPLATE - SCHEMA REV... Template

Balluff Micropulse BTL5-E series user guide

Balluff

Balluff Micropulse BTL5-E series user guide

HBM U10M Mounting instructions

HBM

HBM U10M Mounting instructions

M-system W2PV instruction manual

M-system

M-system W2PV instruction manual

Johnson Controls DP150 Series installation guide

Johnson Controls

Johnson Controls DP150 Series installation guide

Woodward UMT 1 manual

Woodward

Woodward UMT 1 manual

Electro-Voice DH3 Technical specifications

Electro-Voice

Electro-Voice DH3 Technical specifications

Airmar Tilted Element B164 Owner's guide and installation instructions

Airmar

Airmar Tilted Element B164 Owner's guide and installation instructions

Atlas Copco MT TS Series Product instructions

Atlas Copco

Atlas Copco MT TS Series Product instructions

S+S Regeltechnik THERMASGARD MWTM Series Operating Instructions, Mounting & Installation

S+S Regeltechnik

S+S Regeltechnik THERMASGARD MWTM Series Operating Instructions, Mounting & Installation

Lumel P15 user manual

Lumel

Lumel P15 user manual

aci ACCESS series Installation & operation instructions

aci

aci ACCESS series Installation & operation instructions

Camille Bauer SINEAX U 554 operating instructions

Camille Bauer

Camille Bauer SINEAX U 554 operating instructions

Garmin GT15M-IH installation instructions

Garmin

Garmin GT15M-IH installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.