Novus N1100 User manual

NOVUS AUTOMATION 1/11
Controller
N1100
UNIVERSAL CONTROLLER
– INSTRUCTIONS MANUAL – V4.0x D
SAFETY ALERTS
The symbols below are used on the equipment and throughout this
document to draw the user’s attention to important operational and
safety information.
CAUTION:
Read complete instructions prior to
installation and operation of the
unit.
CAUTION OR WARNING:
Electrical shock hazard.
All safety related instructions that appear in the manual must be
observed to ensure personal safety and to prevent damage to either
the instrument or the system. If the instrument is used in a manner not
specified by the manufacturer, the protection provided by the
equipment may be impaired.
PRESENTATION
The N1100 is an extraordinarily versatile process controller. It holds
in one single instrument all the main features needed for the vast
majority of industrial processes. It accepts in a single model virtually
all the sensors and signals used in the industry and provides the
main output types required for the operation of diverse processes.
The configuration can be performed directly on the controller or through
the USB interface. The NConfig software (free) is the configuration
management tool. Connected to the USB of a Windows computer, the
controller is recognized as a serial communications port (COM) running
with a Modbus RTU protocol.
Through the USB interface, even if disconnected from the power
supply, the configuration performed in a piece of equipment can be can
be saved in a file and repeated in other pieces of equipment that
require the same configuration.
It is important that the users read carefully this manual before using
the controller. Verify if the release of this manual matches the
instrument version (the firmware version is shown when the controller
is energized).
MAIN CHARACTERISTICS
•Multi-sensor universal input (sensors and standard signals);
•Protection for open sensor in any condition;
•Relay, 4-20 mA and logic pulse control outputs all available in the
standard model;
•Self-tuning of PID parameters;
•Automatic / Manual function with “bumpless” transfer;
•Four modes of independents alarms, with functions of minimum,
maximum, differential (deviation), open sensor and event;
•Timer functions that can be associated to the alarms;
•Retransmission of PV or SP in 0-20 mA or 4-20 mA;
•Input for remote setpoint;
•Digital input with 5 functions;
•Programmable soft-start;
•7 setpoint profile programs with 7 segments each, with the ability
to be linked together for a total of 49 segments;
•Password for parameters protection;
•Universal power supply.
CONFIGURATION / FEATURES
Select the input type (in parameter “
tYPE
”) from Table 1 below
TYPE CODE CHARACTERISTICS / RANGE OF MEASUREMENT
J
Tc j
Range: -110 to950 ºC (-166to 1742 ºF)
K
Tc k
Range: -150 to 1370 ºC (-238to 2498 ºF)
T
Tc t
Range: -160 to 400 ºC (-256to 752 ºF)
N
Tc n
Range: -270 to 1300 ºC (-454to 2372 ºF)
R
Tc r
Range: -50to 1760 ºC (-58to 3200 ºF)
S
Tc s
Range: -50to 1760 ºC (-58to 3200 ºF)
B
Tc b
Range: 400to 1800 ºC (752to 3272 ºF)
E
Tc e
Range: -90to 730ºC (-130to1346 ºF)
Pt100
Pt
Range: -200to850ºC (-328to1562ºF)
0–50 mV
L.0.50
Linear Signals
Programmable indication from-1999 to 9999
4-20 mA
L.4.20
0-5 Vdc
L0.5
4-20 mA
sqrt
4-20 mA input with Square Root extraction.
Programmable indication from-1999 to 9999
4-20 mA
NON
LINEAR
ln j
Non Linear Analog Signals
Indication range depends on the selected sensor
Ln k
ln t
ln n
ln r
ln s
ln b
ln E
Ln.Pt
Table 1 – Input types
Note: All input types are factory calibrated.
OUTPUTS, ALARMS AND DIGITAL INPUTS CONFIGURATION
The controller input and output channels (I / O) can assume multiple
functions: control output, digital input, digital output, alarm output,
retransmission of PV and SP. These channels are identified as I / O
1, I / O 2, I / O 3, I / O 4 and I / O 5.
The basic controller model comes loaded with the following features:
I / O 1- output to Relay SPST-NA;
I / O 2- output to Relay SPST-NA;
I / O 5- current output, digital output, digital input;
Optionally, other features can be added, as shown under the item
“Identification” in this manual:
- 3R: I / O3 with output to SPDT relay;
- DIO: I / O3 and I / O4 as digital input and output channels;
- 485: Serial Communication

N1100 Controller
NOVUS AUTOMATION 2/11
The function code of each I/O can be selected among the options on
Table 2.
I/O TYPE
I/O FUNCTION
CODE
-
No function
OFF
Output
Alarm 1 Output
A1
Output
Alarm 2 Output
A2
Output
Alarm 3 Output
A3
Output
Alarm 4 Output
A4
Output
Control Output (Relay or Digital Pulse)
CTRL
Digital Input
Automatic/Man mode change
mAN
Digital Input
Run/Stop mode change
RVN
Digital Input
Selected Remote SP
RSP
Digital Input
Freezes program execution
KPRG
Digital Input
Program 1 selection
PR 1
Analog Output
0 to 20 mA analog control output
(.0.20
Analog Output
4 to 20 mA analog control output
(.4.20
Analog Output
0 to 20 mA PV retransmission
P.0.20
Analog Output
4 to 20 mA PV retransmission
P.4.20
Analog Output
0 to 20 mA SP retransmission
S.0.20
Analog Output
4 to 20 mA SP retransmission
S.4.20
Table 2 - I/O channel functions
During the configuration of channels, only the valid options for each
channel will be shown on the display. The description for the
functions follows:
•
off
- No function
The I/O channel programmed with code
off
will not be used by the
controller.
Note: Although without function, this channel is available through the
serial communication (command 5 MODBUS).
•
A1
,
a2
,
a3
,
a4
– Alarm output
The selected channel can be used as output to alarms. Available for
all the I/O channels.
•
(trL
- PWM control output
Defines the channel to be used as control output (relay or digital
pulse). Available for all the channels. The digital pulse is available
on (when available) and I/O5.
•
mAn
–Digital input with Manual/Auto function
Defines the channel as Digital Input with the function of switching the
control mode between Automatic and Manual. Available for I/O3,
I/O4 (when available) and I/O5.
Closed Contact =Manual control / NO
Opened Contact = Automatic control / YES
•
rvn
- Digital input with RUN function
Defines channel as Digital Input with the function of enabling / disabling
the control and alarm outputs (“
RvN
”: YES / no). Available for I/O3,
I/O4 (when available) and I/O5.
Closed Contact = Outputs enables / NO
Opened Contact = Outputs disables / YES
•
rsp
– Digital input with remote SP function
Defines channel as Digital Input with the function of selecting the
remote SP. Available for I/O3, I/O4 (when available) and I/O5.
Closed Contact=Remote SP
Opened Contact = Main SP
•
kprg
– Digital input with Hold Program function
Defines channel as Digital Input with the function of commanding the
execution of the selected setpoint profile program. Available for I/O3,
I/O4 (when available) and I/O5.
Closed Contact = Enables execution of the program
Opened Contact = Interrupts execution of the program
Note: Even when the execution of the program is interrupted, the
control output remains active and controlling the process at the point
(Setpoint) of interruption. The program will resume its normal
execution starting from this same point when the digital input is
closed.
•
Pr 1
– Digital input with function to Execute Program 1
Defines the channel as Digital Input with the function of commanding
the execution of the setpoing profile program 1. Available for I/O3,
I/O4 (when available) and I/O5.
Useful function for switching between the main setpoint and a
secondary one defined by the program 1.
Closed = selects program 1
Opened = useds main Setpoin
•
(.0.20
–0-20 mA Control Output
Available for I/O 5 only, defines the channel as a 0-20 mA control output.
•
(.4.20 -
4-20 mA Control Output
Available for I/O 5 only, defines the channel as a 4-20 mA control output.
•
P.0.20
– 0-20 mA PV retransmission
Available for I/O 5 only, configures the channel to retransmit the PV
measurement in 0-20 mA.
•
P.4.20
- 4-20 mA PV retransmission
Available for I/O 5 only, configures the channel to retransmit the PV
measurement in 4-20 mA.
•
s.0.20
–0-20 mA SP (Setpoint) retransmission
Available for I/O 5 only, configures the channel to retransmit the
values of SP in 0-20 mA.
•
s.4.20
–4-20 mA SP (Setpoint) retransmission
Available for I/O 5 only, configures the channel to retransmit the
values of SP in 0-20 mA.
ALARMS FUNCTIONS
The controller has 4 independent alarms. They can be programmed
to operate with eight different functions, represented in Table 3.
•
off
– Alarms turned
off
.
•
ierr
– Sensor break alarm
It is activated whenever the input sensor is broken or disconnected.
•
rs
– Ramp & soak program event alarm
This alarm is activated by the Ramp & Soak program (refer to the
PROGRAMS OF RAMP AND SOAK section on how to set the event
alarm).
•
lo
– Alarm of Absolute Minimum Value
It is activated when the measured value is below the value defined in
the alarm Setpoint.
•
ki
– Alarm of Absolute Maximum Value
It is activated when the measured value is above the value defined in
the alarm Setpoint.
•
dif
– Alarm of Differential Value
In this function, the parameters “
SPA1
”, “
SPA2
”, ”
SPA3
” and “
SPA4
”
represent the PV deviation as compared to the main SP.
Using the Alarm 1 as example: for Positive SPA1 values, the
differential alarm will be triggered when the PV value is out of the
range defined in:
(SP –SPA1) to (SP + SPA1)
For a negative SPA1 value, the differential alarm will be triggered
when the PV value is within the range defined above
•
difl
– Alarm of Minimum Differential Value
It is activated when the PV value is below the value defined in:
(SP –SPA1)
Using the Alarm 1 as example.
•
difk
– Alarm of Maximum Differential Value
It is activated when the PV value is above the value defined in:
(SP + SPA1)
Using the Alarm 1 as example.

N1100 Controller
NOVUS AUTOMATION 3/11
PROMPT
TYPE
ACTION
Off
Disabled
Output is not used as alarm.
Ierr
Sensor Break
(input Error)
Activated when the input signal of PV is
interrupted, out of the range limits or Pt100
in short-circuit.
Rs
Event
(ramp and Soak)
Can be activated at a specific segment of
program.
Lo
Minimum value
(Low)
SPAn
PV
Ki
Maximum value
(High)
SPAn
PV
Difl
Minimum
Differential
(differential
Low)
Positive SPAn Negative SPAn
SV
PV
SV -SPAn
SV
PV
SV -SPAn
Difk
Maximum
Differential
(differential
High)
SV
PV
SV + SPAn
SV
PV
SV + SPAn
Positive SPAn
Ngative SPAn
Dif
Differential
(differential)
SV
PV
SV + SPAn
SV -SPAn
SV
PV
SV -SPAn
SV + SPAn
Positive SPAn
Nagative SPAn
Table 3 – Alarm functions
Where SPAn refers to Setpoints of Alarm “
SPA1
”, “
SPA2
”, “
SPA3
”
and “
SPA4
”.
ALARM TIMER MODES
The controller alarms can be configured to perform 4 timer modes:
•Continuous (normal mode).
•One pulse with defined duration;
•Delayed activation;
•Repetitive pulses;
The illustrations in Table 4 show the behavior of the alarm output for
various combinations of times T1 and T2. The timer functions can be
configured in parameters
A1t1
,
A1t2
,
A2t1
and
A2t2
.
OPERATION
T 1
T 2
ACTION
Normal
operation 0 0
Alarm Event
Alarm
Output
Activation for
a defined time
1 s to
6500 s 0
Alarm Event
Alarm
Output
T1
Activation with
delay 0 1 s to
6500 s
Alarm Event
Alarm
Output
T2
Intermittent
activation
1 s to
6500 s
1 s to
6500 s
Alarm Event
Alarm
Output
T1
T2
T1
Table 4 - Temporization Functions for the Alarms
The LEDs associated to the alarms will light when the alarm
condition is recognized, not following the actual state of the output,
which may be temporarily OFF because of the temporization.
ALARM INITIAL BLOCKING
The initial blocking option inhibits the alarm from being recognized
if an alarm condition is present when the controller is first energized.
The alarm will be enabled only after the occurrence of a non-alarm
condition followed by a new occurrence for the alarm.
The initial blocking is useful, for instance, when one of the alarms is
configured as a minimum value alarm, causing the activation of the
alarm soon upon the process start-up, an occurrence that may be
undesirable.
The initial blocking is disabled for the sensor break alarm function.
SQUARE ROOT EXTRACTION
When the input type is configured as
SQRT
the controller assumes
the input as a 4-20 mA while extracting the square root of the applied
input signal.
ANALOG RETRANSMISSION OF PV AND SP
The analog output, when not used for control purposes, is available
for retransmitting the PV and SP values in 0-20 or 4-20 mA. This
analog output is electrically isolated from other inputs and outputs.
The analog output signal is scalable, with the output range defined by
the values programmed in the parameters “
SPLL
” and “
SPkL
”.
It is possible to obtain a voltage output by installing a resistor shunt
(550 Ω max.) to the current output terminals (terminals 7 and 8). The
actual resistor value depends on the desired output voltage span.
There is no electrical isolation between serial communication
(RS485) and channel I/O5.
SOFT-START
The soft-start feature avoids abrupt variations in the power delivered
to the load regardless of the system power demand.
This is accomplished by defining a limiting ramp for the control output.
The output is allowed to reach maximum value (100 %) only after the
time programmed in the soft-start parameter has elapsed.
The Soft-start function is generally used in processes that require slow
start-up, where the instantaneous application of 100 % of the available
power to the load may cause damages to parts of the system.
In order to disable this function, the soft-start parameter must be
configured with 0 (zero).
REMOTE SETPOINT
The controller can have its Setpoint value defined by an analog,
remotely generated signal. This feature is enabled through the
channels I/O3, I/O4 or I/O5 when configured as digital inputs and
configured with the function
rsp
(Remote SP selection) or through
the parameter
E.rsp
. The remote Setpoint input accepts the signals
0-20 mA, 4-20 mA, 0-5 V and 0-10 V.
For the signals of 0-20 and 4-20 mA, a shunt resistor of 100
Ω
is
required between terminals, as shown in Figure 4c.
CONTROL MODE
The controller can operate in two different manners: Automatic mode
or Manual mode.
The parameter “
avto
” defines the control mode to be adopted.
In Automatic mode the controller defines the amount of power to be
applied on the process.
In Manual mode the user himself defines this amount of power. The
user can then adjust the MV percentage while displaying PV/MV.
PID AUTOMATIC MODE
For the Automatic mode, there are two different strategies of control:
PID automatic control and ON/OFF automatic control.
PID control has its action based on a control algorithm that takes into
account the deviation of PV with respect to SP, the rate of change of
PV and the steady state error. These parameters are particular to a
system and can be obtained automatically by the controller’s Auto
Tune feature (
Atvn
parameter).
On the other hand, the ON/OFF control (obtained when
Pb
=0)
operates with 0 % or 100 % of power, when PV deviates from SP.
The determination of parameters
Pb
,
Ir
and
Dt
is described in the
item DETERMINATION OF PID PARAMETERS of this manual.

N1100 Controller
NOVUS AUTOMATION 4/11
USB INTERFACE
The USB interface is used for CONFIGURING or MONITORING the
controller. The NConfig software must be used for the configuration.
It makes it possible to create, view, save and open configurations
from the equipment or files in your computer. The tool for saving and
opening configurations in files makes it possible to transfer
configurations between pieces of equipment and to make backup
copies. For specific models, the NConfig software also makes it
possible to update the firmware (internal software) of the controller
through the USB.
For MONITORING purposes you can use any supervisory software
(SCADA) or laboratory software that supports the MODBUS RTU
communication on a serial communications port. When connected to
the USB of a computer, the controller is recognized as a conventional
serial port (COM x). Use the NConfig software or consult the
DEVICE MANAGER in the Windows CONTROL PANEL to identify
the COM port that was assigned to the controller. Consult the
mapping of the MODBUS memory in the controller’s communications
manual and the documentation of your supervisory software to
conduct the MONITORING process.
Follow the procedure below to use the USB communication of the
equipment:
1. Download the NConfig software from our website and install it on
your computer. The USB drivers necessary for operating the
communication will be installed together with the software.
2. Connect the USB cable between the equipment and the
computer. The controller does not have to be connected to a
power supply. The USB will provide enough power to operate the
communication (other equipment functions cannot operate).
3. Open the NConfig software, configure the communication and
start recognition of the device.
The USB interface IS NOT SEPARATE from the
signal input (PV) or the controller’s digital inputs and
outputs. It is intended for temporary use during
CONFIGURATION and MONITORING periods. For
the safety of people and equipment, it must only be
used when the piece of equipment is completely
disconnected from the input/output signals. Using the
USB in any other type of connection is possible but
requires a careful analysis by the person responsible
for installing it. When MONITORING for long periods
of time and with connected inputs and outputs, we
recommend using the RS485 interface, which is
available or optional in most of our products.
INSTALLATION / CONNECTIONS
The controller must be fastened on a panel, following the sequence
of steps described below:
•Prepare a panel cut-out of 45.5 x 45.5 mm;
•Remove the mounting clamps from the controller;
•Insert the controller into the panel cut-out;
•Slide the mounting clamp from the rear to a firm grip at the panel.
RECOMMENDATIONS FOR THE INSTALLATION
•To minimize the pick-up of electrical noise, the low voltage DC
connections and the sensor input wiring should be routed away
from high-current power conductors. If this is impractical, use
shielded cables. In general, keep cable lengths to a minimum.
•All electronic instruments must be powered by a clean mains
supply, proper for instrumentation.
•It is strongly recommended to apply RC'S FILTERS (noise
suppressor) to contactor coils, solenoids, etc.
•In any application it is essential to consider what can happen when
any part of the system fails. The controller features by themselves
can not assure total protection.
ELECTRICAL CONNECTIONS
The controller complete set of features is drawn in Figure 1:
Figure 1 - Connections of the back panel
Power Supply Connections
Observe the power
requirement for the
unit. of required power
supply.
Figure 2
– Power supply connections
Input Connections
•Thermocouple (T/C) and 0-50 mV
The Figure 3a indicates the wiring for the thermocouple and 0-50 mV
signals. If the thermocouple wires need to be extended, use
appropriate compensation cables.
•RTD (Pt100):
Figure 3b shows the Pt100 wiring, for 3 conductors. For proper cable
length compensation, use conductors of same gauge and length).
For 4-wires Pt100, leave one conductor disconnected at the
controller. For 2-wire Pt100, short-circuit terminals 11 and 12.
T/C, 0-50mV
Pt100
Figure 3a - Connection of T/C,
0-50 mV
Figure 3b - Connection of Pt100 a
3-wire
•4-20 mA:
The connections for current signals 4-20 mA must be carried-out
according to Figure 4a.
4-20mA
Figure 4a - Current connection
4-20 mA
Figure 4b – Connection for 5 V
•5 V
Refer to Figure 4b for connecting voltage signals.

N1100 Controller
NOVUS AUTOMATION 5/11
Remote Setpoint
Feature available in the controller's terminals 9 and 10. When the
Remote SP input signal is 0-20 mA or 4-20 mA, an external
100
Ω
shunt resistor of must be connected to terminals 9 and 10 as
indicated in Figure 4c.
Figure 4c – Connection for remote SP
Digital Input Connections
Figures 5a and 5b show switches (Dry Contact) driving I/O3(or
I/O4) and I/O5.
Figure 5a – I/O3 or I/O4as Digital
Input
Figure 5b – I/O5 as Digital Input
Connection of Outputs
The I/O channels, when configured as outputs, must have their load
limit capacities observed, according to the product specifications.
Figure 6a – I/O3 or I/O4 with output
pulse for SSR.
Figure 6b – I/O5 with output pulse
for SSR.
OPERATION
The controller's front panel, with its parts, can be seen in the Figure 7:
Figure 7 - Identification of the parts referring to the front panel
Display of PV/Programming: Displays the current value of PV
(Process Variable). When in configuration mode, it shows the
parameters names.
Display of SP/Parameters: Displays the value of SP (Setpoint).
When in configuration mode, it shows the parameters values.
COM indicator: Flashes to indicate communication activity in the
RS485 interface.
TUNE indicator: Stays on while the controller is in tuning process.
MAN indicator: Signals that the controller is in the manual control
mode.
RUN indicator: Indicates that the controller is active, with the control
output and alarms enabled.
OUT indicator: For relay or pulse control output; it reflects the actual
state of the output. If an analog output is assigned for control (0-20
mA or 4-20 mA), the OUT indicator lights continuously.
A1, A2, A3 and A4 indicators: signalize the occurrence of alarm
situation.
P
P Key used to walk through the menu parameters.
Back Key: used to retrocede parameters.
Increment key and
-Decrement key: allow altering the
values of the parameters.
When the controller is powered on, its firmware version is presented
for 3 seconds, after which the controller starts normal operation. The
values of PV and SP are displayed and the outputs are enabled.
In order to operate appropriately, the controller needs a configuration
that is the definition of each one of the several parameters presented
by the controller. The user must be aware of the importance of each
parameter and for each one determine a valid condition or a valid
value.
Note: Since many parameters depend on the input type chosen, it
is recommended that the parameter
TYPE
be the first one to be
configured.
The parameters are grouped in levels according to their functionality
and operation easiness. The 7 levels of parameters are:
LEVEL ACCESS
1- Operation
Free access
2- Tuning
Reserved access
3- Programs
4- Alarm
5- Scale
6- I/Os
7- Calibration
Tabele5– Cycles of Parameters
The parameters in the operation level (1st level) are easily accessed
through the
P
key. The access deeper levels use the combination
of Keys:
(BACK) and
P
(PROG) pressed simultaneously
Press to advance or to retrocede parameters within a level.
At the end of each level, the controller returns to the operation level.
Keep pressing the
P
key to move fast forward in the level.
Alternatively, the controller returns to the operation level after
pressing the key for 3 seconds.
All configuration parameters are stored in protected memory. The
values are saved when the keys or are pressed after changing
a parameter value. The value of SP is saved upon pressing the
key or every 25 seconds.
P
P
P

N1100 Controller
NOVUS AUTOMATION 6/11
DESCRIPTION OF THE PARAMETERS
PV / SP indication - The upper display shows the
current value of PV. The lower display shows the
control SP value.
avto
Control Mode:
Yes
- Means automatic control mode.
no
- Means manual control mode.
Bumpless transfer between automatic and manual.
PV / MV- The upper display shows PV value and the
lower display shows the percentage
of the
manipulated variable MV
applied to the control
output.
When in manual control, the MV
value can be
manually changed by the and keys.
When in
auto mode the MV value can only be viewed.
To distinguish the MV display from the SP display,
the MV is shown flashing intermittently.
Pr n
Enable
Program
Execution of Program - Selects the ramp and
soak profile program to be executed.
0- does not execute program
1 to 7 -number of the program to be
executed
With enabled outputs (
RvN
=
YES
), the program
starts right after the program is selected.
rvn
Enables control outputs and alarms.
YES
- Outputs enables.
NO
- Outputs not enabled.
CYCLE OF TUNING
Atvn
Auto-tune
Enables the auto tuning feature for the PID
parameters.
YES
– Auto-tune enable
NO
– Do not execute auto tune.
See the DETERMINATION OF PID PARAMETERS
section for more details.
pb
Proportional
Band
Proportional Band - Value of the term Pof the
control mode PID, in percentage of the maximum
span of the input type. Adjust of between 0 and
500.0 %.
Select zero for ON/OFF control.
ir
Integral Rate
Integral Rate - Value of the term Iof the PID
algorithm, in repetitions per minute (Reset).
Adjustable between 0 and 24.00.
Displayed only if proportional band≠0.
dt
Derivative Time
Derivative Time - Value of the term Dof the control
mode PID, in seconds. Adjustable between 0
and250seconds.
Displayed only if proportional band≠0.
(t
Cycle Time
Pulse Width Modulation (PWM) period in seconds.
Adjustable between 0.5 and 100.0 seconds.
Displayed only if proportional band≠0.
kyst
Hysteresis
Control hysteresis - This parameter is only shown
for ON / OFF control. Adjustable between 0and
the measurement input type span.
Displayed only if proportional band = 0.
ACt
Action
Control logic:
re
Control with reverse Action. Appropriate for
heating. Turns control output on when PV is
below SP.
dir
Control with direct Action. Appropriate for
cooling
. Turns control output on when PV is
above SP.
bias
Bias function - Allows adding a percentage value
between -100 % and +100 %. to the MV control
output.
The value 0 (zero) disables the function.
ovll
Output Low
Limit
Lower limit for the control output - Minimum
percentage value assumed by the control output
when in automatic mode and in PID.
Typically configured with 0.0 %.
ovkl
Output High
Limit
Upper limit for the control output - Maximum
percentage for the control output when in
automatic mode and in PID.
Typically configured with 100.0 %.
sfst
Softstart
SoftStart Function –Time in seconds during which
the controller limits the MV value progressively
from 0 to 100 %. It is enabled at power up or when
the control output is activated. If in doubt set zero
(zero value disables the Soft start function).
Sp.a1
Sp.a2
Sp.a3
Sp.a4
Alarm SP: Value that defines the point of activation
for the programmed alarms with the functions “
Lo
”
or “
ki
”.
For the alarms configured with Differential type
functions, this parameter defines deviation (band).
Not used for the other alarm functions.
CYCLE OF PROGRAMS
t.bas
Program time
base
Program time base - Defines the time base that will
be used by all Ramp & Soak programs.
Se(
- Time basis in seconds
min
- Time basis in minutes
Pr n
Program
number
Selects the ramp and soak profile program to be
edited/viewed. The sequence of parameters that
follows refer to this selected program. Total of 20
programs possible. There are 7 possible programs.
Ptol
Program
Tolerance
Maximum admitted deviation of PV with respect to
SP.If exceeded, the program execution is suspended
(the internal timer freezes) until the deviation be
returns back within the defined tolerance.
The value 0 (zero) disables the function.
Psp0
Psp7
Program SP
Program SP’s, 0 to7: Group of 8 values of SP that
define the Ramp and Soak profile segments.
Pt1
Pt7
Program Time
Segments durations, 1 to7:
Defines the time of
duration, in second or minutes, 7 of the segments of
the program being edited.
Pe1
Pe7
Program event
Alarms of Event, 1 to 7:
Parameters that define
which alarms are to be activated during the
execution of a certain program segment. The alarms
chosen must have its function configured as “
rS
”.
Lp
Link Program
Link Program: number of the next profile program to
be linked following the current program. Profiles can
be linked together to produce larger programs of up
to 49 segments.
0- do not link to any other program.
1 a7 – number of the program to be linked to.
PV Indication
(Red Screen)
SP Indication
(Green Screen)
PV Indication
(Red Screen)
MV Indication
(Green Screen)

N1100 Controller
NOVUS AUTOMATION 7/11
CYCLE OF ALARMS
Fva1
Fva2
Fva3
Fva4
Function Alarm
Functions of Alarms. Defines the functions for the
alarms among the options of the Table 3.
oFF, iErr, rS, Lo, xi, DiFL, DiFx, DiF
bla1
bla2
bla3
bla4
Blocking Alarm
Block of Alarms. This function blocks the alarms1
to 4.
YES
- enables initial blocking
NO
- inhibits initial blocking
xya1
xya2
xya3
xya4
Hysteresis of
Alarm
Alarm Hysteresis. Defines the difference between
the value of PV at which the alarm is triggered and
the value at which it is turned off (in engineering
units)..
A1t1
A2t1
Alarm Time t1
Defines the temporization time t1, for the alarms.
In seconds.
The value 0 (zero) disables the function.
A1t2
A2t2
Alarm Time t2
Defines the temporization time t2 for the alarms
time functions. In seconds.
The value 0 (zero) disables the function.
CYCLE OF SCALE
Type
Type
INPUT TYPE: Selects the input signal type to be
connected to the process variable input. Refer to
Table 1 for the available options.
This must be the first parameter to be
configured.
Dppo
Decimal Point
Defines the decimal point position.
vnI t
Unit
UNIT: Defines the indication unit in Celsius “°
(
“ or
Fahrenheit “°
f
“
This parameter is presented whenever a
temperature sensor is configured as input.
0ffs
Offset
SENSOR OFFSET: Offset value to be added to
the PV reading to compensate sensor error.
Default value: zero.
Spll
Setpoint Low
Limit
Defines the SP lower limit of.
For the linear analog input types available (0-20 mA,
4-20 mA, 0-50 mV and 0-5 V), defines the minimum
PV indication range, besides limiting the SP
adjustment.
Defines lower limit for range retransmission PV and
SP.
Spxl
Setpoint High
Limit
Defines the upper limit for adjustment of SP.
For the linear analog input types available (0-20 mA,
4-20 mA, 0-50 mV and 0-5 V), defines the maximum
PV indication range, besides limiting the SP
adjustment.
Defines upper limit for range retransmission PV and
SP.
e.rsp
Enable Remote
SP
Enables remote SP.
YES
Enables the Function
no
Does not enable the Function
This parameter is not displayed when the remote
SP selection is defined by a Digital Input.
rsp
Remote SP
Defines the signal type for the remote SP.
0-20
current of 0-20 mA
4-20
current of 4-20 mA
0-5
voltage of 0-5 V
0-10
voltage of 0-10 V
Parameter displayed when remote SP is enabled.
rsll
Remote SP
Low Limit
REMOTE SETPOINT LOW LIMIT: used in
conjunction with the rSxL, scales the remote SP
input defining the initial value in the remote SP
indication range.
Parameter displayed when remote SP is enabled.
rskl
Remote SP
High Limit
REMOTE SETPOINT HIGH LIMIT: defines the full
scale indication of the Remote Setpoint.
Parameter displayed when remote SP is enabled.
bavd
Baud Rate
Serial Communication Baud Rate selection, in
kbps:
1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 e 115.2
prty
Parity
Parity of the serial communication.
none
Without parity
Ewem
Even parity
0dd
Odd parity
Addr
Address
SLAVE ADDRESS SELECTION: Identifies the
controller in the network. The possible address
numbers are from 1 to 247.
CYCLE DE I/OS
Io 1
Function of the channel I/O 1: Selection of the
function used in the channel I/O 1, according to the
Table 2.
Io 2
Function of the channel I/O 2: Selection of the
function used in the channel I/O 2, according to the
Table 2.
Io 3
Function of the channel I/O 3: Selection of the
function used in the channel I/O 3, according to the
Table 2.
Io 4
Function of the channel I/O 4: Selection of the
function used in the channel I/O 4, according to the
Table 2.
Io 5
Function of the channel I/O 5: Selection of the
function used in the channel I/O 5, according to the
Table 2.
CALIBRATION CYCLE
All of the input and output types are calibrated in the factory. If a
recalibration is required, this should be carried out by a
experienced personnel. If this cycle is accidentally accessed, pass
through all the parameters (without pressing the or keys)
until the PV/SV screen is displayed
pass
Password
Input of the Access Password.
This parameter is presented before the protected
cycles. See item Protection of Configuration.
(alib
Calibration?
Allows instrument calibration.
YES
- Perform calibration
NO - Do not perform calibration
inL(
Input Low
Calibration
Enter the value corresponding to the low scale
signal applied to the analog input.
See section MAINTENANCE / Input Calibration.
ink(
Input High
Calibration
Enter the value corresponding to the full scale
signal applied to the analog input.
See section MAINTENANCE / Input Calibration.

N1100 Controller
NOVUS AUTOMATION 8/11
rsL(
Remote SP Low
Calibration
See section: MAINTENANCE / Input Calibration.
Enter the value corresponding to the low scale
signal applied to the remote SP input.
rsk(
Remote SP
High Calibration
See section: MAINTENANCE / Input Calibration.
Enter the value corresponding to the full scale
signal applied to the remote SP input.
0vL(
Output Low
Calibration
See section MAINTENANCE / Analog output
Calibration.
Enter the analog value as measured at the analog
output.
0vk(
Output High
Calibration
See section MAINTENANCE / Analog output
Calibration.
Enter the analog value as measured at the analog
output.
rstr
Restore
Restores the factory calibration for all input, analog
output and remote SP, disregarding modifications
carried out by the user.
(j
Cold Junction
Adjusts the of cold junction temperature value.
ktyp
Hardware Type
Parameter that informs the controller about the
hardware optionals installed. It should not be altered
by the user, except when an accessory is introduced
or removed.
0 – Basic model, without optional I/Os, with or
without RS485.
1– 3R (485)
2 – DIO (3R)
Pas.(
Password
Change
Allows defining a new access password, always
different from zero.
Prot
Protection
Sets up the Level of Protection. See Table 7.
OPERATION
CYCLE TUNING CYCLE PROGRAMS CYCLE ALARM CYCLE SCALE CYCLE I/OS CYCLE CALIBRATION
CYCLE
PV / SP
atvn
Tbas
fva1
-
fva4
type
io1
pass
Avto
pb
pr n
bla1 - bla4
dppo
Io2
Inl(
PV / MV
ir
Ptol
kya1
-
kya4
vnit
Io3
Ink(
Pr n
dt
psp0 –psp7
a1t1
Offs
Io4
Rsl(
Rvn
(t
pt1 – pt7
a1t2
Spll
Io5
Rsk(
Kyst
Pe1
–
pe7
a2t1
Spkl
0vl(
a(t
Lp
a2t2
e.rsp
0vk(
bias
Rsp
rstr
ovll
Rsll
(j
ovkl
Rskl
ktyp
sfst
Bavd
Pas.(
Spa1 - spa4
Prty
prot
addr
Table 6 – All the controller parameter
PROTECTION OF CONFIGURATION
The controller provides means for protecting the parameters
configurations, not allowing modifications to the parameters values,
avoiding tampering or improper manipulation.
The parameter Protection (
PROt
), in the Calibration level,
determines the protection strategy, limiting the access to particular
levels, as shown by the table below.
Protection
Level Protected Cycles
1
Only the Calibration level is protected.
2
I/Os and Calibration levels.
3
Tuning, I/Os and Calibration levels.
4
Alarm, Tuning, I/Os and Calibration levels.
5
Programs, Alarm, Tuning, I/Os and Calibration levels.
6
Tuning, Programs, Alarm, Input, I/Os and Calibration
levels.
7
Operation (except SP), Tuning, Programs, Alarm,
Scale, I/Os and Calibration levels.
8
Operation (including SP), Tuning, Programs, Alarm,
Scale, I/Os and Calibration levels.
Table7- Levels of Protection for the Configuration
Access Password
The protected levels, when accessed, request the user to provide the
Access Password for granting permission to change the
configuration of the parameters on these cycles.
The prompt PASS precedes the parameters on the protected levels.
If no password is entered, the parameters of the protected cycles can
only be visualized.
The Access Code is defined by the user in the parameter Password
Change (
PAS.(
), present in the Calibration level
The factory default for the password code is 1111.
Protection of the access code
The protection system built into the controller blocks for 10 minutes
the access to protected parameters after 5 consecutive frustrated
attempts of guessing the correct password.
Master Password
The Master Password is intended for allowing the user to define a
new password in the event of it being forgotten. The Master
Password doesn’t grant access to all parameters, only to the
Password Change parameter (
PAS(
). After defining the new
password, the protected parameters may be accessed (and
modified) using this new password.

N1100 Controller
NOVUS AUTOMATION 9/11
The master password is made up by the last three digits of the serial
number of the controller added to the number 9000.
As an example, for the equipment with serial number 07154321, the
master password is 9 3 2 1.
PROGRAMS OF RAMP AND SOAK
This feature allows the creation of Ramp and Soak Setpoint Profiles
(Programs). Up to 7 different profiles with 7 segments each can be
programmed. Longer profiles of up to 49 segments can be created by
linking 2 or more profiles together.
The figure below displays a profile model:
Figure 8 - Example of a Ramp and Soak program
Once a profile is defined and selected for execution, the controller
starts to generate the SP profile automatically in accordance with the
elaborated program.
To execute a profile with fewer segments just program 0 (zero) for
the time intervals that follow the last segment to be executed.
SV
Time
T1
T2
T3
SP0
SP1
SP2
SP3
T4=0
Figure 9 - Program example with few segments
The program tolerance “
ptol
” defines the maximum deviation
between PV and SP for the execution of the profile. If this deviation is
exceeded, the program will be halted until the deviation falls to within
the tolerance band.
Programming 0 (zero) in the “
Ptol
” parameter disables the program
tolerance and the profile execution will continue regardless of the PV
value (time priority as opposed to SP priority).
LINK OF PROGRAMS
It is possible to create a more complex program (up to 49 segments),
joining two or more programs. This way, at the end of a program
execution the controller immediately starts to run the next one, as
indicated in the parameter “
LP
".
To force the controller to run a given program or many programs
continuously, it is only necessary to link a program to itself or the last
program to the first.
SV
time
T1
T2
T3
T4
T5
T1
T2
T3
T4
SP0
SP1
SP2
SP3
SP4
SP5 / SP0
SP1
SP2
SP3
SP4
Program 1
Program 2
Figure 10 – Example of interlinked programs
EVENT
The Event Alarm function associates the alarms to specific segments
of a program. The information of which alarms are to be activated or
deactivated is given in parameters “
PE1
“ to “
PE7
. Press the and
keys until the desired alarm numbers are displayed.
The Event Alarm requires that the Alarm function be configured as
“
rS
“.
Notes:
1. If
PtoL
is different than zero, the controller will wait for the PV to
reach the first program set point SP0 in order to start the
program execution. Otherwise, it will start promptly.
2. Should any power failure occur, the controller resumes the
program execution at the beginning of the segment where it was
interrupted.
DETERMINATION OF PID PARAMETERS
During the automatic tuning the process is controlled in ON / OFF
mode in the programmed SP. Depending on the process behavior,
oscillations may occur above or below the Setpoint. The automatic
tuning may take many minutes to the concluded, particularly in slow
processes.
When the parameter ATUN is altered to YES, the automatic tuning
is immediately initiated by the controller (provided RUN=YES,
otherwise it will wait until this condition becomes true).
Some recommendations for the automatic tuning process are:
•
avto
= YES: make sure the controller is set for automatic control
mode.
•Disable Ramp & Soak programs configuring
Pr n
= 0. (the
automatic tuning algorithm expects a stable Setpoint value)
•Select a Setpoint that is close or equal to the desired process
Setpoint.
•Enable the automatic tuning (
atvn
= YES).
•Enable outputs if not yet enabled (
rvn
= YES).
The “TUNE” indicator on the display stays lit until the completion of
the automatic tuning process.
For control output types relay or pulse, the automatic tuning
calculates the longest suitable period (cycle time (t) for the PWM
output. The cycle time period may be reduced if the process
experiences some oscillation. When driving a SSR, it’s
recommended to set (t = 1 s.
If the automatic tuning does not result in a satisfactory control, refer
to Table 7 for guidelines on how to correct the behavior of the
process.
PARAMETER
VERIFIED PROBLEM
SOLUTION
Proportional Band Slow answer Decrease
Great oscillation
Increase
Rate of Integration
Slow answer
Increase
Great oscillation Decrease
Derivative Time
Slow answer or instability
Decrease
Great oscillation Increase
Table 7 - Guidance for manual adjustment of the PID parameters
MAINTENANCE
PROBLEMS WITH THE CONTROLLER
Connection errors and inadequate programming are the most
common errors found during the controller operation. A final revision
may avoid loss of time and damages.
The controller displays some messages to help the user identify
problems.
MENSSAGE DESCRIPTION OF THE PROBLEM
----
Open input. No sensor or signal.
Err1
Err6
Connection and/or configuration errors.
Check the wiring and the configuration.
Other error messages may indicate hardware problems requiring
maintenance service. When contacting the manufacturer, inform the
instrument serial number, obtained by pressing the key
for more
than 3 seconds.

N1100 Controller
NOVUS AUTOMATION 10/11
CALIBRATION OF THE INPUT
All inputs are factory calibrated and recalibration should only be done
by qualified personnel. If you are not familiar with these procedures
do not attempt to calibrate this instrument.
The calibration steps are:
a) Configure the type of input to be calibrated.
b) Configure the lower and upper limits of indication for the
maximum span of the selected input type.
c) At the input terminals inject a signal corresponding to a known
indication value a little above the lower display limit.
d) Access the parameter “
inLC
”. With the keys
and
, adjust
the display reading such as to match the applied signal. Then
press the
P
key.
e) Inject a signal that corresponds to a value a little lower than the
upper limit of indication.
f) Access the parameter “
inkC
”. With the keys
and
, adjust
the display reading such as to match the applied signal. Then
press the
P
key.
Note: When checking the controller calibration with a Pt100
simulator, pay attention to the simulator minimum excitation current
requirement, which may not be compatible with the 0.170 mA
excitation current provided by the controller.
REMOTE SETPOINT CALIBRATION
All inputs are factory calibrated and recalibration should only be done
by qualified personnel. If you are unfamiliar with these procedures do
not attempt to calibrate this instrument.
If the recalibration or the remote Setpoint is required, proceed as
follows.
a) Configure the remote Setpoint type to be calibrated.
b) Program the low and high limits of the remote Setpoint to the
minimum and maximum values respectively.
c) Apply to the remote Setpoint input a known signal that is slightly
above the low limit of that input.
d) At the parameter “
rsL(
” use the
and
keys to show in
the display the corresponding value of the applied signal. Then
press the
P
key.
e) Apply to the remote Setpoint input a known signal that is slightly
below the high limit of that input.
f) At the parameter “
rsk(
” use the
and
keys to show in the
display the corresponding value of the applied signal. Then press
the
P
key.
ANALOG OUTPUT CALIBRATION
•
Configure I/O 5 for the current output to be calibrated, be it control
or retransmission.
•
In the screen “
Ctrl
”, program manual mode (
man
).
•
Connect a current meter at the analog output.
•
Enter the calibration cycle with the correct password.
•
Select the screen “
ovLC
”. Press the
and
keys for the
controller to recognize the calibration process of the current
output.
•
Read the current indicated on the current meter and adjust the
parameter “
ovLC
” to indicate this current value (use the
and
keys)
•
Select the screen “
ovxC
”. Press the
and
keys for the
controller to recognize the calibration process of the current
output.
•
Read the current indicated on the current meter and adjust the
parameter “
ovxC
” to indicate this current value
•
Press the key in order to confirm the calibration procedure and
return to the operating level.
SERIAL COMMUNICATION
The controller can be supplied with an asynchronous RS-485 digital
communication interface for master-slave connection to a host
computer (master).
The controller works as a slave only and all commands are started by
the computer which sends a request to the slave address. The
addressed unit sends back the requested reply.
Broadcast commands (addressed to all indicator units in a multi drop
network) are accepted but no reply is sent back in this case.
CHARACTERISTICS
•Signals compatible with RS-485 standard. MODBUS (RTU)
Protocol. Two wire connection between 1 master and up to 31
(addressing up to 247 possible) instruments in bus topology. The
communication signals are electrically insulated from the rest of
the device;
•Maximum connection distance: 1000 meters.
•Time of disconnection for the controller: Maximum 2 ms after last
byte.
•Selectable speed; 8 data bits; 1 stop bit; selectable parity (no
parity, pair or odd);
•Time at the beginning of response transmission: maximum 100
ms after receiving the command.
•There is no electrical isolation between serial communication
(RS485) and channel I/O5
The RS-485 signals are:
D1 D D +
B Bi-directional data line.Terminal 16
D0
D -
A
Bi-directional inverted data line.
Terminal 17
C
Optional connection that improves the
performance of the communication.
Terminal 18
GND
CONFIGURATION OF PARAMETERS FOR SERIAL
COMMUNICATION
Three parameters must be configured for using the serial type:
bavd
: Communication speed.
prty
: Parity of the communication.
addr
: Communication address for the controller.
REDUCED REGISTERS TABLE FOR SERIAL
COMMUNICATION
COMMUNICATION PROTOCOL
The MOSBUS RTU slave is implemented. All configurable parameters
can be accessed for reading or writing through the communication port.
Broadcast commands are supported as well (address 0).
The available Modbus commands are:
03 - Read Holding Register 06 - Preset Single Register
05 - Force Single Coil 16 - Preset Multiple Register
HOLDING REGISTERS TABLE
Follows a description of the usual communication registers. For full
documentation download the Registers Table for Serial
Communication in the N1100 section of our web site –
www.novusautomation.com.
P
D:

N1100 Controller
NOVUS AUTOMATION 11/11
All registers are 16 bit signed integers.
Address Parameter
Register Description
0000 Active SP Read: Active control SP (main SP, from
ramp and soak or from remote SP).
Write: to main SP.
Range: from
spll
to
spkl
.
0001 PV Read: Process Variable.
Write: Not allowed.
In case of temperature reading, the value
read is always multiplied by 10,
independently of
dppo
value.
0002 MV
Read: Output Power in Automatic or
Manual mode.
Write: only allowed when in Manual mode.
Range: 0 to 1000 (0.0 to 100.0 %).
SPECIFICATIONS
DIMENSIONS:........................................48 x 48 x 110 mm (1/16 DIN)
............................................................Approximate Weight: 150 g
CUTOUT IN THE PANEL:...................45.5 x 45.5 mm (+0.5 -0.0 mm)
POWER SUPPLY:.....................100 to 240 Vac/dc (±10 %), 50/60 Hz
Optional 24V:.....................12 to 24 Vdc / 24 Vac (-10 % / +20 %)
Maximum consumption:........................................................ 9 VA
ENVIRONMENTAL CONDITIONS:
Operation Temperature: ................................................5 to 50 °C
Relative Humidity:...................................... 80 % max. up to 30 ºC
For temperatures above 30 ºC, reduce 3 % for each ºC
Internal Use; Category of installation II, Degree of pollution 2;
altitude < 2000 m.
INPUT.............T/C, Pt100, voltage and current (according to Table 1)
Internal Resolution:................................... 32767 levels (15 bits)
Resolution of Display:...... 12000 levels (from -1999 up to 9999)
Rate of input reading:.................................... up to 5 per second
Precision: ..Thermocouples J, K, T,E: 0.25 % of the span ±1 ºC
...................Thermocouples N, R, S, B: 0.25 % of the span ±3 ºC
................................................................Pt100: 0.2 % of the span
............................. 4-20 mA, 0-50 mV, 0-5 Vdc: 0.2 % of the span
Input Impedance: .0-50 mV, Pt100 and thermocouples: >10 MΩ
................................................................................. 0-5 V: >1 MΩ
................................................ 4-20 mA: 15 Ω(+2 Vdc @ 20 mA)
Measurement of Pt100: .............. Three wires type, (α=0.00385)
with compensation for cable length, excitation current of 0.170 mA.
All input and output types are factory-calibrated. Thermocouples
according to standard NBR 12771 / 99, RTD’s NBR 13773 / 97;
ANALOGICAL OUTPUT (I/O5):......0-20 mA or 4-20 mA, 550 Ωmax.
.....31000 levels, Isolated, for control or retransmission of PV and SP.
CONTROL OUTPUT:
2 Relays SPST-NA (I/O1 and I/O2): 1.5 A / 240 Vac, general use
..........................1 Relay SPDT (I/O3): 3 A / 250 Vac, general use
..........................Voltage pulse for SSR (I/O5): 10 V max. / 20 mA
.............Voltage pulse for SSR (I/O3 and I/O4): 5 V max. / 20 mA
INPUT OF REMOTE SP:........................ 0-20 mA, 4-20 mA, 5 V, 10 V
The Remote SP mA inputs require an external resistor of 100 R
connected directly to the terminals 9 and 10 of the controller's back
panel.
ELECTROMAGNETIC COMPATIBILITY:............... EN 61326-1:1997
and EN 61326-1/A1:1998
SAFETY: .......................... EN61010-1:1993 and EN61010-1/A2:1995
USB INTERFACE: 2.0, CDC class (virtual communications port),
MODBUS RTU protocol.
SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6.3
mm;
FRONT PANEL: IP65, polycarbonate - UL94 V-2;
CASE: IP20, ABS+PC UL94 V-0;
PROGRAMMABLE CYCLE OF PWM: 0.5, up to 100 seconds;
STARTS UP OPERATION: after 3 seconds connected to the power
supply;
CERTIFICATIONS: ..................................... CE / UL (FILE: E300526)
IDENTIFICATION
N1100 -
3R -
485 -
24V
A
B
C
D
A: Controller model:
N1100;
B: Optional I/Os:
Blank: (basic version, without I/O3 nor I/O4);
3R (SPDT Relay in I/O3);
DIO (Digital I/Os in I/O3 and I/O4);
C: Digital Communication:
Blank (basic version, without serial communication);
485 (RS485, Modbus protocol)
D: Power Supply:
Blank (basic version, 100 to 240 Vac/dc);
24V (12 to 24 Vdc / 24 Vac input voltage).
SAFETY INFORMATION
Any control system design should take into account that any part of
the system has the potential to fail. This product is not a protection or
safety device and its alarms are not intended to protect against
product failures. Independent safety devices should be always
provided if personnel or property are at risk.
Product performance and specifications may be affected by its
environment and installation. It’s user’s responsibility to assure
proper grounding, shielding, cable routing and electrical noise
filtering, in accordance with local regulations, EMC standards and
good installation practices.
SUPPORT AND MAINTENANCE
This product contains no serviceable parts inside. Contact our local
distributor in case you need authorized service. For troubleshooting,
visit our FAQ at m www.novus.com.br.
LIMITED WARRANTY AND LIMITATION OF LIABILITY
NOVUS warrants to the original purchaser that this product is free
from defects in material and workmanship under normal use and
service within one (1) year from the date of shipment from factory or
from its official sales channel to the original purchaser.
NOVUS liability under this warranty shall not in any case exceed the
cost of correcting defects in the product or of supplying replacement
product as herein provided and upon the expiration of the warranty
period all such liability shall terminate.
For complete information on warranty and liability limitations, check
appropriate section in our web site:
www.novusautomation.com/warranty.
Table of contents
Other Novus Controllers manuals
Popular Controllers manuals by other brands

Teledyne
Teledyne SofTA 300S ELSD quick start guide

Gira
Gira 1288 Series operating instructions

Feniex
Feniex FLASHER H-2220 manual

Mitsubishi
Mitsubishi FX3G-14MR/ES installation manual

Firetrol
Firetrol FTA570F-AG003E Installation and maintenance manual

ProMinent
ProMinent DULCOMETER Assembly and operating instructions