Interval between defrost cycles. Adjustable between 0 and 999
seconds/minutes/hours, depending on the specified time base.
Defrost duration. Adjustable between 0 and 999 seconds/minutes/hours ,
depending on the specified time base.
Hold the temperature indication throughout the defrost interval or the time defined
by this parameter.
0Allows to update the defrost indication.
1to 250 Time (seconds/minutes/hours) besides the defrost time the
indication will remain held.
Enables compressor protection by monitoring the electrical voltage if the
mains voltage is not between the Setpoints C P L and C PH.
0Disables compressor protection.
1Enable compressor protection.
Function available only for N321R-NTC-LVD model.
Determines a delay in compressor shutdown during the activation of compressor
protection by voltage monitoring. Adjustable time interval between 5 and 30
seconds.
Function available only for N321R-NTC-LVD model.
Voltage lower limit used by the compressor protection. Voltage minimum
value at which the compressor can operate.
Parameter adjustable between 150 to 254 Vac must be obligatorily 5 Vac
lower than the value set at the higher limit (CPH).
Function available only for N321R-NTC-LVD model.
Voltage higher limit used by the compressor protection. Voltage maximum
value at which the compressor can operate.
Parameter adjustable between 150 to 254 Vac must be obligatorily 5 Vac
higher than the value set at the lower limit (C P L ).
Function available only for N321R-NTC-LVD model.
Controllers with the optional RS485 Modbus RTU communication interfac e
have the Add parameter at the Configuration level. Set a unique
communication address for each equipment connected to the network. You
must set an address between 1 and 247.
Level 3 –Calibration Level
The controller is factory calibrated. Recalibration should only be done by qualified
personnel. Press the key for 3 seconds to access this level. This level alsocontains
the parameters for protectionconfiguration.
If you access it by accident, go throughall the parameters without changing them,
until the controller returnsto the measurement level.
Password. Parameter to enter a password to allow changes to the other
parameters.
Calibration Low. Calibration of the measuring range offset. Adjustment of
the lower value of the sensor measuring range.
Calibration High - Gain calibration. Adjustment of the upper value of the
sensor measuring range.
Voltage Calibration. Offset adjustment for calibrating the voltage
indication. Adjustable between -20 to 20 °C (-4 to 68 °F). Function available only
for N321R-NTC-LVD model.
Frequency. Line frequency. Line frequency setting for the supply voltage
supervisor.
060 Hz
150 Hz
Function available only for N321R-NTC-LVD model.
Cold Junction Calibration. Function available only for thermocouples.
Factory Calibration. Restores factory calibration parameters. When changed
from 0to 1, the original calibration is retrieved and changes to the calibration
will be ignored.
Protection. Defines the levels of parameters to be protected.
Password Change. Parameter that allows you to change the curren t
password. You can set the password to a number between 1 and 999.
Serial number. First part of the controller electronic serial number.
Serial number. Second part of the controller electronic serial number.
Serial number. Third part of the controller electronic serial number.
WORKING WITH THE CONTROLLER
The controller turns on the control output to maintain the system temperature at the
selected Setpoint. The front panel display shows the symbol whenever the compressor
is active. The defrost processof this controller is executed by stopping the compressor.
This procedure is done every time interval defined by the user. The control outputremains
off by time also defined by the user. During the defrost procedure, the temperature
indication can be held by adjusting theparameter dFk.
The d f 1 and dFt parameters define, respectively, the time interval betweendefrosts
and the duration of the defrost cycle. The controller displayshowsthe symbol to
indicate that a defrost cycle is in progress.
Manual defrost: The key allows you to start or stop the defrost immediately. By
pressing this key for 1 second, the controller is forced into defrost. If it is in defrost, it will
be forced to end.
CONFIGURATION PROTECTION
The configuration protectionsystem prevents unduechanges to the controller
parameters and, consequently, to its operating mode. This system is composed of
parameters that define the degree of protectionadopted (whether total or only partial).
Parameters that define protection:
P A s : Parameter to enter a password to allow changes in theother parameters.
P r t : Parameter to define the level of parameters that will be protected:
1- Only Calibration level is protected (Default configuration).
2- Calibration and Configuration levels are protected.
3- All levels are protected: Calibration, Configuration and SP.
PAC Parameter to changethe current password. Valid passwordsare in the range
0 to 999.
Configuration protection usage
The PAS parameter is displayed before entering a protected level. If the correct
password is entered, parametersin all following levels can be changed. If wrong or no
password is entered, parametersin the following levels will be read-only.
Important notes:
1 - After 5consecutive attempts to enter a wrong password, new tentative will be
blocked for the next 10 minutes. If the current valid password is unknown, the
master password can be used only to define a new password for thecontroller.
2 - The equipment leaves the factory with password 111.
MASTER PASSWORD
The master password, whichallows you todefine a new password for the controller, is
based in the serial number of thecontroller, and calculated as following:
[ 1 ] + [ higher digit of SN2 ] + [ higher digit of SN1 ] + [ higher digit of SN0 ]
For example, the master password for a devicewithserial number 97123 465 is: 1936
As follows: 1 + sn2= 97; sn1= 123; sn0= 465 = 1 9 3 6
How to use the master password:
1 - In the PA S parameter, enter the master password.
2 - In the PACparameter, enter a new password, which mustnot be zero (0).
3 - Use this new password.
ERROR MESSAGES
On the display, the controllershows messages that correspond to problemsrelated to
the temperature measurement. Wheneverthey are displayed, the control output relay is
turned off.
•Measured temperature exceeded maximum measurement range of the
sensor.
•Broken Pt100. Short-circuited NTC sensor.
•Measured temperature exceeded minimum measurement range of the
sensor.
•Short circuited Pt100. Broken NTC.
COMPRESSOR PROTECTION (N321R-NTC-LVD)
The controller constantly monitors the voltage of power networkand shutsthe compressor
if this tension is not within limits. These limitsare defined in parameters CPL and CPK,
adjustable between150 and 254 Vac.
In addition to shuttingdown the compressor, the controller starts to signal this occurrence
on its display: Toggles the indication of voltage value measured with the temperature
value.
If the voltage is below 150 Vac, it should indicate 0. When it exceeds 254 Vac, it should
saturate and indicate 255 Vac.
WARRANTY
For warranty conditions and returns, please contact sales@temperature.com.au
Temperature °Controls Pty Ltd
7 Yamma Street, Sefton NSW 2162 61 2 9721 8644
8/280 Whitehall St., Yarraville VIC 2013 61 3 9687 0000
36 121-125 Kerry Rd., Archerfield QLD 4108 61 7 3373 8424
sales@temperature.com.au
www.temperature.com.au
www.temperatureshop.com.au