Thank you for purchasing this product of
Olympia Electronics. A European manufacturer.
GENERAL
o
These luminaires are used indoors (ta 40 C)
where emergency light is needed.
Each luminaire must be permanently connected
to mains power supply.
In normal operation the led strip lights and the
battery is charging.
In case of a mains power supply failure the
luminaire will light the led strip automatically in
emergency mode (powered by its battery).
When the mains power supply is restored the
device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 4.
Battery Cut-off
The luminaire enters in this operation when the
mains power supply fails and battery has lost its
energy. During this operation the luminaire
enters the idle state and battery consumption is
negligible, in order to be protected from deep
discharge.
Battery charging
The battery charging is completely controlled. In
this case, the best possible battery
maintenance is achieved, as well as the
elongation of its duration. When the battery has
completely charged, it charges with a
maintenance current.
Manual Test
The manual test can be conducted only if the
main power supply and the battery is
connected. By pressing the test button briefly an
operation test is initiated. During this test period
all indication LEDs are OFF.
Automatic test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
main power supply and the battery should be
connected.
Automatic Autonomous Test
The Automatic autonomous Test is conducted
and measures the luminaire`s back up
operation. This test is conducted automatically
every six months. In order to be performed, the
main power supply and the battery should be
connected (the battery should be charged). If
the battery is not charged, the test is postponed
until the battery is completely charged. If during
the Automatic Autonomous Test the luminaire’s
duration is lower than the named, then the
battery must be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
stated in the technical characteristics. During
emergency mode, a LED strip test is also
performed.
Resetting Errors
Push the Test button for 5 seconds, to
extinguish all the indicated LED errors. Then
the luminaire enters regular operation mode.
Indication LED status (with connected mains
power supply).
AC Charge
On: Good charge current.
Οff: No battery (No charging current
Page 1 from 4
SELF-TESTING MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LED’s
GR-316/30LGR-316/15L
GR-315/15L GR-315/30L
220-240V AC/50-60Hz
3.5W / 7VA 5W / 8VA3.5W / 7VA
Bayblend FR3010, transparent polycarbonate
TECHNICAL CHARACTERISTICS
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
CHARGING TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
ILLUMINATION (MAINS / EMERGENCY)
ILLUMINATION SOURCE
180min
90min
24h
Charge, lamp fault, fault indication LED, TEST button
From overcharge and full discharge
IP 40
3.6V/1Ah 3.6V/1.5Ah 3.6V/3Ah
30 white LED’s 30 white LED’s 15 white LED’s 15 white LED’s
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
0 to 40 C
o
Up to 95%
3 years (1 year for the battery)
630gr. 770gr.
350 x 134 x 45 mm (CRV 362 x 134 x 58 mm)
923316010_09_008
210lm / 210lm 210lm / 210lm 105lm / 105lm 105lm / 105lm
5W / 7.5VA
700gr.