Page 2 from 5923939013_09_004
measures the device’s back up operation and
emergency duration. This test is conducted
automatically every 6 months. In order to be
performed, the mains power supply and the
battery should be connected and fully charged. If
the battery is not fully charged, the test is
postponed until the battery is completely
charged. If during this test, the autonomy is less
than nominal then the battery fault led turned on
continuously and the battery must be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is stated
in the list of the technical characteristics. During
emergency mode, a light source test is also
performed.
Resetting Errors
Push the TEST/RESET button (page 3) for more
than 5 seconds, to delete all the indicated LED
errors. Then the device enters regular operation
mode.
Indication LED status (with connected mains
power supply).
Charge
On: Good charge current.
Οff: No battery (No charging current
or disconnected battery).
Lamp Fault (with L1 connected to L)
Οn (with LED strip off): Faulty LED strip (must
be replaced).
Οn (with LED strip on): Problem in the back up
circuit of the LED strip (must be checked by an
authorized personnel).
Off: Good LED strip.
Battery Fault
Οff: Battery OK.
Blink (With Charge LED ON): Autonomy or low
battery problem (the battery must be replaced).
Blink (With Charge LED Off): No charging
current or disconnected battery.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only.
2. The device must be connected to the mains
power supply through a fuse dependent on the
total amount of the line’s power load.
3. In case of battery or lamp replacement, these
must be replaced by parts of the same type, by the
manufacturer or by a competent person.
4. In case of inactive use for a period greater than 2
months, disconnect the battery by pulling out the
battery’s connector.
5. I s not allowed to discard batteries in to t i
common trash bins, they must be
discarded only in battery recycling
points. Do not incinerate.
NOTE!! After finishing the installation you
must power the luminaire at least for 24 hours
for battery charging to perform the nominal
autonomy.
Battery replacement
It can be done only by a competent person
and after the mains interruption
1. Unfasten the 4 retaining screws (step 10 of the
installation instructions) and remove the
diffusor.
2. Unfasten the 2 retaining screws step 9 of the
installation instructions and remove the
reflector.
3. Remove the old battery and place a new on of
the same type and characteristics.
4. Replace the removed parts (previous steps
1,2).
The light source contained in this luminaire shall only be replaced by the manufacturer, or his
agent, or a similar qualified person.
NOTE! The light source is non-user replaceable.
(*) Maintained operation: The luminaire lights its illumination source, when it is powered by the
mains power supply or not.
Non Maintained operation: The luminaire lights its illumination source, only in power supply’s
failure.
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
1: Maintained (*)
A: Including test device
B: Including remote rest mode
C: Including inhibiting mode
G: Internally illuminated safety sign
*90: 1.5 hour duration
180: 3 hours duration
Note!! The installer should fill in, on the specification
label, the letter G if the luminaire is used as a safety
sign.
*
X190ABCG