Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the device’s back up operation
and emergency duration. This test is conducted
automatically every 6 months. In order to be
performed, the mains power supply and the
battery should be connected and fully charged. If
the battery is not fully charged, the test is
postponed until the battery is completely
charged. If during this test, the autonomy is less
than nominal then the battery fault led turned on
continuously and the battery must be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is stated
in the list of the technical characteristics. During
emergency mode, a light source test is also
performed.
Resetting Errors
Push the TEST/RESET button for 5 seconds, to
delete all the indicated LED errors (page 3). Then
the luminaire enters regular operation mode.
Indication LED status (with connected mains
power supply).
Charge
On: Good charge condition.
Οff: No battery (No charging current
or disconnected battery).
Lamp Fault with L1 connected to L
Οn (with LED strip off): Faulty LED strip (must
be replaced).
Οn (with LED strip on): Problem in the back up
circuit of the LED strip (must be checked by an
authorized personnel).
Off: Good LED strip.
Battery Fault
Οff: Battery OK.
Blink (With Charge LED ON): Autonomy or low
battery problem (the battery must be replaced).
Blink (With Charge LED Off): No charging
current or disconnected battery.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personel
only, after a mains interruption.
2. The device must be connected to the mains
power supply through a fuse dependent on the
total amount of the line’s power load.
3. In case of battery or lamp replacement, these
must be replaced by parts of the same type, by
the manufacturer or by a competent person.
4. In case of inactive use for a period greater
than 2 months, disconnect the battery by pulling
out the battery’s connector.
5. I s not allowed to discard batteries in to t i
co mmo n tr ash bin s, t he y mu s t b e
discarded only in battery recycling
points. Do not incinerate.
NOTE: LED= Light Emitting Diode
L A B E L I N G E X P L A N A T I O N :
X: Self contained
1: Maintained (*)
A: Including test device
B: Including remote rest mode
C: Including inhibiting mode
G: Internally illuminated
*90: 1.5 hour duration
180: 3 hours duration
(*) Maintained operation: The luminaire lights its
illumination source, when it is powered by the
mains power supply or not.
Non Maintained operation: The luminaire lights its
illumination source, only in power supply’s failure.
Note!! The installer should fill in, on the
specification label, the letter G if the luminaire is
used as a safety sign.
NOTE!! After finishing the installation you
must power the luminaire at least for 24 hours
for battery charging to perform the nominal
autonomy.
Battery replacement
It can be done only by a competent person
and after the mains interruption.
1. Unfasten the 4 retaining screws (not all the
way) (step 10 of the installation instructions) and
remove the diffusor.
2. Unfasten the 2 retaining screws (step 9 of the
installation instructions) and remove the reflector.
3. Remove the old battery and place a new one
of the same type and characteristics.
4. Replace the removed parts (previous steps
1,2).
The light source contained in this luminaire
shall only be replaced by the manufacturer,
or his agent, or a similar qualified person.
NOTE! The light source is non-user replaceable.
923939015_09_004
Page 2 from 5
X1 81 0A B C G