9
Parallel Interface
NPN I/O type FJ-3000/FJ-3050/FJ-H3000/FJ-H3050
FJ-3000-10/FJ-3050-10/FJ-H3000-10/FJ-H3050-10
Internal Specications
[Input] signals: RESET, DI0 to DI7, DSA0, DSA1
Input voltage 12 to 24 V DC ±10 %
ON current *1 5 mA min.
ON voltage *1 8.8 V min.
OFF current *2 0.5 mA max.
OFF voltage *2 1.1V max.
ON delay 5 ms max.
OFF delay 0.7 ms max.
Internal circuit
COM IN
[Input] signals: STEP0/ENCTRIG_Z0, STEP1/ENCTRIG_Z1,
ENCTRIG_A0 to 1, ENCTRIG_B0 to 1
Input voltage 12 to 24 V DC ±10 %
ON current *1 5 mA min.
ON voltage *1 8.8 V min.
OFF current *2 0.5 mA max.
OFF voltage *2 0.8 V max.
ON delay 0.1 ms max.
OFF delay 0.1 ms max.
Internal circuit
COM IN
Input terminalInput terminal
*1 ON current/ON voltage
This refers to the current or voltage values needed to shift from the OFF → ON state. The ON voltage value is the potential difference
between each of the input terminals and COM IN.
*2 OFF current/OFF voltage
This refers to the current or voltage values needed to shift from the ON → OFF state. The OFF voltage value is the potential difference
between each of the input terminals and COM IN.
[Output] signals: BUSY0, RUN/BUSY1, OR0 to 1, GATE0 to 1,
ERROR, DO0 to 15, READY0 to 1
Output voltage 12 to 24 V DC ±10 %
Load current 45 mA max.
ON residual voltage 2 V max.
OFF leakage current 0.2 mA max.
Internal circuit
COM OUT
[Output] signals: When STGOUT0 to 3 are used,
connect the COMIN terminal.
Output voltage 12 to 24 V DC ±10 %
Load current 45 mA max.
ON residual voltage 2 V max.
OFF leakage current 0.2 mA max.
Internal circuit
COM IN
COM OUT
I/O Connector
No.
Signal name
Wire color
Mark (red)
Function
No.
Signal name
Wire color
Mark (blk)
Function
A1
COMIN Orange Common for input signals
B1
RESET Orange Controller restart
A2
ENCTRIG_A1 (*2)
Gray
Encoder trigger input (Phase A)
B2
ENCTRIG_A0
Gray
Encoder trigger input(Phase A)
A3
ENCTRIG_B1 (*2)
White
Encoder trigger input (Phase B)
B3
ENCTRIG_B0
White
Encoder trigger input(Phase B)
A4
STEP1 (*2)/
ENCTRIG_Z1 (*2)
Yellow Measurement trigger input/
Encoder trigger input (Phase Z)
B4
STEP0/
ENCTRIG_Z0
Yellow
Measurement trigger input/
Encoder trigger input(Phase Z)
A5
DSA1 (*2) Pink Data send request signal
B5
DSA0 Pink Data send request signal
A6
DI1 Orange Command inputs
B6
DI0 Orange Command inputs
A7
DI3 Gray
B7
DI2 Gray
A8
DI5 White
B8
DI4 White
A9
DI7 Yellow
B9
DI6 Yellow
A10
STGOUT1 Pink Strobe trigger output (*1)
B10
STGOUT0 Pink Strobe trigger output (*1)
A11
STGOUT3 Orange Strobe trigger output (*1)
B11
STGOUT3 Orange Strobe trigger output (*1)
A12
ERROR Gray ON when there is an error.
B12
RUN/BUSY1 (*2)
Gray
ON by layout setting/ON during processing
A13
COMOUT1 White Common for control signals
B13
BUSY0 White ON during processing
A14
GATE1 (*2) Yellow ON for the set output time
B14
GATE0 Yellow ON for the set output time
A15
OR1 (*2) Pink Overall judgment result
B15
OR0 Pink Overall judgment result
A16
READY1 (*2) Orange
ON when image input is allowed
B16
READY0 Orange
ON when image input is allowed
A17
COMOUT2 Gray Common for output signals
B17
DO0 Gray Data output
A18
DO1 White Data output
B18
DO2 White
A19
DO3 Yellow
B19
DO4 Yellow
A20
DO5 Pink
B20
DO6 Pink
A21
DO7 Orange
B21
DO8 Orange
A22
DO9 Gray
B22
DO10 Gray
A23
DO11 White
B23
DO12 White
A24
DO13 Yellow
B24
DO14 Yellow
A25
COMOUT3 Pink Common for output signals
B25
DO15 Pink
•Handling the output common terminals
COMOUT1: STGOUT0 to 3, RUN/BUSY1, ERROR, BUSY0, OR0 to 1, GATE0 to 1 COMOUT2: READY0 to 1, DO0 to 7 COMOUT3: DO8 to 15
*1
This is a signal that is used when the strobe device is connected to the Controller. In camera 2ch type, only STGOUT0 and STGOUT1 can be used.
*2 This signal is only available in the Random trigger mode.
Output terminal
Output terminal
Load Load