Omron E5GN User manual

c-sc 1. 00
c-db 0. 0
chys 1. 0
Input type *2
Scaling upper limit
(only when setting analog input)
Scaling lower limit
(only when setting analog input)
Decimal point
(only when setting analog input)
°C/°F selection
Set point upper limit
Set point lower limit
In ON/OFF control =
In 2-PID control =
Standard control = stnd
Heating and cooling control = h-c
(Select standard control or healing
and cooling control as required)
Control period (control output 1)
(Unit: Seconds)
Control period (control output 2)
(Unit: Seconds)
Alarm 1 type: Specified models only
°C=
°F=
(C stands for Celsius, F for Fahrenheit)
Self-tuning ON =
Self-tuning OFF =
In Reverse operation(heat) =
In Direct operation(cool) =
*2
*3
Initial setting level enables users to specify their preferred operating
conditions (input type, alarm type, control method, etc.)
*2: Refer to the adjoining tables for details of input types and alarm types.
• Up and Down keys
Use the keys to change the values displayed on
the No.2 display.
Each press of Ukey increments or advances
the values displayed on the No.2 display.
Each press of Dkey decrements or returns the
values displayed on the No.2 display.
●
Connections
(The applicability of the electric terminal varies with the type of machine.)
■Wiring
■Operation menu
●Installation
●Dimensions
Operation indicators
• CMW:
communications writing enable/disable indicator
Lights when communications writing is “enabled”
and is out when it is “disabled”.
• STOP: control stop indicator
Lights when “Run/Stop” is stopped during opera-
tion.
During control stop, functions other than control
output are valid.
• OUT: Control output 1/Control output 2 indicator
Lights when control outputs 1 and 2 are ON or
either of them is ON.
• °C / °F : temperature unit
The temperature unit is displayed when
the displayed value is a temperature.
When this parameter is
set to “°C”, “°c” is displayed,
and when set to “°F”, “°f” is displayed.
This flashes while ST(Self-Tuning) is
activated.
• AL : Alarm 1 output indicator
Lights when alarm 1 output is ON.
•Since the voltage output (control output) is not electrically insulated from the internal
wiring, one or other of the control output terminals must be left unearthed when using
an earthed thermocouple thermometer. (Connection makes measurements unreliable
due to sneak currents.)
•
Power supply, input, output, and communication terminals (for models with
communications) have basic insulation between them.
When double insulation is required, apply supplemental insulation defined in
IEC 60664 that is suitable for the maximum operating voltage with clearances
or solid insulation.
• Insert the controller through the hole in the panel. Push
the adapter on from the rear and fasten temporarily, re-
moving any gap between the controller, panel and adap-
ter. Finally, secure two fixing screws alternately keeping
the torque to between 0.29 to 0.39 N•m.
Dimensions (mm) (48 x number of units –2.5)
Individual mounting (mm)
Side-by-side mounting(waterproof not possible) (mm)
●Names of parts on front panel
• No.1 display
Process value or set data symbol
• No.2 display
Set point, set data read-out value or changed
input value
• Mode key
Press this key to change the contents of the
display
* Terminal part can be removed for maintenance without disconnecting the terminal wiring.
E5GN
Temperature controller
POWER ON
CAUTION
Do not touch terminals when voltage is applied.
Electric shock hazard
Do not allow metal fragments or lead wire scraps to fall inside this product. This may cause electric shock, fire
or malfunction.
Do not use this product where subject to flammable or explosive gas.
Doing so may cause explosion.
Never disassemble, repair or modify the product. This may cause electric shock, fire or
malfunction.
CAUTION - Risk of Electrical Shock
a) Devices are Open Type, Listed Process Control Equipment and must be mounted in an enclosure.
b) More than one disconnect switch may be required to de-energize the equipment before servicing.
c) Signal inputs are SELV, limited energy.
d) Caution - To reduce risk of fire or Electrical shock, Do not interconnect the outputs of different Class 2
circuits.
The life expectancy of the output relay varies considerably according to its the output relay within its rated load
and electrical life expectancy, if the output relay is used beyond its life expectancy, its contacts may become
fused or burned.
Use copper stranded or solid wire only. For terminals 1-6 use 24-14 AWG. For terminals 7-9 use 28-22 AWG.
Tightening torque: Terminals 1-6: 0.24N•m, 2 inch lbs(max), Terminals 7-9: 0.13N•m, 1.2 inch lbs(max)
Loose screws may cause malfunction.
Correctly set the settings on the temperature controller matched to the control target.If the settings are not
compatible with the control target, the product may operate in an unexpected manner, resulting in damage to
the product or an accident.
To maintain safety in the event of malfunction of the temperature controller, we recommend taking safety
measures, for example, installing an excessive temperature rise prevention alarm on a separate line. If
malfunction prevents control, this may result in a major accident.
WARNING: To reduce the risk of electric shock or fire, install in a Pollution Degree 2 environment (a
controlled environment relatively free of contaminants).
(1) Do not use this product in the following places:
• Places directly subject to heat radiated from heating equipment.
• Places subject to splashing liquid or oil atmosphere.
• Places subject to direct sunlight.
•Places subject to dust or corrosive gas (in particular, sulfide gas and
ammonia gas).
• Places subject to intense temperature change.
• Places subject to icing and condensation.
• Places subject to vibration and large shocks.
(2) Use/store within the rated temperature and humidity ranges.
Provide forced-cooling if required.
(3) To allow heat to escape, do not block the area around the product.
Do not block the ventilation holes on the product.
(4) Be sure to wire properly with correct polarity of terminals.
(5) Use AWG24 to AWG14 leads for terminal Nos. 1 to 6 and AWG28 to AWG
22 for terminal Nos. 7 to 9 (with lead cover peel back allowance of 5 or 6
mm).
(6) Do not wire the terminals which are not used.
(7) Allow as much space as possible between the controller and devices that
generate a powerful high-frequency or surge.
Separate the high-voltage or large-current power lines from other lines, and
avoid parallel or common wiring with the power lines when you are wiring to
the terminals.
(8) Use this product within the rated load and power supply.
(9) Make sure that the rated voltage is attained within two seconds of turning the
power ON.
(10) Make sure the controller has 30 minutes or more for warm up.
(11) When executing self-tuning, turn the load and the unit ON simultaneously,
or turn the load ON before you turn the controller ON.
(12) A switch or circuit breaker should be provided close to this unit.
The switch or circuit breaker should be within easy reach of the operator,
and must be marked as a disconnecting means for this unit.
(13) When you have removed the terminal block, never touch nor apply shock to
the terminals and the electronic components inside.
(14) Cleaning: Do not use paint thinner or the equivalent. Use standard grade
alcohol to clean the product.
Precautions for safety use
0682727-0H
●Operation level
●Adjustmentlevel
●Protect level
●Initial setting level
For detailed operating instructions, please refer to
the E5GN User's Manual.
Instruction Manual
Thank you for purchasing the OMRON E5GN tempera-
ture controller. Read this manual carefully before using
the controller and always keep it close at hand while the
controller is in use.
OMRON CORPORATION
©All Rights Reserved
●Alarms
*1: Upper and lower limits can be set for parameters 1, 4 and 5 to provide for
different types of alarm. These are indicated by the letter "L" and "H".
• Default = "2"
Alarm type
1
0
2
3
4
5
6
7
8
9
10
11
Vary with "L", "H" values
Vary with "L", "H" values
Vary with "L", "H" values
No alarm function Output off
Deviation upper/lower limit
standby sequence ON
Absolute value upper limit
Absolute value lower limit
Absolute value upper limit
standby sequence ON
Absolute value lower limit
standby sequence ON
Deviation lower limit
standby sequence ON
Deviation upper limit
standby sequence ON
Deviation upper/lower range
Deviation upper limit
Deviation upper/lower limit
Deviation lower limit
Alarm output function
Positive alarm value (X)
LH
LH
LH
ON
OFF SP
Negative alarm value (X)
X
ON
OFF SP
ON
OFF SP
X
X
ON
OFF SP
ON
OFF SP
ON
OFF SP
X
XX
ON
OFF SP
ON
OFF SP
ON
OFF SP
X
X
XX
ON
OFF SP
ON
OFF SP
ON
OFF 0
ON
OFF X
X
0
ON
OFF 0
ON
OFF X
X
0
ON
OFF 0
ON
OFF X
0
ON
OFF 0
ON
OFF X
0
Setting
*1
*1
*1
■Other functions
In addition to the aforementioned, there are alarm hysteresis,
automatic return of display mode and others in the advanced
setting level.
Refer to "E5GN User's Manual" for details.
For communications details, please refer to "E5AN/EN/CN/GN
communications User's Manual".
In the pack:
• Main unit
• Watertight packing
• Adapter
• Instruction manual
Suitability for Use
OMRON shall not be responsible for conformity with any standards, codes, or regulations that
apply to the combination of the products in the customer's application or use of the product.
Take all necessary steps to determine the suitability of the product for the systems, machines,
and equipment with which it will be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE
OMRON PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL
EQUIPMENT OR SYSTEM.
See also Product catalog for Warranty and Limitation of Liability.
Operation stopped.(control/alarm are both stopped.)
●Specifications
Power supply voltage
Operating frequency
Operating voltage range
Power consumption
Indication accuracy
Control output 1
Control method
Alarm output
(control output 2)
Ambient temperature
Ambient humidity
Storage temperature
Altitude
Recommended fuse
Weight
Installation environment
100-240V AC type
24V AC/DC type
50-60Hz
85 to 110% of the rated voltage
Approx. 7VA (AC100-240V)
Approx. 4VA (AC24V)
Approx. 2.5W (DC24V)
Thermocouple, platinum resistance
thermometer:
(±0.5 % of indication value or ±1
°
C,
which is greater) ±1 digit max.
Analog input:
±0.5 % FS ±1 digit max.
Relay output: SPST-NO,
250VAC 2A (resistive load)
Voltage output 12VDC 21mA
Electrical life of relay:
100,000 operations
ON/OFF or 2-PID control
SPST-NO, 250 VAC, 1 A(resistive load),
electrical life:100,000 operations
–10 to 55°C
(Avoid freezing or condensation)
RH 25 to 85%
–25 to 65°C
(Avoid freezing or condensation)
Max. 2,000m
T2A, 250V AC, time-lag,
low-breaking capacity
Approx. 90g (main unit only)
Setup category II, pollution
degree 2 (as per IEC61010-1)
●Input type
–200to850(℃)
–199.9to500.0(℃)
0.0to100.0(℃)
–199.9to500.0(℃)
0.0to100.0(℃)
/–300to1500(。
F)
/–199.9to900.0(。
F)
/0.0to210.0(。
F)
/–199.9to900.0(。
F)
/0.0to210.0(。
F)
Setting range
Setting
0
1
2
3
4
Input type
Platinum
resistance
thermometer
Input
Pt100
JPt100
Platinumresistance
thermometer
inputtype
–200to1300(℃)
–20.0to500.0(℃)
–100to850(℃)
–20.0to400.0(℃)
–200to400(℃)
–199.9 to 400.0(℃)
0to600(℃)
–100to850(℃)
–200to400(℃)
–199.9 to 400.0(℃)
–200to1300(℃)
0to1700(℃)
0to1700(℃)
100to1800(℃)
0to90(℃)
0to120(℃)
0to165(℃)
0to260(℃)
/–300to2300(。
F)
/0.0to900.0(。
F)
/–100to1500(。
F)
/0.0to750.0(。
F)
/–300to700(。
F)
/–199.9 to 700.0(。
F)
/0to1100(。
F)
/–100to1500(。
F)
/–300to700(。
F)
/–199.9 to 700.0(。
F)
/–300to2300(。
F)
/0to3000(。
F)
/0to3000(。
F)
/300to3200(。
F)
/0to190(。
F)
/0to240(。
F)
/0to320(。
F)
/0to500(。
F)
Setting rangeSetting
0
1
2
3
4
17
5
6
7
18
8
9
10
11
12
13
14
15
16
Input type
Thermocouple
Infrared
Thermosensor
ES1B
Analog input
Input
K
J
T
E
L
U
N
R
S
B
10 –70℃
60 –120℃
115 –165℃
140 –260℃
0to50mV Use the following ranges for scaling:
–1999 to 9999, –199.9 to 999.9
Thermocoupleinputtype
*6: Error shown only for "Process value / Set point". Not shown for other
status.
●Error display (trouble shooting)
When an error has occurred, the No.1 display alternately indicates error
codes together with the current display item.
No.1 display Meaning
A/D converter error
*6
Memory error
Input error
*6
(S. Err)
(E111)
Check the wiring of inputs, disconnections,
shorts and input type.
Turn the power OFF then back ON again. If the dis-
play remains the same, the controller must be re-
paired. If the display is restored to normal, then a
probable cause can be external noise affecting the
control system. Check for external noise.
After the correction of input error, turn the power
OFF then back ON again. If the display remains
the same, the controller must be repaired. If the
display is restored to normal, then a probable
cause can be external noise affecting the control
system. Check for external noise.
CAUTION
Action Status at error
Control
output
OFF
OFF
OFF
OFF
OFF
Alarm
1 2 3 4 5 6 7 89
TC
PT
A
BA
BB
+−
(−)(+)
+−
−+
RS-485
Communications
function
Voltage output
12V DC 21mA
(resistive load)
Control output 1
Input power supply:
•100 to 240V AC Type
•24V AC/DC Type
Analog input
Alarm 1/Control output 2
250V AC 1A
(resistive load)
48
24
35
CMW OUTSTOP
22.2+0.3
0
22.2+0.3
0
40 min.
+1
0
45 +0.6
0
CMW OUTSTOP CMW OUTSTOP
Adjustment level is for entering set
values and shift values for control.
AT execute =
AT cancel =
Communication write
*4
Temperature input shift
(Unit:
°C
or
°
F)
Input shift upper limit
(When Infrared Thermo-
sensor ES1A selected)
Input shift lower limit
(When Infrared Thermo-
sensor ES1A selected)
Proportional band
Derivative time
(Unit: secs)
Cooling coethcient
Dead band
Integral time
(Unit: secs)
Manual reset value
(Unit: %)
Hysteresis
(Control output 1)
Hysteresis
(Control output 2)
Operation level should normally be used
during operations.
PV/SP
Alarm value 1 *4
Alarm value upper limit 1
*3
Alarm value lower limit 1
*3
Run/Stop
When control start =
When control stop =
Operation / adjustment
protect
Initial / Communication
protect
Setting change protect
Restricts which settings can be
displayed or changed, and restricts
change by key operation.
Press
(less than 1 second)
Hold down
for at least
3 seconds
Hold down for
at least 1 second
Hold and
Mkeys down for
at least 3 seconds
*3: Applicable only to models with alarm functions
*4: Applicable only to models with a communications function
*5: Operation is stopped when moved to the initial setting level. (control/alarm are
both stopped.)
*7:
The grayed-out setting items may not be displayed according to the models and setting.
●AT (auto-tuning)
Communication
unit No.
Communication
rate
Data length
Stop bit
Parity
Make sure the communication settings (Communication rate, etc.)
match those of the Host Computer.
●Communication setting level
Press
(less than 1 second)
STX
Node
No. SID FINS-mini
Command text ETX
Sub-
address
BCC
STX
Node No.
Sub-address
SID
FINS-mini
command text
ETX
BCC
Code (H'02) to indicate the head of the communication frame (text).
If STX is received a second time while receiving a communication, it
indicates that the communication is starting again from that point.
Specifies the transmission destination unit No.Settings range from
00 to 99.
"00" (Fixed)
Service ID, "0" (Fixed)
Contains command contents such as read and write values, and sta-
tus data
Code (H'03) indicating the end of the text.
Block check character
Error check method used by FINS-mini.
Each byte from node No. through ETX has an XOR (exclusive OR)
value
For CompoWay / F
●Command format
Command
STX
STX
Node
No.
Node
No.
SID
Sub-ad-
dress
Sub-ad-
dress
Buffer sizeFormat
MRC
MRC
SRC
SRC
Response ETX
Termina-
tion code
Response
code BCC
0 3
0 3
0 5
0 5
0
00
●Controller attribute read-out
Use this function to check the controller's format
and communication buffer size.
212 11222 4 10 4
00
0F
10
11
12
13
14
16
18
Termina-
tion code
Name Description
Normal termination
Command error
Parity error
Framing error
Overrun
BCC error
Format error
Sub-address error
Frame length error
Unexecutable command received
Parity mismatch
No stop bit detected
Receive buffer overflowed
BCC mismatch
Incorrect data length
Incorrect sub-address
When the receive frame exceeds the specified byte count
●Termination code (For CompoWay / F)
• AT in Adjustment level
Designate “on: AT execute” to execute
AT and “off: AT cancel” to cancel AT. Also when AT execution ends, the display
automatically returns to “off”.
ETX BCC
•Make sure that the surrounding temperature does not exceed the
allowable operating temperature given in the specifications espe-
cially when two or more controllers are mounted.
N6
*5
*7
*7
*7
*7 *7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
No.1 display
flushes when hold
down for more
than 1 second
• Level key
Use this key to change levels:
• Press the key and the Mkey together for
at least 3 seconds to switch to protect level.
*4
• Default = "0"
44.8
(36.8)
1003
22
When waterproofing is
required, be sure to mount
the controller separately.
Attach the waterproof
packing from the terminal
side and then insert the
controller to the panel.
Recommended panel
thickness is 1 to 5 mm.
s-hc stnd
c-cp 20
Operates
as above
the upper
limit.
If the input value exceeds the display limit (–1999(–199.9) to
9999(999.9)), though it is within the control range, [[[[ will be displayed
under –1999(–199.9) and ]]]] above 9999(999.9). Under these
conditions, control output and alarm output will operate normally.
Refer to "E5GN User's Manual" for details of control range.
Hold and
Mkeys down for
at least 1 second
U
D
“AT execute” “at” flashes
“AT cancel”
Only the value set to the “ins: temperature input shift”
parameter is applied to the entire temperature input
range. When the process value is 200 °C, the process
value is treated
as 201.2 °C after input shift if the input
shift value is set to 1.2 °C.
The process value is treated as 198.8 °C after input shift
if the input shift value is set to –1.2 °C.
After shift
Before shift
Sensor input
Temperature
Inputshiftvalue:(1.2°C)
501.2℃
500.0℃
201.2℃
200.0℃
-18.8℃
-20.0℃
-20.0℃ 200.0℃ 500.0℃
(Ex.) Thermocouple input type, Input type:1,
Temperature unit:°C, temperature input shift:1.2 °C
Relay output
250V AC 2A
(resistive load)
EN
CAUTION
Indicates a potentially hazardous situation which, if
not avoided, is likely to result in minor or moderate
injury or property damage. Read this manual
carefully before using the product.
CAUTION
Safety Precautions
●Key to Warning Symbols
●Warning Symbols
●Operation / Adjustment protection
The following table shows the relationship between settings and
protect limits related to Operation level and Adjustment level.
Default setting : 0
◎:Can be displayed and changed
○:Can be displayed
×:
Can not be displayed and change
to other levels not possible
Operation level
Adjustment level
Process value
Set point
Others
Level Set value
0
○
◎
◎
◎
1
○
◎
◎
×
2
○
◎
×
×
3
○
○
×
×
●Setting change protection
Setting changes by key operation are restricted.
OFF “off”: Setting can be changed by key operation
ON “on” : Setting cannot be changed by key operation
(Protect level settings can all be changed.)
●Initial setting/Communications protection
This protect level restricts movement to the initial setting level,
communications setting level and advanced function setting level.
Set value
0
1
2
○
○
×
○
○
×
○
×
×
Initial setting
level Communications
setting level
Advanced function
setting level
Default setting : 1
○:Changetootherlevelspossible
×:Changetootherlevelsnotpossible
OMRON ELECTRONICS. LLC
ONE COMMERCE DRIVE SCHAUMBURG, IL 60173-5302 U.S.A
Phone 1-847-843-7900 FAX:1-847-843-7787
EUROPEAN H.Q : OMRON EUROPE B.V
Wegalaan 67-69 P.O.BOX.13 2130 AA HOOFDDORP THE
NETHERLANDS
Phone 31-23-5681300 FAX 31-23-5681388
OMRON ASIA-PACIFIC PTE.LTD.
83, Clemenceau Avenue, #11-01, UE Square, Singapore
239920 SINGAPORE
Phone 65-6-835-3011 FAX 65-6-835-2711

■配線
動作表示LED
・CMW:通信による書き込み可否表示
通信書き込みが許可(ON)で点灯、禁止
(OFF)で消灯します。
・STOP:制御停止表示
運転中に「ラン/ストップ」を停止「stop」
にしたとき点灯します。制御停止中でも制御
出力以外は動作します。
・OUT:制御出力1、制御出力2表示
制御出力1、制御出力2のどちらかが、一方
でもONなら点灯します。
形E5GN
電子温度調節器
●フロント部の名称
●初期設定レベル
●運転レベル
●調整レベル
キー
+ キー
3秒以上
●プロテクトレベル
・第1表示
現在値または設定データの種別を表示します。
・第2表示
目標値、設定データの読出値、変更時の入力値を
表示します。
・モードキー
このキーを押すと、表示項目が変更されます。
・ダウンキー/アップキー
第2表示の値を変更するときに使用します。
キーを押すごとに、第2表示の値がアップし
ます。または設定内容が進みます。
キーを押すごとに、第2表示の値がダウンし
ます。または設定内容が戻ります。
キー操作による設定変更やレベルの移
行を制限します。
運転/調節プロテクト
初期/通信プロテクト
設定変更プロテクト
通信書込*4
温度入力補正値
(単位:℃または。
F)
上限温度入力補正値
(非接触温度センサ
選択時)
積分時間
(単位:秒)
冷却係数
マニュアルリセット値
(単位:%)
調節感度(制御出力1)
下限温度入力補正値
(非接触温度センサ
選択時)
比例帯
微分時間
(単位:秒)
デッドバンド
調節感度(制御出力2)
●通信設定レベル
通信の各種設定は上位コンピュータ側と一致させてください。
通信ユニットNo.
通信速度
通信データ長
通信ストップビット
通信パリティ
●接続(機種によって端子の用途は異なります。)●取付け
●外形寸法図
・本体をパネル角穴へ入れ、アダプタを端子側からパネル面と
のすき間が少なくなるように押し込んで仮固定してください。
次に、アダプタの2箇所の固定ネジを締め付けトルク0.29〜
0.39N・mで交互にバランスをとりながら締め付けて固定して
ください。
・本機の発熱によって周囲温度が仕様を超えないように、複数
個取り付けて使用される場合は、特にご留意ください。
・外形寸法(単位mm) 個別取付のとき(単位mm) 密着取り付けのとき(
防水できません
)(単位mm)
*メンテナンス時に端子配線を外さずに、端子部のみを引き抜くことができます。
22.2
22.2
40以上
(48×台数−2.5)
48
24
35
(36.8)
1003
22
44.8
キー
3秒以上 1秒未満
キー
1秒以上
キー1秒未満
■操作メニュー
入力種別*2
スケーリング上限値
(アナログ入力設定時のみ)
スケーリング下限値
(アナログ入力設定時のみ)
少数点位置
(アナログ入力設定時のみ)
目標値リミット上限値
目標値リミット下限値
制御周期(制御出力1)
(単位:秒)
警報1種別
温度単位
ON/OFF制御の時
2自由度PID制御の時
標準制御の時
加熱冷却制御の時
(標準制御または加熱冷却制御を選択
します。)
℃の時
。
Fの時
(摂氏(℃)または華氏(。
F)のどち
らかに設定します。)
ST
(
セルフチューニング
)
ONの時
ST
(
セルフチューニング
)
OFFの時
逆動作(加熱制御)の時
正動作(冷却制御)の時
●異常時の表示について(トラブルシューティング)
異常が発生すると、第1表示にエラー内容を表示します。エラー表示に
よってエラーの内容を確認し、その内容についての処置をしてください。
■その他の機能
操作方法で説明している機能の他に警報ヒステリシス、
表示モード自動復帰などの機能が別レベルにあります。
詳細は「形E5GNユーザーズマニュアル」を参照して
ください。
通信については、「形E5AN/EN/CN/GN通信機能ユー
ザーズマニュアル」を参照してください。
AT実行の時
AT中止の時
AC100〜240V
または
AC/DC24V
(極性なし)
1 2 3 4 5 6 7 89
TC
PT
A
BA
BB
+−(−)(+)
+−
−+
RS-485通信機能
電圧出力
DC12V21mA
(抵抗負荷)
制御出力1
入力電源 リレー出力
AC250V2A
(抵抗負荷)
アナログ入力
警報1/制御出力2
AC250V1A
(抵抗負荷)
・レベルキー
このキーを押すと、各レベル間を移行します。
・ レベルキーと モードキーを同時に3秒以
上押すと、プロテクトレベルに切り替わります。
●警報種別
警報種別
1
0
2
3
4
5
6
7
8
9
10
11
L,Hの値による
L,Hの値による
L,Hの値による
警報機能なし 出力OFF
上下限
待機シーケンス付
絶対値上限
絶対値下限
絶対値上限
待機シーケンス付
絶対値下限
待機シーケンス付
下限
待機シーケンス付
上限
待機シーケンス付
上下限範囲
上限
上下限
下限
警報出力機能
警報値(X)が正
LH
LH
LH
ON
OFF SP
警報値(X)が負
X
ON
OFF SP
ON
OFF SP
X
X
ON
OFF SP
ON
OFF SP
ON
OFF SP
X
XX
ON
OFF SP
ON
OFF SP
ON
OFF SP
X
X
XX
ON
OFF SP
ON
OFF SP
ON
OFF 0
ON
OFF X
X
0
ON
OFF 0
ON
OFF X
X
0
ON
OFF 0
ON
OFF X
0
ON
OFF 0
ON
OFF X
0
設定値
●AT(オートチューニング)
ATを実行するときは「on:AT実行」、
ATを中止したいときは、「off:AT中止」
を指定してください。
・調整レベルのAT
取扱説明書
オムロン製品をお買い上げいただきありがとうござい
ます。この製品を安全に正しく使用していただくために、
お使いになる前にこの取扱説明書をお読みになり、十
分にご理解ください。お読みになった後も、いつも手
元に置いてご使用してください。
オムロン株式会社
©All Rights Reserved
*1
*1
*1
注意
通電中は端子に触れないでください。
感電の恐れがあります。
製品の中に金属や導線を入れないでください。
感電、火災、故障の原因になります。
引火性、爆発性ガスのあるところでは、使用しないでください。
爆発の恐れがあります。
分解したり、修理、改造はしないでください。
感電、火災、故障の原因になります。
注意 感電の危険
a)当機は、オープンタイプのプロセスコントローラとしてULListingの認定を受けていますので盤内でご使用
ください。
b)2つ以上の遮断スイッチをご使用の場合、修理点検前に、全てのスイッチをOFFし製品を無通電状態にし
てください。
c)信号入力はSELV、制限回路です。
d)注意:火災や感電の危機を低減する為、異なるClass2回路の出力を内部で接続しないでください。
出力リレーの寿命は、開閉容量、開閉条件により大きく異なるので必ず実使用条件を考慮し、定格負荷、電
気的寿命回数内でご使用ください。
寿命を超えた状態で使用すると接点溶着や焼損の恐れがあります。
配線材料は銅製で、より線か、棒線を使用ください。
1〜6番目端子にはAWG24-14、7〜9番端子にはAWG28-22を使用して、ネジ締めトルクは、1〜6番端子:0.24N・
m以下(2lb-inmax)、7〜9番端子:0.13N・m以下(1.2lb-inmax)で締めてください。
ネジがゆるむと発火および誤動作の恐れがあります。
温調器の各種設定値は、制御対象に合わせて正しく設定してください。設定内容と制御対象の内容が異なる
場合には、意図しない動作により装置の破損や事故の原因になります。
温調器の故障時にも安全なように、別系統で過昇温防止警報を取り付けるなどの安全対策を行ってください。
故障により制御不能になると、重大な事故につながる恐れがあります。
警告:感電や、火災の危険度を低減するために、汚染度2(相対的に汚染物質がない状態に管理された環境)
の環境に設置してください。
ご使用に際してのご承諾事項
下記用途に使用される場合、当社営業担当者までご相談のうえ仕様書などによりご確認いただくとともに、定格・
性能に対し余裕を持った使い方や、万一故障があっても危険を最小にする安全回路などの安全対策を講じてください。
a) 屋外の用途、潜在的な化学的汚染あるいは電気的妨害を被る用途またはカタログ、取扱説明書等に記載のない条
件や環境での使用
b) 原子力制御設備、焼却設備、鉄道・航空・車両設備、医用機械、娯楽機械、安全装置、および行政機関や個別業
界の規制に従う設備
c)人命や財産に危険が及びうるシステム・機械・装置
d)ガス、水道、電気の供給システムや24時間連続運転システムなど高い信頼性が必要な設備
e)その他、上記a)〜d)に準ずる、高度な安全性が必要とされる用途
* 上記は適合用途の条件の一部です。当社のベスト、総合カタログ、データシート等最新版のカタログ、マニュアル
に記載の保証・免責事項の内容をよく読んでご使用ください。
梱包内容
・本体
・防水パッキン 1枚
・アダプタ 1個
・取扱説明書
45
●電圧出力(制御出力)は内部回路と電気的に絶縁されていませんので接地タイプの熱電
対を使用する場合は制御出力端子のいずれかをアースに接続しないでください。(接
続しますと回り込み電流により、測定温度に誤差が発生します。)
●電源−入力−出力−通信(通信付きの場合)端子相互間は基礎絶縁です。
二重絶縁が必要な場合、空間距離や固体絶縁などにより最高使用電圧に適した、
IEC60664にて定義されている補助絶縁を施してください。
*1:設定値1、4、5は警報種別の上・下限値が個別に設定でき、
L,Hで表しています。
・初期値は「2」です。
初期設定レベルでは、入力種別、警報種別、制御
方式などのお客様のご使用条件を設定します。
運転中は通常、運転レベルでご使用
ください。
調整レベルは、制御を行うための設
定や補正値を入力するレベルです。
*6:表示が「現在値/目標値」のときだけエラー表示します。他の状態
ではエラー表示しません。
*3:警報機能がある機種だけ機能します。
*4:通信機能がある機種だけ機能します。
*5:初期設定レベルへ移行すると運転が停止します。(制御・警報共に停止)
*7:グレー表示になっている設定項目は、機種や設定内容により表示されない場合
があります。
1)下記の環境では使用しないでください。
・加熱機器から輻射熱を直接受けるところ
・水がかかるところ、被油のあるところ
・直射日光が当たるところ
・塵あい、腐食性ガス(とくに硫化ガス、アンモニアガスなど)のあるところ
・温度変化の激しいところ
・氷結、結露の恐れのあるところ
・振動、衝撃の影響が大きいところ
2)周囲温度および湿度は仕様範囲内で使用および保存してください。必要によ
り、強制冷却してください。
3)放熱を妨げないよう、温調器の周辺をふさがないでください。温調器本体の
通風孔はふさがないでください。
4)端子の極性を確認し、正しく配線してください。
5)配線材は、1〜6番端子はAWG24〜AWG14、7〜9番端子はAWG28〜
AWG22を使用してください。(電線被覆剥きしろ:5〜6mm)
6)使用しない端子には何も接続しないでください。
7)強い高周波を発生する機器やサージを発生する機器から、できるだけ離して
設置してください。配線は、高電圧、大電流の動力線とは分離して配線して
ください。また、動力線との平行配線や同一配線を避けてください。
8)電源電圧および負荷は、仕様、定格の範囲内でご使用ください。
9)電源投入時には、2秒以内に定格電圧に達するようにしてください。
10)ウォームアップ時間は30分以上としてください。
11)セルフチューニングを使用される場合は、温調器と負荷の電源を同時、ある
いは負荷の電源を先に投入してください。
12)作業者がすぐ電源をOFFできるようスイッチまたはサーキットブレーカを設
置し、適切に表示してください。
13)端子台をはずした時、絶対に電子部品に手を触れたり衝撃を与えたりしない
でください。
14)清掃について:シンナー類は使用しないでください。市販のアルコールをご
使用ください。
安全上の要点 ●仕様
電源電圧 AC100-240V、50/60Hz
またはAC24V、50/60Hz
/DC24V
許容電圧変動範囲 定格電圧の85〜110%
消費電力
約7VA(AC100-240V)
約4VA(AC24V)/約2.5W(DC24V)
指示精度 熱電対/白金測温抵抗体
(指示値の±0.5%または±1℃の
大きい方)±1ディジット以下
アナログ入力
±5%FS±1ディジット以下
制御出力1
リレー出力AC250V2A(抵抗負荷)
電圧出力DC12V21mA
リレーの電気的寿命10万回
制御方式 2自由度PIDまたはON/OFF
警報出力
リレー出力AC250V1A(抵抗負荷)
(制御出力2) リレーの電気的寿命 10万回
使用周囲温度 −10〜55℃
(ただし、氷結、結露しないこと)
使用周囲湿度 相対湿度25〜85%
保存温度 −25〜65℃
(ただし、氷結、結露しないこと)
高度 2,000m以下
推奨ヒューズ T2A、250VAC タイムラグ
低遮断容量
質量 約90g(本体のみ)
設置環境 設置カテゴリII、汚染度2
(IEC61010-1による)
CMW OUTSTOP
CMW OUTSTOP
・℃/゜F 温度単位表示
表示されているデータが、温度の場合に点灯
します。表示は選択されている「温度単位」
の設定値により決定され、「゜c」ならば「℃」、
「゜f」ならば「゜F」を意味します。
ST(セルフチューニング)動作中は
点滅します。
・AL:警報1表示
警報1が発生したとき点灯します。
CMW OUTSTOP
●入力種別
–200〜850(℃)
–199.9〜500.0(℃)
0.0〜100.0(℃)
–199.9〜500.0(℃)
0.0〜100.0(℃)
/–300〜1500(°F)
/–199.9〜900.0(°F)
/0.0〜210.0(°F)
/–199.9〜900.0(°F)
/0.0〜210.0(°F)
設定範囲
設定値
0
1
2
3
4
入力種別
測温抵抗体 仕様
Pt100
JPt100
–200〜1300(℃)
–20.0〜500.0(℃)
–100〜850(℃)
–20.0〜400.0(℃)
–200〜400(℃)
–199.9〜400.0(℃)
0〜600(℃)
–100〜850(℃)
–200〜400(℃)
–199.9〜400.0(℃)
–200〜1300(℃)
0〜1700(℃)
0〜1700(℃)
100〜1800(℃)
0〜90(℃)
0〜120(℃)
0〜165(℃)
0〜260(℃)
/–300〜2300(°F)
/0.0〜900.0(°F)
/–100〜1500(°F)
/0.0〜750.0(°F)
/–300〜700(°F)
/–199.9〜700.0(°F)
/0〜1100(°F)
/–100〜1500(°F)
/–300〜700(°F)
/–199.9〜700.0(°F)
/–300〜2300(°F)
/0〜3000(°F)
/0〜3000(°F)
/300〜3200(°F)
/0〜190(°F)
/0〜240(°F)
/0〜320(°F)
/0〜500(°F)
設定範囲設定値
0
1
2
3
4
17
5
6
7
18
8
9
10
11
12
13
14
15
16
入力種別
熱電対
非接触
温度センサ
形ES1B
アナログ入力
仕様
K
J
T
E
L
U
N
R
S
B
スケーリングにより–1999〜9999、
–199.9〜999.9の範囲で使用。
制御周期(制御出力2)
(単位:秒)
STX
ノード
No. SID FINS-mini
コマンドテキスト ETX
サブア
ドレス BCC
STX
ノードNo.
サブアドレス
SID
FINS-mini
コマ
ンドテキスト
ETX
BCC
通信フレーム(テキスト)の先頭を示すコード(H'02)です。
受信中に再びSTXを受信した場合は、STXを受信した所か
ら受信をやり直します。
通信ユニットNo.を指定します。00〜99を設定します。
「00」固定
サービスIDで「0」固定
読出値、書込値、ステータスなどコマンドに対応した内容
を格納します。
テキストの終了を示すコード(H'03)です。
ブロックチェックキャラクタ
FINS-miniで使用するエラーチェック方法です。
ノードNo.〜ETXまでの値を1バイトごとにXOR(排他的論
理和)した値
CompoWay/Fの場合
●コマンドフォーマット
コマンド
STX
STX
ノード
No. SID ETX
サブア
ドレス
バッファサ
イズ
形式
BCC
MRC
MRC
SRC
SRC
レスポンス
ノード
No. ETX
サブア
ドレス 終了
コード レスポンス
コード BCC
03
03
05
05
0
00
●本体属性の読み出し
212 11222 4 10 4
本機の内部の形式、通信バッファサイズを確認するときに使用し
ます。
10
11
12
13
14
00
0F
16
18
終了
コード 名称 内容
正常終了
コマンドエラー
パリティエラー
フレーミングエラー
オーバーラン
BCCエラー
フォーマットエラー
サブアドレスエラー
フレーム長エラー
実行できないコマンドを受信したとき
パリティが一致しなかったとき
ストップビットが検出されなかったとき
受信バッファがオーバーフローしたとき
BCCが一致しなかったとき
データの長さが正しくなかったとき
サブアドレスが不正
受信フレームが所定バイト数を超えたとき
●終了コード(CompoWay/Fの場合)
*2
*3
現在値/目標値
ラン/ストップ
制御開始の時
制御停止の時
警報値1*3
警報上限値1*3
警報下限値1*3
詳細な使用方法は別冊「形E5GNユーザー
ズマニュアル」を参照してください。
電源投入
入
力
タ
イ
プ
測
温
抵
抗
体
熱
電
対
入
力
タ
イ
プ
10〜70℃
60〜120℃
115〜165℃
140〜260℃
0〜50mV
(表示が点滅し制御
が停止します。)
運転が停止します。(制御・警報共に停止)
*5
*7
*7
*7 *7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*7
*2:入力種別と警報種別の
項目は、左の表を参照
してください
*4
・初期値は両入力タイプとも「0」です。
s-hc stnd
c-cp 20
h-c
stnd
c-sc 1. 00
c-db 0. 0
chys 1. 0
+ キー
1秒以上
入力が制御可能範囲内で表示可能範囲(–1999(–199.9)〜9999(999.9))を超えた
場合、–1999(–199.9)より小さい値は[[[[、9999(999.9)より大きい値は ]]]]
と表示します。
この表示のときは制御出力および警報出力ともに正常に動作します。
制御可能範囲についての詳細は「形E5GN ユーザーズマニュアル」を参照してくださ
い。
防水が必要な場合は、必ず
個別取り付けを行なってくだ
さい。本体に端子側から防
水パッキンを取り付けてから、
パネルに挿入してください。
厚さ1〜5m m の パネルに取
り付け可能です。
第1表示 異常内容
*6
*6
メモリ異常
入力異常
s.err(S.Err)
e111(E111)
処置
入力の誤配線、断線、短絡および入力種別を確認
してください。
入力異常を確認後、電源を入れ直してください。
表示内容が変わらない場合は修理が必要です。
正常になった場合はノイズの影響が考えられるので、
ノイズが発生していないか確認してください。
電源を入れ直してください。
表示内容が変わらない場合は修理が必要です。
正常になった場合はノイズの影響が考えられるので、
ノイズが発生していないか確認してください。
A/Dコンバータ
異常
異常時の状態
制御出力 警報
OFF
OFF
OFF
異常高温と
して処理
OFF
OFF
+0.3
0
+0.3
0
+1
0
+0.6
0
U
D
「AT実行」「at」が点滅
「AT中止」
ATが終了した場合も「off」になります。
JPN
正しい取扱いをしなければ、この危険のために、時
に軽傷・中程度の傷害をおったり、あるいは物的損
害を受ける恐れがあります。お使いになる前にこの
取扱説明書をお読みになり、十分にご理解ください。
注意
●警告表示の意味
安全上のご注意
●運転/調整プロテクト
工場出荷時の設定であれば、運転レベルと調整レベルの設定項目は全て
使用可能ですが、「運転/調整プロテクト」の設定を「1」にすると、
調整レベルの設定項目は表示されなくなります。
ただし、予め設定されている調整レベルの設定項目の内容は有効です。
工場出荷設定値「0」
◎:表示/設定変更可能
○:表示のみ可能
×:表示/設定変更不可能
現在値
目標値
その他
調整レベル
レベル 設定値
0
○
◎
◎
◎
1
○
◎
◎
×
2
○
◎
×
×
3
○
○
×
×
●設定変更プロテクト
キー操作での設定変更を制限します。
OFF「off」:キー操作での設定変更可能
ON「on」:キー操作での設定変更不可能
(ただしプロテクトレベルの設定は、すべて変更可能)
●初期/通信プロテクト
初期設定レベル、通信設定レベル、高機能設定レベルへの移行を制限します。
設定値
0
1
2
○
○
×
○
○
×
○
×
×
初期設定レベル 通信設定レベル
高機能設定レベル
工場出荷設定値「1」
運
転
レ
ベ
ル
○:移行可能
×:移行不可能
補正後
補正前
センサ入力
本機で扱う温度
温度入力補正値:(1.2℃)
501.2℃
500.0℃
201.2℃
200.0℃
-18.8℃
-20.0℃
-20.0℃ 200.0℃ 500.0℃
「ins」温度入力補正値の設定値分だけ、センサ
入力範囲のすべての点において入力温度を補正し
ます。補正前の現在値が200℃のとき、補正値を
1.2℃とすると補正後は201.2℃、補正値を-1.2℃
とすると補正後は198.8℃として扱います。
例)熱電対入力タイプ、入力種別設定:1、
温度単位設定:℃、温度入力補正値:1.2℃
*7
*7
●営業にご用の方も、技術お問い合わせの方も、フリ−コ−ルにお電話ください。
音声ガイダンスが流れますので、案内に従って操作ください。
フリ−コ−ル:0120-919-066
携帯電話・PHS等移動通信からのお電話は、お手数ですが、
TEL:055-982-5015(通話料がかかります)へおかけください。
【技術のお問い合わせ時間】
■営業時間:9:00〜12:00/13:00〜19:00
(土・日・祝祭日は9:00〜12:00/13:00〜17:00)
■営業日:年末年始を除く
上記フリ−コ−ル以外に、055-982-5000(通話料がかかります)
におかけいただくことにより、直接制御機器の技術窓口につながります。
【営業のお問い合わせ時間】
■営業時間:9:00〜12:00/13:00〜17:30(土・日・祝祭日は休業)
■営業日:土・日・祝祭日/春季・夏季・年末年始を除く
●FAXによるお問い合わせは下記をご利用ください。
テクニカルセンタ お客様相談室 FAX 055-982-5051
●インターネットによるお問い合わせは下記をご利用ください。
http://www.fa.omron.co.jp/support/
●FAQ(よくあるご質問)ホ−ムペ−ジをご用意しています。
http://www.dom.omron.co.jp/faq.nsf
●その他のお問い合わせ先
納期・価格・修理・サンプル・承認図は貴社のお取引先、または貴社の担当オムロン営
業員にご相談ください。
営業統轄事業部
東京都品川区大崎1-11-1 ゲートシティ大崎ウエストタワー14F(〒141-0032)
●警告表示
Other manuals for E5GN
7
Table of contents
Other Omron Temperature Controllers manuals

Omron
Omron E5C-T Series Use and care manual

Omron
Omron E5ZN Series User manual

Omron
Omron E5CD-B-800 Series User manual

Omron
Omron E5AJ-A2HB User manual

Omron
Omron E5*C-B Series User manual

Omron
Omron EJ1G User manual

Omron
Omron E5 C Series User manual

Omron
Omron E5CN-HT User manual

Omron
Omron E5AN-H User manual

Omron
Omron E5 N H - Parts list manual