Omron H5CX-A User manual

12345678
OFF
ON
12345678
OFF
ON
Step1
Step1
Step3
Step2
Step2
5) The input signal will not be accepted after 5 to 505 ms has elapsed from when the power supply is turned
OFF.
6) Inrush current generated by turning ON or OFF the power supply may deteriorate contacts on the power
supply circuit. Turn ON or OFF to a device with the rated current of more than 10 A.
7) Make sure that all settings are appropriate for the application. Unexpected operation resulting in property
damage or accidents may occur if the settings are not appropriate.
8) Do not leave the Timer for long periods of time at a high temperature with output current in the ON state.
Doing so may result in the premature deterioration of internal components (e.g., electrolytic capacitors).
9) EEPROM is used as memory when the power is interrupted. The write life of the EEPROM is 100,000
writes. The EEPROM is written when the power is turned OFF or when switching from function setting,
mode or Timer/Twin Timer selection mode to run mode.
10) Dispose of the product according to local ordinances as they apply.
11) Attach the front panel when using the Timer. The latches in the middle of each of four sides secure the
front panel to the main body. To remove the panel, widen the four latches and pull the panel toward you.
To mount the panel, fit all four latches correctly into the slots on the main body.
1) H5CX models with a 24-VAC/12 to 24-VDC power supply use a transformer-free power supply method in
which the power supply terminals are not isolated from the signal input terminals. If a non-isolating DC
power supply is used, unwanted current paths may occasionally burn or destroy internal components
depending on the wiring. Always check the wiring sufficiently before use.
2) An inrush current of approx. 10 A will flow for a short time when the power supply is turned ON. If the
capacity of the power supply is not sufficient, the Timer may not start. Be sure to use a power supply
with sufficient capacity.
3) Maintain voltage fluctuations in the power supply within the specified operating voltage range.
4) To allow for the startup time of peripheral devices (sensors, etc.), the Timer starts timing operation
between 200 to 250 ms after power is turned ON. For this reason, in operations where timing starts
from power ON, the time display will actually start from 249 ms. If the set value is 249 ms or less, the
time until output turns ON will be a fixed value between 200 and 250. The present value display will start
from 250 ms. (Normal operation is possible for set values of 250 ms or more.) In applications where a
set value of 249 ms or less is required, use start timing with signal input.
Display Parameter name Set value Comments
timr ---*1
timm ---
outm
otim
iflt 20ms,1ms *2
imod npn,pnp *2
colr
otmd 1c1c,2c *2
sl-h
kypt
on-a
on-c
on1a 0to 9999 ×1,000
---
---
×1,000
on2a 0to 9999 ×1,000
on1c
on2c
1234
2000 s
s
SET
---
---
---
oftr ---*1
ontr ---*1
timm up,down *2 ---
totm Only modes toff and ton can be
selected for H5CX-L8E@.
toff,ton,tof1,ton1
*2
iflt 20ms,1ms *2
imod npn,pnp *2
colr
otmd 1c1c,2c *2
sl1h ---
1
2
3
4
5
6
7
8
OFF ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Mounting and Panel-cutout Dimensions Diagram
Standard panel cutout is shown in the
following diagram (conforms to DIN
43700). A space of 15 mm or greater
(a panel cut-out distance of 60 mm or
greater) is recommended towards
the Adapter's hook side to enable
easier mounting work.
1. The thickness of a mounting panel
should be 1 to 5 mm.
2. It is possible to mount Timers side by
side by mounting Adapters. (But only
towards the non-hook side.)
Application as a Timer
•Turn ON pin 1 on the DIP switch (enabled).
•
•Display in RUN mode.
(except for Z mode)
Present value
Set value
DIP switch setting
Time range
Output mode
UP/DOWN mode
Input signal width
Disable Enable
0.001 s to 9.999 s
0.01 s to 99.99 s
0.1 s to 999.9 s
1 s to 9999 s
0 min 01 s to 99 min 59 s
0.1 min to 999.9 min
0 h 01 min to 99 h 59 min
0.1 h to 999.9 h
E Mode (Interval: Power recycle)
Key-protect switch
Basic settings can be done only with the DIP switch.
DIP switch settings are updated when the
power is turned ON. (Set the DIP switch
before installation and turning ON power.)
A Mode (Signal-ON delay (I):
Power recycle)
A-2 Mode (Power-ON delay (I):
Power recycle)
F Mode (
Cumulative
: Power retain)
First, switch to a Twin Timer •Display in RUN mode.
RUN mode.
Power ON
Timer
DIP switch monitor
Twin Timer
Press for 1 s.
OFF-time range
ON-time range
Output mode
UP/DOWN mode
Input signal width
DOWN
1 ms
Pin 2 Pin 3 OFF-time range
0.01 s to 99.99 s
0.1 s to 999.9 s
1 s to 9999 s
0 min 01 s to 99 min 59 s
Pin 4 Pin 5 ON-time range
0.01 s to 99.99 s
0.1 s to 999.9 s
1 s to 9999 s
0 min 01 s to 99 min 59 s
DIP switch setting
Item
Disable Enable
UP
20 ms
•Turn ON pin 1 on the DIP switch (enabled).
• DIP switch settings are updated when the power is turned ON.
(Set the DIP switch before installation and turning on power.)
Key-protect switch
Step3
Application as a Twin Timer
Change to "Twin Timer"
using the UKey.
Timer/Twin Timer
selection mode
Press for 1 s.
Present value
ON Set value
Present value
OFF Set value
Basic settings can be done only with the DIP switch.
Note: H5CX-L8@has no DIP switch, so go to .
Wire properly after checking the specifications of the power supply
voltage.
Do not connect unused terminals.
Key-protect Switch Settings
Self-diagnostic Functions
OFF (disable)
ON (enable)
* Changing mode to Timer/Twin Timer selection mode or function setting mode.
When the key-protect switch is ON,
individual key operations can be disabled
to prevent setting errors according to the
key protect levels (KP-1 to KP-7) shown
in the following table.
* Key protect levels are set in function
setting mode.
0.01 s to 99.99 s
(default setting)
0.1 s to 999.9 s
1 s to 9999 s
0 min 01 s to 99 min 59 s
0.001 s to 9.999 s
0.1 h to 999.9 h
1 h to 9999 h
0 h 01 min to 99 h 59 min
0.1 min to 999.9 min
1 min to 9999 min
The characters displayed in reverse video are the default settings.
When performing settings with operation keys only, set pin1 of the DIP switch to OFF (factory setting).
If pin 1 of the DIP switch is set to ON, the setting items indicated in will not be displayed.
OFF time range
ON time range
UP/DOWN mode
Twin Timer Output
mode
Input signal width
NPN/PNP input
Display color
Instantaneous/time-limit
Displayed only for the
H5CX-A@and H5CX-A11@.
Displayed only for models with
terminal blocks.
Displayed only for H5CX-L8E@.
red,grn,org,r-g,g-r,
r-o,o-r,g-o,o-g *2
red,grn,org,r-g,g-r,
r-o,o-r,g-o,o-g *2
Present value
ON duty
•Display in RUN mode. (Z mode)
Present value
Cycle time
Note: H5CX-L8@-N has no DIP switch, so go to Step2 .
Display Parameter name Set value Comments
Displayed only for models other than H5CX-L8E@.
Refer to the table
on the right.
Refer to the table
on the right.
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp, The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC (U.S.A.)
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD. (SINGAPORE)
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
OFF
• Default settings are all OFF.
Note: Refer to the datasheet (Cat. No. L111) for detailed parameter settings.
Note: Refer to the datasheet (Cat. No. L111) for detailed parameter settings.
Parameters that cannot be set with the DIP switch are set with the operation keys on the front
panel.
• Default settings are all OFF.
Refer to the table on the right.
Refer to the table on the right.
Repeat cycle-OFF start Repeat cycle-ON start
Indicates a potentially hazardous situation which, if not
avoided, is likely to result in minor or moderate injury or
in property damage.
Do not allow pieces of metal, wire clippings, or fine metallic
shavings or fillings from installation to enter the product. Doing so
may occasionally result in electric shock, fire, or malfunction.
Minor injury due to explosion may occasionally occur. Do not use
the Timer where subject to flammable or explosive gas.
Fire may occasionally occur. Tighten the terminal screws to the
rated torque
H5CX terminals: 6.55 to 7.97 lb-in (0.74 to 0.90 N⋅m)
P2CF socket terminals: 4.4 lb-in (0.5 N⋅m)
Minor injury due to electric shock may occasionally occur. Do not
touch any of the terminals while power is being supplied. Be sure
to mount the terminal cover after wiring.
The life expectancy of the output relay varies considerably
according to its usage. Use the output relay within its rated load
and electrical life expectancy. If the output relay is used beyond its
life expectancy, its contacts may become fused or there may be a
risk of fire. Also, be sure that the load current does not exceed the
rated load current and when using a heater, be sure to use a
thermal switch in the load circuit.
5) Do not use in the following locations:
•Locations subject to sudden or extreme changes in temperature.
•Locations where high humidity may result in condensation.
•Locations with excessive vibration or shock.
•Locations subject to water.
•Locations subject to oil.
6) Do not use this Timer in dusty environments, in locations where corrosive gasses are present, or in locations
subject to direct sunlight.
7) Install the Timer well away from any sources of static electricity, such as pipes transporting molding
materials, powders, or liquids.
8) Internal elements may be destroyed if a voltage outside the rated voltage range is applied.
9) Wire terminal polarity correctly.
10) Separate the Timer from sources of noise, such as devices with input signals from power lines carrying
noise, and wiring for I/O signals.
11) Do not connect more than two crimp terminals to the same terminal.
12) Up to two wires of the same size and type can be inserted into a single terminals.
13) Use the specified wires for wiring. Applicable Wires: AWG 18 to AWG 22, solid or twisted, copper
14) Install a switch or circuit breaker that allows the operator to immediately turn OFF the power, and label it
to clearly indicate its function.
15) When the Timer is operated with no-voltage input (NPN input), approximately 14 V is output from the
input terminals. Use a sensor that contains a diode.
16) Use a switch, relay, or other contact so that the rated power supply voltage will be reached within 0.1
seconds. If the power supply voltage is not reached quickly enough, the Timer may malfunction or outputs
may be unstable.
17) Use a switch, relay, or other contact to turn the power supply OFF instantaneously. Outputs may
malfunction and memory errors may occur if the power supply voltage is decreased gradually.
18) When changing the set value during a timing operation, the output will turn ON if the set value is changed
as follows because of the use of a constant read-in system:
Elapsed time (UP) mode: Present value ≥Set value
Remaining time (DOWN) mode: Elapsed time ≥Set value (The present value is set to 0.)
When in the remaining time mode, the amount the set value is changed is added to or subtracted from the
present value. When the set value is 0, the output turns ON the moment the signal is input. The reset
operation turns OFF the output.
19) Do not use organic solvents (such as paint thinners or benzine), strong alkali, or strong acids. They will
damage the external finish.
20) Confirm that indications are working normally, including the backlight LED, and LCD. The indicator LEDs,
LCD, and resin parts may deteriorate more quickly depending on the application environment, preventing
normal indications. Periodic inspection and replacement are required.
21) The waterproof packing may deteriorate, shrink, or harden depending on the application environment.
Periodic inspection and replacement are required.
1) When mounting the Timer to a panel, tighten the two mounting screws alternately, a little at a time, so as to
keep them at an equal tightness. If the panel screws are tightened unequally, water may enter the panel.
2) Store the Timer at the specified temperature. If the Timer has been stored at a temperature of less than
−10°C, allow the Timer to stand at room temperature for at least 3 hours before use.
3) Mounting the Timer side-by-side may reduce the life expectancies of internal components.
4) Use the Timer within the specified ranges for the ambient operating temperature and humidity.
58
@45 +0.6
−0
A
A=(48n−2.5) +1
−0
Power supply voltage 100 to 240 VAC, 50/60 Hz (Other than H5CX-@D)
12 to 24 VDC/24 VAC, 50/60 Hz (H5CX-@D)
Allowable voltage fluctuation range
85% to 110% of rated supply voltage (12 to 24 VDC: 90% to 110%)
Power consumption Approx. 6.2 VA at 100 to 240 VAC,
Approx. 5.1 VA/2.4 W at 24 VAC/12 to 24 VDC
Operating temperature range −10 to 55°C (−10 to 50°C if Timers are mounted side by
side) (with no icing or condensation)
Storage temperature range −25 to 70°C (with no icing or condensation)
Operating humidity range 25% to 85%
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Weight Approx. 115 g (main unit only)
Installation environment Over-voltage category III, pollution degree 2 (IEC 61812-1)
Input method
No-voltage Input
ON impedance: 1 kΩmax. (Leakage current: 12 mA when 0 Ω)
ON residual voltage: 3 V max.
OFF impedance: 100 kΩmin.
Voltage Input High (logic) level: 4.5 to 30 VDC
Low (logic) level: 0 to 2 VDC (Input resistance: approx. 4.7 kΩ)
No-voltage (NPN) input/voltage (PNP) input (switchable)
Control output
Contact output 250 V AC, 5A (resistive load)
30 V DC, 5A (resistive load)
Solid state output Open collector, 30 VDC max.,100 mA max.
Residual voltage: 1.5 VDC max.
(Effective value: Approx. 1 VDC)
Leakage current: 0.1 mA max.
Electrical life of relay 100,000 operations (at an ambient temperature of 23°C)
Mechanical life of relay 10,000,000 operations (at an ambient temperature of 23°C)
Degree of protection IEC IP66, UL508 Type 4X*
MODE
MODE
●Set the parameters using the UD Keys.
MODE
MODE
●Set the parameters using theNUD Keys.
---.-s
---- s
--:-- ms
---.-m
---- m
--:-- hm
---.-h
---- h
-.--- s
*1 The set values for the time range are as follows:
MODEMODE
12.34
12.34
18.50
SET1
SET2
S
S
S
10
1
2
3
4
5
6
7
8
Item OFF ON
UP
20 ms
DOWN
1 ms
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
*1 The set values for the time range are the same as for Timer operation.
*2 After reaching the last set value, the UD Keys will return to the first set value.
12.34
10.00
MODEMODE
s
s
12.34
18.50 s
s
SET1
SET2
MODE +
MODE +
tim twn
func
tim
dip
1off
MODE
U1
U1
Key protect indicator
Level
KP-1 (default setting)
KP-2
KP-3
KP-4
KP-5
KP-6
KP-7
Mode change*
Invalid
Invalid
Invalid
Invalid
Invalid
Invalid
Invalid
Display switch in the run mode
Valid
Valid
Valid
Valid
Invalid
Invalid
Invalid
Reset Key
Valid
Invalid
Valid
Invalid
Invalid
Valid
Invalid
Up/Down Key
Valid
Valid
Invalid
Invalid
Invalid
Valid
Valid
6789
0V
12345
6789
0V
12345
67
8
9
10
11
1
2
3
4
5
(+)(−)
0V
67
8
9
10
11
1
2
3
4
5
0V
4
3
2
1 8
7
6
5
0V
4
3
2
1 8
7
6
5
0V
4
3
2
1 8
7
6
5
H5CX-A-N/-AD-N H5CX-AS-N/-ASD-N
H5CX-A11-N/-A11D-N H5CX-A11S-N/-A11SD-N
H5CX-L8-N/-L8D-N
H5CX-L8E-N/-L8ED-N
H5CX-L8S-N/-L8SD-N
1
3
2
8
9
5
4
6
7
10
11
up,down *2
hold/0.01 to 99.99
0to 9999
1to 9999
1to 9999
H5CX-A@-N/-L@-N
Digital Timer
©All Rights Reserved
OMRON Corporation
INSTRUCTION MANUAL
1148541-8B
EN CAUTION
Suitability for Use
Keys to Warning Symbols
SAFETY PRECAUTIONS
CAUTION
Precautions for Safe Use
Precautions for Correct Use
60 or greater
15 or greater
•Panel-cutout Dimensions Diagram
(Units: mm)
n Units mounted
side-by-side
3. If the Timers are mounted side by side,
water resistance will be lost.
• Digital Timer
• Instruction manual (this document)
• DIP switch label (Except for H5CX-L8@)
Package Contents
• Mounting Adapter, Waterproof Packing,
Terminal Cover (except for H5CX-A11@
and H5CX-L8@)
Ratings (Specifications)
Conformance to EN/IEC Standards
•
•
*Individual mounting: Degree of protection on the front panel of the Timer conforms to UL 508
Type 4X when all of the following conditions are satisfied:
The Y92S-29 waterproof packing and Y92F-30 mounting adapter are used with the Timer.
Use only these parts for replacement.
The Timer is mounted on the flat surface of an enclosure that is rated and marked "Type
4X for Indoor Use Only."
Pin 5 Pin 6 Output mode
Pin 2 Pin 3 Pin 4 Time range
(setting when
purchased.)
Power ON
●Change from RUN Mode to Function Setting Mode.
The characters displayed in reverse video are the default settings.
When performing settings with operation keys only, set pin 1 of the DIP switch to OFF (factory setting).
If pin 1 of the DIP switch is set to ON, the setting items indicated in will not be displayed.
RUN mode Function
setting mode
3 s min.
3 s min.
Function setting mode
Time range
UP/DOWN mode
Output mode
Output time
Input signal width
NPN/PNP input
Display color
Instantaneous/
time-limit
Only modes a-2,b,e, and zcan be
selected for H5CX-L8E@.
Display Set value
(If the output time is set to 0.00, hold
is displayed.)
Displayed for modes a,a-1,a-2,
a-3,b,b-1 and sonly. Unit: second
Only displayed for the H5CX-A@and
H5CX-A11@.
Displayed only for models with
terminal blocks.
Displayed only for the H5CX-L8E@.
• Models Other Than H5CX-L8E@
• H5CX-L8E@
Set value upper limit
Key protect level
Output ON count
alarm set value
The monitor value is only displayed.
It cannot be set. ×1,000
Instantaneous output 1 (OUT1)
ON count alarm set value
Time-limit
output 2 (OUT2) ON
count alarm set value
Instantaneous output 1 (OUT1)
ON count monitor value
Time-limit
output 2 (OUT2) ON
count monitor value
Output ON count
monitor value
●Change from RUN Mode to Function Setting Mode.
Power ON
RUN mode Function
setting mode
3 s min.
3 s min.
Function setting mode
Set value upper limit 1
OMRON shall not be responsible for conformity with any standards, codes, or
regulations that apply to the combination of the products in the customer's
application or use of the product.
Take all necessary steps to determine the suitability of the product for the systems,
machines, and equipment with which it will be used. Know and observe all
prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS
RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A
WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE
OMRON PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE
INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
See also Product catalog for Warranty and Limitation of Liability.
48
a,a-1,a-2,a-3,b,
b-1,d,e,f,z,s *2
kp-1,kp-2,kp-3,kp-4,
kp-5,kp-6,kp-7 *2
Contact output
Reset
Signal
Gate Internal circuit
Solid state output
*
Unused
Terminals 1 and 6 of the
H5CX-AD-N are
connected internally.
Terminals 2 and 3 of the H5CX-A11D-N
are connected internally.
Terminals 2 and 3 of the H5CX-A11SD-N
are connected internally.
Time-limit contact
output OUT2
Instantaneous
contact output
OUT1
Terminals 1 and 2 of the H5CX-L8D-N
are connected internally.
Terminals 1 and 2 of the H5CX-L8SD-N
are connected internally.
Internal circuit
Solid state output
*
Reset
Signal
Gate
Unused
Unused
(+)
(−)(+)
(−)
Reset
Signal
Gate
Terminals 1 and 6 of the
H5CX-ASD-N are
connected internally.
Unused
(+)(−)
Reset
Signal
Gate
Contact output
Signal
Reset
Solid state output
*
Internal circuit
Unused
(+)(−)
(+)(−)
Contact output
Internal circuit
Signal
Reset
(+)(−)
Internal circuit
Internal circuit
Display Section
1. Key Protect Indicator (orange)
2. Control Output Indicator (orange)
3. Reset Indicator (orange)
4. Present Value Display (Main Display)
(Character height: 12 mm, red*)
*Characters on models with terminal
blocks can be switched between red,
green, and orange.
5. Time Unit Indicators (If the time range
is 0 min, 0.0 min, 0 h, 0.0 h, or 0 h 0
min, these indicators flash to indicate
timing operation.)
6. Set Value Display (Sub-display)
(Character height: 6 mm, green)
7. Set Value 1, 2 Indicator
Operation Key
8. Mode Key (Changes modes and setting items)
9. Reset Key (Resets present value and output)
10. Up Keys 1 to 4
11. Down Keys 1 to 4
The following displays will appear if an error occurs.
Main
display Sub-display Error Output
status Correction method Set value after
reset
e1 Not lit CPU error No change
e2 Not lit Memory error (RAM) No change
e2 sum Memory error (EEPROM)*1 OFF Factory setting
e3*2 No change Output ON count alarm
set value exceeded
No
change
Either press the Reset Key
or reset the power supply.
Reset the power supply.
The monitor value is only displayed.
It cannot be set. ×1,000
The monitor value is only displayed.
It cannot be set. ×1,000
kypt ---
on-a 0to 9999 ×1,000
on-c ---
on1a 0to 9999 ×1,000
on2a 0to 9999 ×1,000
on1c ---
on2c ---
The monitor value is only displayed.
It cannot be set. ×1,000
The monitor value is only displayed.
It cannot be set. ×1,000
• Models other than H5CX-L8E@
• H5CX-L8E@
Key protect level
Output ON count
alarm set value
Output ON count
monitor value
Instantaneous output 1 (OUT1)
ON count alarm set value
Time-limit output 2 (OUT2) ON
count alarm set value
Instantaneous output 1 (OUT1)
ON count monitor value
Time-limit output 2 (OUT2) ON
count monitor value
kp-1,kp-2,kp-3,kp-4,
kp-5,kp-6,kp-7 *2
The monitor value is only displayed.
It cannot be set. ×1,000
sl2h ---1to 9999
Set value upper limit 2
For details, refer to the latest datasheet (Cat. No. L111).
Thank you for purchasing the OMRON Product.
To ensure the safe application of the Product, read this
manual carefully before using the Product and always keep
it close at hand when the Product is in use.
*2 After reaching the last set value, the UD Keys will return
to the first set value.
No change
Reset Key
Reset Key
Power for load
+
Load
Power for load
+
Load
NPN Output PNP Output
Power for load
+
Timer
Inductive
load
*1 This includes times when the life of the EEPROM has expired.
*2 The normal display and e3 will appear alternately.
When the Reset Key is pressed, e3 will no longer be displayed even if the alarm set value is exceeded.
(Monitoring is possible, however, because the counter will continue without clearing the output ON count.)
Displayed only for models other than H5CX-L8E@.
Minor electric shock, fire, or malfunction may occasionally occur.
Do not disassemble, modify, or repair the Timer or touch internal
components.
When conforming to EMC standards, refer to the information provided in this Instruction Manual for cable
selection and other conditions.
This is a class A product. In residential areas it may cause radio interference, in which case the user may be
required to take adequate measures to reduce interference.
Basic insulation is provided between the power supply and input terminals. (No insulation is provided between
the power supply and input terminals for the H5CX-@D-N.)
Basic insulation is provided between power supply and output terminals, and between input and output
terminals. When double insulation or reinforced insulation is required, apply double insulation or reinforced
insulation as defined in IEC 60664 that is suitable for the maximum operating voltage with clearances or solid
insulation.
•Installation in a Panel
H5CX is normally installed on a flat surface in an operation panel. Use a Type 1 Enclosure for the operation
panel.
•Use an isolated source for power input for the H5CX-@D.
Use the isolated source for Inputs and for Solid State Output.
•Environment
Surrounding Air Temperature: −10 to 40°C
•Power supply: The inputs are non-isolated. (Applicable to H5CX-@D only)
The same power supply as the main power source should be used for that for input.
•Accessories (Order Separately)
Track Mounting/Front Connecting Socket
Flush Mounting Adapter
Waterproof Packing
Front Panel (4 digits)
11-pin
11-pin, finger-safe type
8-pin
8-pin, finger-safe type
---
---
Light gray (Munsell 5Y7/1)
White
Black
P2CF-11
P2CF-11-E
P2CF-08
P2CF-08-E
Y92F-30
Y92S-29
Y92P-CXT4G
Y92P-CXT4S
Y92P-CXT4B
Precautions for Compliance with UL Standards and CSA Standards
Notice to Users of the H5CX in the USA and Canada
Please use the following installation information instead of the general information in the instruction manuals in
order to use the product under certified conditions of UL and CSA when the product is installed in the USA or
Canada. These conditions are required by NFPA 70, National Electrical Code in the USA and the Canadian
Electrical Code, Part I in Canada and may vary from information given in the product manuals or safety
precautions.
(51)
103.2*
H5CX
-A11@-N
H5CX
-L8@-N
92.3*
Y92S-29 (provided)
Waterproof Packing
Y92S-29 (provided)
Waterproof Packing
Panel
Y92F-30
(provided)
Flush Mounting Adapter
Y92F-30 (provided)
Flush Mounting
Adapter Panel
Panel
Y92S-29 (order separately)
Waterproof Packing
Y92F-30 (order separately)
Flush Mounting
Adapter P3GA-11 (order separately)
Back-connecting Socket
*These dimensions vary with the
type of DIN track (reference value).
P2CF-11(-E) Front-connecting
sockets (order separately)
P2CF-08(-E) Front-connecting
sockets (order separately)
(51)
(51)
Panel
Y92S-29 (order separately)
Waterproof Packing
Y92F-30 (order
separately)
Flush Mounting
Adapter
P3G-08 (order separately)
Back-connecting Socket
(51)
Mounting Dimensions (Units: mm)
Flush Mounting
Front panel dimensions are the
same.
Surface Mounting
48
48
89.97.5
H5CX-A11@-N
76.57.5
H5CX-A-N/-AS-N
57.57.5
H5CX-AD-N/-ASD-N
H5CX-L8@-N
84.87.5
100.9
90
Nomenclature
Terminal Arrangement
OFF
Parameters that cannot be set with the DIP switch are set with the operation keys on the front
panel.
Input Connections
No-voltage Inputs (NPN Inputs)
Voltage Inputs (PNP Inputs)
Open Collector Voltage Output Contact Input
Note: Operate with transistor ON Note: Operate with transistor ON Note: Operate with relay ON
0 V
Reset
Signal
Gate
PLC or
sensor Sensor
0 V
Reset
Signal
Gate
0 V
Reset
Signal
Gate
No-contact Input
(NPN Transistor)
Contact Input
No-contact Input
(PNP Transistor)
Sensor Sensor
0 V
Reset
Signal
Gate
0 V
Reset
Signal
Gate
0 V
Reset
Signal
Gate
Note: Operate with transistor OFF Note: Operate with transistor ON Note: Operate with relay ON
*
With Inductive Load
--.-- s
12345678
OFF
ON
12345678
OFF
ON
Step1
Step1
Step2
Step3
Step3
Step2
Step2
48
48
89.97.5
パネル 形Y92F-30(別売)
埋込み取付用アダプタ
形Y92S-29(別売)
防水パッキン
(51)
形P3GA-11(別売)
裏面接続ソケット
形H5CX-A11□-N
76.57.5
パネル 形Y92F-30(付属)
埋込み取付用アダプタ
形Y92S-29(付属)
防水パッキン
(51)
形H5CX-A-N/-AS-N
57.57.5
パネル 形Y92F-30(付属)
埋込み取付用アダプタ
形Y92S-29(付属)
防水パッキン
(51)
形H5CX-AD-N/-ASD-N
形H5CX-L8□-N
84.87.5
パネル 形Y92F-30(別売)
埋込み取付用アダプタ
形Y92S-29(別売)
防水パッキン
(51)
形P3G-08(別売)
裏面接続ソケット
*DINレールの種類により異な
ります。(参考値)
103.2 100.9
形H5CX
-A11□-N
形P2CF-11(-E)(別売)
表面接続ソケット
*
形H5CX
-L8□-N
形P2CF-08(-E)(別売)
表面接続ソケット
92.3 90
*
画面 パラメータ名 設定値 特記事項
timr −※1時間レンジ
timm UP/DOWNモード −
outm 出力モード
e,f,z,s※2
otim 出力時間
iflt 入力信号時間 20ms,1ms ※2
imod NPN/PNP入力モー
ド切替
npn,pnp ※2 形H5CX-A□、形H5CX-A11□
の時のみ表示
colr 表示色切替 red,grn,org,r-g,g-r,
r-o,o-r,g-o,o-g ※2
端子台タイプの時のみ表示
otmd 瞬時/限時切替 1c1c,2c ※2
sl-h
kypt キープロテクトレベ
ルkp-5,kp-6,kp-7 ※2
●形H5CX-L8E□以外の場合
on-a 出力ON回数警報設
定値
on-c 出力ON回数モニタ
値
●形H5CX-L8E□の場合
on1a 瞬時出力(OUT1)
ON 回数警報設定値
0〜9999 ×1000
−
−
×1000
on2a 限時出力(OUT2)
ON 回数警報設定値
0〜9999 ×1000
on1c 瞬時出力(OUT1)
ON 回数モニタ値
モニタ値の表示のみ。設定では
ありません。×1000
on2c 限時出力(OUT2)
ON 回数モニタ値
モニタ値の表示のみ。設定では
ありません。×1000
計時値
セット時間
1234
2000 s
s
SET
ー
ー
ー
画面 パラメータ名 設定値 特記事項
oftr −※1ジンレ間時FFO
ontr −※1ジンレ間時NO
timm UP/DOWN モード up,down ※2 −
totm ツインタイマ出力モ
ード
toff,ton,tof1,ton1
※2
iflt 入力信号時間 20ms,1ms ※2
imod NPN/PNP 入力モー
ド切替
npn,pnp ※2
colr 表示色切替 red,grn,org,r-g,g-r,
r-o,o-r,g-o,o-g ※2
otmd 瞬時/限時切替 1c1c,2c ※2
−
−
kypt キープロテクトレベ
ル kp-5,kp-6,kp-7 ※2
−
on-a 出力 ON 回数警報設
定値
0〜9999 ×1000
on-c −出力ON回数モニタ
値
on1a 瞬時出力(OUT1)
ON 回数警報設定値
0〜9999 ×1000
on2a 限時出力(OUT2)
ON 回数警報設定値
0〜9999 ×1000
on1c 瞬時出力(OUT1)
ON 回数モニタ値
−
on2c 限時出力(OUT2)
ON 回数モニタ値
−
1
2
3
4
5
6
7
8
項目 OFF
ディップスイッチ設定
OFF時間レンジ
ON時間レンジ
出力モード
UP/DOWNモード
入力信号時間
ON
無効 有効
右記参照
右記参照
フリッカOFFスタート
UP
20ms
フリッカONスタート
DOWN
1ms
スイッチ 2 スイッチ 3 OFF時間レンジ
OFF
ON
OFF
ON
OFF
OFF
ON
ON
0.01s〜99.99s
0.1s〜999.9s
1s〜9999s
0min01s〜99min59s
スイッチ 4 スイッチ 5 ON時間レンジ
OFF
ON
OFF
ON
OFF
OFF
ON
ON
0.01s〜99.99s
0.1s〜999.9s
1s〜9999s
0min01s〜99min59s
負荷用電源
+
タイマ
誘導負荷
負荷用電源
+
負荷
負荷用電源
+
負荷
※接点ONで動作
0V
ゲート
シグナ ル
リセッ ト
※トランジスタONで動作
0V
センサなど
ゲート
シグナ ル
リセッ ト
※トランジスタONで動 作
0V
ゲート
シグナ ル
リセッ ト
PLC、
センサなど
ゲート
シグナ ル
リセッ ト
※トランジスタOFFで動作
0V
センサなど
ゲート
シグナ ル
リセッ ト
※接点ONで動作
0V
ゲート
シグナ ル
リセッ ト
※トランジスタONで動作
0V
センサなど
形H5CX-A□-N/-L□-N
デジタルタイマ
取扱説明書
オムロン製品をお買い上げいただきありがとうござ います 。
この製品を安全に正しく使用していただくために、お使いになる
前にこの取扱説明書をお読みになり、十分にご理解ください 。
お読みになったあとも、いつも手元に置いてご使用ください 。
©All Rights Reserved
詳細は、最新版のカタログ(SGTA-028)を参照してください 。
正しい 取 扱 いをしなければ 、この危 険のために、
時に軽傷・中程度の傷害をおったり、あるいは
物的損害を受ける恐れがあります 。
安全上のご注意 使用上の注意
●警告表示の意味
注意
注意
注意
注意
軽度の感電、発火、機器の故障が稀に起こる恐れがあ
ります 。製品の中に金属、導線または、取り付け加工中
の切粉などが入らないようにしてください 。
爆発により稀に軽度の傷害の恐れがあります 。引火性、
爆発性ガスのある所では使用しないでください 。
発火が稀に起こる恐れがあります 。端子ネジは下記の規
定トルクで締めてください 。
H5CX本体端子:6.55 〜7.97 Lb-In(0.74 〜0.90 N・m)
P2CFソケット 端 子 : 4.4 Lb-In(0.5 N・m)
感電により軽度の傷害が稀に起こる恐れがあります 。通
電中は端子に触らないでください 。また 、配線後、必ず端
子カバーを取り付けてください 。
出力リレーの 寿 命は、開閉容量、開閉条件により大きく異
なるので必ず実使用条件を考慮し、定格負荷、電気的寿
命回数内でご使用ください 。寿命を超えた状態で使用する
と接点溶着や焼損の恐れがあります 。また 、負荷電流は必
ず定格以下でご使用いただき、ヒータ等を使 用する場 合
は、必ず負荷回路にサーモ・スイッチをご 使 用ください 。
軽度の感電、発火、機器の故障が稀に起こる恐れがあり
ます 。分解、改造、修理したり、内部に触らないでください 。
ご使用に際してのご承諾事項
ご使用に際してのご承諾事項
下記用途に使用される場合、当社営業担当者までご相談のうえ仕様書などによりご
確認いただくとともに、定格・性能に対し余裕を持った使い方や、万一故障があっても
危険を最小にする安全回路などの安全対策を講じてください 。
a) 屋外の用途、潜在的な化学的汚染あるいは電気的妨害を被る用途またはカタロ
グ、取扱説明書等に記載のない条件や環境での使用
b) 原子力制御設備、焼却設備、鉄道・航空・車両設備、医用機械、娯楽機械、安全
装置、および行政機関や個別業界の規制に従う設備
c) 人命や財産に危険が及びうるシ ステ ム・機械・装置
d)
ガス、水道、電気の供給システムや24 時間連続運転システムなど高い信頼性が必
要な設備
e)その 他 、上記 a)〜d)に準ずる、高度な安全性が必要とされる用 途
*上記は適合用途の条件の一部です。当社のベスト、総合カタログ、データシート等
最新版のカタログ、マニュアルに記載の保証・免責事項の内容をよく読 ん でご 使
用ください 。
安全上の要点
1)パネルへの取り付けの際は 2ヵ所 の ねじを交 互にバランスを取りながらしっかり締 めてくださ
い。バランスがとれていない場合 、パネルの内 部に水が浸 入する可能性があります 。
2)保存は、記載された定格範囲内としてください 。また 、−10℃以下で保存後、使用する場合は、
常温に 3時間以上放置してから通電してください 。
3)密着取り付けをすると内部部品の寿命が短くなる恐 れがあります 。
4)使用周囲温度や使用周囲湿度については、記載された定格範囲内でご使用ください 。
5)下記環境下での使用は避けてください 。
・温度変化の激しいところ。
・湿度が高く結露が生じる恐れのあるところ
・振動、衝撃の影響が大きいところ
・水がかかるところ
・被油のあるところ
6)
粉塵の多い場所、腐食ガスの発生する場所、直射日光の当たる場所での使用は避けてください 。
7)多量の静電気が発生する環境(成形材料、粉、流体材料をパイプ搬送する場合など)でご 使
用の場合は静電気発生源を製品本体より離してください 。
8)定格以外の電圧を印加しますと、内部素子が破壊する恐れがあります 。
9)端子の極性は、誤配線のないようにしてください 。
10)ノイズ発生源、ノイズがのった強電線から入力信号源の機器、入力信号線の配線、および 製
品本体を離してください 。
11)圧着端子を使用する場合は 1つの端子に 2個までとしてください 。
12)
配線は1端子あたり2本までは締め付けられますが、その 場 合 、2本は同じ線種で使用してください 。
13)配線に使用する適用電線は記載された適切なものを使用してください 。
適用電線 AWG18 〜22 単線またはより線 銅
14)
作業者がすぐ電源を OFFできるよう、スイッチまたはサーキットブレーカを設置し、適切に表示してくださ
い。
15)無電圧入力(NPN 入力)で使用される場合、入力端子より約 14Vが出力されます。ダイオー
ドの入ったセンサをご使用ください 。
16)電源電圧は 0.1 秒以内に定格電圧に達するようにスイッチ 、リレーなどの接 点を介して 一 気
に印加してください 。徐々に電圧を印加しますと、電源リセットしなかったり出力の 誤 動 作が 発
生することがあります 。
17)電源遮断時はスイッチ 、リレーなどの 接 点を介して一 気 に行ってください 。徐々に電圧を低下さ
せますと、出力の誤動作やメモリ異常が発生することがあります 。
18)“常時読込方式”を採 用しており、計時中に次のような設定値変更をしますと出 力 が ONしま
すのでご注意ください 。
“入力モード : UP”の場合 計時値≧設定値
“入力モード : DOWN”の場合 経過時間≧設定値(計時値=0となります )
DOWN モードの場 合、設定値を変更した量は計時値に加算/減算されます。設定値 =0 で
の動作は、シグナ ル入 力された 時 点で 出 力が O Nします 。リセット操 作により出力は O FFします。
19)本体の外装は有機溶剤(シンナー・ベンジンなど)強アルカリ性、強酸物質に侵されますので
使用しないでください 。
20)表示(バックライトLED、LCD)が正常に動作していることをご 確 認ください 。ご使用環境によ
っては、LED、LCD、樹脂部品の劣化を早め、表示不良になることがあります ので 、定期的な
点 検 および交 換をお 願いします。
21)防水パッキンはご使用環境によっては、劣化・収縮および硬化するため定期的な点検およ
び交換をお願いします。
●パネル加工寸法図(単位:mm)
標準パネルカットは下図のとおりです。
(DIN43700 準拠)
アダプタのフック側方向への取付間隔は、
作業性を考慮すると15mm 以上(パネル
カット間隔 60mm 以上)あけることを推 奨し
ます 。
58
48
15以上
60以上
□45+0.6
ー0
注1. 取付パネルの板厚は1〜5mmが適
当です。
注2. アダプタの取付により密着取付が
可能です。(ただしフックのない方向
のみ)
注3. 密着取り付け時は、耐水性が失われ
ます 。
n個密着取付
A
A=(48n−2.5)
+1
ー0
梱包内容
●製品本体
●取扱説明書(本紙)
●ディップスイッチ 用 ラ ベ ル
(形H5CX-L8□以外)
●取付アダプタ、防水パッキン、
端子カバー(形H5CX-A11□、L8□以
外)
取付およびパネル加工寸法図
●取付寸法図(単位:mm)
フロント部分の寸法は共通です。
〈埋込取付〉
〈表面取付〉
EMCに適合するための、ケーブル選定・その他の条件については、本取扱説明書の記載
内容を参照してください 。
この商品は「classA」
(
工業環境商品
)
です。住宅環境でご利用されると、電波妨害の原因
となる可能性があります 。その場合には電波妨害に対する適切な対策が必要となります 。
電源−入力端子間は基礎絶縁です。(形H5CX-□D-Nは電源−入力端子間は非絶縁です。)
電源−出力、入力−出力端子間は基礎絶縁です。
二重絶縁または強化絶縁が必要な場合、空間距離や固体絶縁などにより最高使用電圧に
適した 、IEC60664にて定義されている二重絶縁または強化絶縁を施してください 。
EN/IEC規格対応について
電源電圧 ・AC100 〜 240V50/60Hz
 ・AC24V50/60Hz / DC12 〜 24V
許容電圧変動範囲 定格電源電圧の85 〜 110%(DC12 〜 24Vは90 〜 110%)
消費電力 約6.2VA(AC100 〜 240V)、
 約5.1VA/2.4W(AC24V/DC12 〜 24V)
使用温度範囲 −10 〜+55℃(密着取付時:−10 〜+50℃)
(ただし、氷結、結露しないこと)
保存温度範囲 −25 〜+70℃(ただし、氷結、結露しないこと)
使用周囲湿度 25 〜 85%
高度 2,000m以下
推奨ヒューズ T2A、AC250V、タイムラグヒューズ 、低遮断容量
質量 約115g(本体のみ)
設置環境 過電圧カテゴリⅢ、汚染度2(IEC61812-1による)
入力方式
 無電圧入力 短絡時インピーダンス:1kΩ以下(0Ω時流出電流12mA)、短絡時
 残留電圧:3V以下、開放時インピーダンス:100kΩ以上
 電圧入力
Hレベル:DC4.5〜30V、Lレベル:DC0 〜 2V(入力抵抗約4.7kΩ)
 無電圧(NPN)入力/電圧(PNP)入力(切替)
制御出力
 リレー出力 AC250V5A(抵抗負荷)
 DC30V5A(抵抗負荷)
 トランジスタ出力 オープンコレクタ DC30Vmax、100mAmax
 残留電圧 DC1.5V以下
  (実力約DC1V)
 漏洩電流 0.1mA以下
リレーの電気的寿命 10万回(周囲温度条件:23℃)
リレーの機械的寿命 1000万回(周囲温度条件:23℃)
保護構造 IEC規格IP66、UL508Type4X*
*単品取付け:フロント部の保 護構 造は、以下の条件が全て満たされた場合に、UL508
Type4Xに適合します。
・防水パッキン形Y92S-29と取付けアダプタ形Y92F-30をタイマと共に使用する。取り
替え時も、これらの 部 品を使 用する。
・タイマは、Type4XforIndoorUseOnlyの認定の表示がある制御ボックスの 平 面
に取り付ける。
定格(仕様)
ディップスイッチで設定できない機能を、前面キーにて設定します。
●運転モードを機能設定モードに切り替えます。
電源投入 機能設定モード
運転モード
3 秒以上
3 秒以上
MODE
MODE
●各パラメータを UD キーで設定します。
反転文字は工場出荷時の設定です。
前面キーのみで設定する場合はディップスイッチ 1 を「OFF」[ 出荷時設定 ] にしてください。
ディップスイッチ 1 が「ON」(有効)の場合は、の設定項目は表示されません。ディップスイッチで設定できない機能を、前面キーにて設定します。
●運転モードを機能設定モードに切り替えます。
電源投入 機能設定モード
運転モード
3 秒以上
3 秒以上
MODE
MODE
●各パラメータを UD キーで設定します。
反転文字は工場出荷時の設定です。
前面キーのみで設定する場合はディップスイッチ 1 を「OFF」[ 出荷時設定 ] にしてください。
ディップスイッチ 1 が「ON」(有効)の場合は、の設定項目は表示されません。
表示 時間レンジ
--.-- s0.01s〜99.99s(初期値)
---.- s0.1s〜999.9s
---- s1s〜9999s
--:-- ms 0min01s〜99min59s
---.- m0.1min〜999.9min
---- m1min〜9999min
--:-- hm 0h01min〜99h59min
---.- h0.1h〜999.9h
---- h1h〜9999h
-.--- s0.001s〜9.999s
※1:時間レンジの設定値は以下のとおりです。
※2:設定値が最後尾に来たとき、UDキーで再び先頭に戻ります。
●運転モードでの 表 示(Zモード)
計時値
ON デューティー比率
計時値
周期時間
MODEMODE
12.34
12.34
18.50
SET1
SET2
S
S
S
10
キープロテクトスイッチ
基本的な設定はディップスイッチだけで行えます。
(注)形H5CX-L8□-Nはディップスイッチがありませんので、
 へ進んでください。
タイマとしてご 使 用される場 合 ツインタイマとしてご 使 用される場 合
キープロテクトスイッチ の 設 定
端子配置
自己診断機能
●運転モードでの 表 示(Zモード以外) ●運転モードでの 表 示
●出荷時はすべてOFFに設定しています。
1
2
3
4
5
6
7
8
項目 OFF
ディップスイッチ設定
時 間レンジ
出力モード
UP/DOWNモード 
入力信号時間
ON
無効 有効
右記参照
右記参照
UP
20ms
DOWN
1ms
スイッチ 2 スイッチ 3 スイッチ 4 時 間レンジ
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
0.001s〜9.999s
0.01s〜99.99s
0.1s〜999.9s
1s〜9999s
0min01s〜99min59s
0.1min〜999.9min
0h01min〜99h59min
0.1h〜999.9h
スイッチ 5 スイッチ 6 出力モード
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Aモード(シグナルオンディレー( )
:電源リセット動作)
A-2モード(パワーオンディレー( )
:電源リセット動作)
Eモード(インターバ ル:電源リセット動作)
Fモード(積算:電源保持動作)
●ディップスイッチの設定は電源投入時に変更されます。(ディップスイッチは取付・通電前に設定ください。)
●スイッチ 1(ディップスイッチ設定)を必ず「ON」(有効)にしてください。
機能設定モ ー ド
機能設定モ ー ド
※1:時間レンジの設定値は「タイマとしてご使用される場合」と同じです。
※2:設定値が最後尾に来たとき、UDキーで再び先頭に戻ります。
キープロテクトスイッチ
基本的な設定はディップスイッチだけで行えます。
(注)形 H5CX-L8□-N はディップスイッチがありませんので、   へ進んでください。
●ディップスイッチの設定は電源投入時に変更されます。(ディップスイッチは取付・通電前に設定ください。)
●スイッチ 1(ディップスイッチ設定)を必ず「ON」(有効)にしてください。
12.34
10.00
計時値
OFFセット時 間
計時値
ONセット時 間
MODEMODE
s
s
12.34
18.50 s
s
SET1
SET2
運転モード
電源ON
MODE +
1秒押
MODE +
1秒押
tim
タイマ
ディップスイッチ
モニタ
Uキーにて「ツインタイマ 」に
変更してください 。
twn
ツインタイマ
func
tim
dip
1off
MODE
U1
U1
機種選択モード
最初にツインタイマに切替えます。
キープロテクト表示
キープロテクトスイッチ「ON」時は、
下表のキープロテクトレ ベ ル(KP-1
〜KP-7)に応じて、各キーの操作を
禁止し、誤設定を防止することがで
きます 。
※キープロテクトレベルは機能設定モード
 で設定します。
ON(有効)
OFF(無効)
(出荷時設定)
*「機種選択モード」・「機能設定モード」への移行
レベル
KP-1(初期値)
KP-2
KP-3
KP-4
KP-5
KP-6
KP-7
*モードの移 行
不可
不可
不可
不可
不可
不可
不可
運転モードでの表示切替
可
可
可
可
不可
不可
不可
リセットキー
可
不可
可
不可
不可
可
不可
アップ/ダウンキー
可
可
不可
不可
不可
可
可
異常が発生した時は下記の表示になります 。
*1.EEP-ROMの書き換え寿命に達した場合も含みます。
*2.e3と通常表示を交互に表示します。
  リセットキーを押 すと、警報設定値以上でもe3は表示しません(ただし、出力ON回数は
  クリアされずカウント継続するため、モニタは可 )。
第1表示
e1
e2
e2
e3 *2
第2表示
消灯
消灯
sum
変化なし
内容
CPU異常
メモリ異 常(RAM)
メモリ異 常(EEP-ROM)*1
出力ON回数オーバー
出力状態
OFF
OFF
OFF
変化なし
 復帰方法
リセットキーまたは
電源再投入
電源再投入
リセットキー
リセットキー
復帰後の設定値
変化なし
変化なし
出荷時の状態
変化なし
・タイマの電源仕様を確認の上、ご使用ください 。
・アキ端 子は使 用しないでください 。
6789
接点出力
(+)(−)
0V
12345
リセッ ト
シグナ ル
ゲート
6789
トランジスタ 出 力
*
(+)(−)
0V
12345
リセッ ト
シグナ ル
ゲート
67
8
9
10
11
1
2
3
4
5
(+)(−)
リセット
シグナル
ゲート
0V
アキ
アキ
内部回路
接点
出力
67
8
9
10
11
1
2
3
4
5
(+)(−)
リセット
シグナル
ゲート
0V
アキ
アキ
内部回路
トランジスタ
出力
4
3
2
1 8
7
6
5
(+)(−)
0V
内部回路
シグナル
リセット
接点
出力
4
3
2
1 8
7
6
5
(+)(−)
0V
アキ
内部回路
シグナル
リセット
トランジスタ
出力
4
3
2
1 8
7
6
5
(+)(−)
内部回路
限時 
接点出力
OUT2
内部回路
瞬時
接点出力
OUT1
形H5CX-A-N/-AD-N 形H5CX-AS-N/-ASD-N
形H5CX-A11-N/-A11D-N 形H5CX-A11S-N/-A11SD-N
形H5CX-L8-N/-L8D-N
形H5CX-L8E-N/-L8ED-N
形H5CX-L8S-N/-L8SD-N
形H5CX-AD-Nの①−⑥
端子は内部で接続されて
います。
形H5CX-ASD-Nの①−⑥
端子は内部で接続されてい
ます 。
形H5CX-A11D-Nの②−③端子は内部で接続されています。
形H5CX-A11SD-Nの②−③端子は内部で接続されています。
形H5CX-L8D-Nの①−②端子は内部で接続されています。
形H5CX-L8SD-Nの①−②端子は内部で接続されています。
フロント部の名称
①キープロテクト表示(橙色)
②制御出力表示(橙色)
③リセット表示(橙色)
④計時値(第 1 表示)
(文字高 12mm、赤色*)
*端子台タイプは、赤色/緑色/橙
色切替
⑤時間単位表示
(0min・0.0min・0h・0.0h・0h0min
のレンジでは、計時中表示として点滅
します)
⑥設定値(第 2 表示(文字高 6mm、
緑色)
)
⑦設定値 1、2表示
●表示部
1
3
2
8
9
5
4
6
7
10
11
⑧モードキー(モードの移行、設定項目の切替を行います)
⑨リセットキー(計時値と出力をリセットします)
⑩アップキー1〜4
⑪ダウンキー1〜4
●操作キー部
up,down※2
a,a-1,a-2,a-3,b,b-1,d,
hold/0.01〜99.99
kp-1,kp-2,kp-3,kp-4,
0〜9999
kp-1,kp-2,kp-3,kp-4,
1〜9999
1〜99999999
1〜9999
設定リミット上限
設定リミット1上限
設定リミット2上限
sl1h
sl2h
*
*
形 H5CX-L8E□は、a-2、b、e、z
のみ選択可能
出力時間 0.00 の時、表示は hold
になります。単位:秒
出力モードが a、a-1、a-2、a-3、
b、b-1、sの時のみ表示
形H5CX-L8E□の時のみ表示
形H5CX-L8E□以外の時のみ表示
形H5CX-L8E□
以外の時のみ表示
・誘導負荷使用時
*:
●
技術的なお問い合わせ
0120−919−066(フリ−コ−ル)
携帯電話・PHSなどは055-982-5015です。
直通の制御機器の技術窓口は055-982-5000です。
■営業時間:9:00 〜 12:00/13:00 〜 19:00(土・日・祝祭日は17:00まで)
■営業日:年末年始を除く
●FAXに よる お 問 い 合 わ せ
テクニカルセンタ お客様相談室 FAX055-982-5051
●インターネットによるお問 い合 わせ / F A Q(よくあるご質問)の検索はオムロン
IndustrialWebをご利用ください。 http://www.fa.omron.co.jp/
       インダストリア ル オ ートメーションビジネスカンパニー営業統轄事業部 
東京都品川区大崎1-11-1ゲートシティ大崎ウエストタワー 14F(〒141-0032)
1)形 H5CXシリーズ の AC24V/DC12-24V 電源タイプは電源端子と信号入力端子間が絶縁さ
れていない電 源トランスレス 方 式となっています 。非絶縁タイプの DC 電源を使用する場合は、
配線によっては回り込みで、稀に内部部品の焼損(破壊)の恐れがあります 。ご使用前に配線
を十分ご確認ください 。
2)電源投入時に短時間ですが突入電流が流れ(約10A)、電源の容量によっては起動しないこと
があります ので、充分な容量の電源をご使用ください 。
3)電源電圧の変動範囲は、許容範囲内としてください 。
4)タイマの周辺機器(センサ等)の立ち上がり時間を考慮して、電源ONから200〜250ms経過
後にタイマ動作を開始します。このため電 源スタートをさせる 場 合 、249ms以下の設定では出
力がONするまでの 時 間 が 200〜250msの範囲内で一定の値となりますのでご注 意ください 。
また 、計時値表示は250msよりスタートします 。(250ms以上の設定では通常動作します。)
249ms以下の設定が必要な場合はシグナルスタートで お 使いください 。
5)電源OFFから5〜505ms経過後は入力を受け付けませんのでご注意ください 。
6)電源ON/OFF時の突入電流によって電源回路上の接点の劣化が考えられますので 、定格
10A以上の機器での開閉をおすすめします 。
7)各種設定値は、計測対象に合わせて正しく設 定してください 。設定内容と
計測対象の内容が
異なる場合には、意図しない動作により装置の破損や事故の原因になります 。
8)高温中に長時間、出力電流を流した状態で放置されますと、内部部品(電解コンデンサ等)の
劣化を早める恐れがありますので 避けてください 。
9)EEP-ROMにより停 電 記 憶を行っています。EEP-ROMの書き換え寿命は10万回です。
EEP-ROMは電源OFF時および機能設定モード/機種選択モードから運 転モードに移行する
時に書き換えます。
10)本製品を廃棄する場合は、各地方自治体の産業廃棄物処理方法に従って処理してください 。
11)フロントパネルを必ず取り付けた 状 態で使 用してください 。フロントパネルは4辺中央のツメで本
体に固定されています。取り外しは、4つのツメを広げながら手 前に引きます。取り付けは、4つの
ツメがすべて本体の溝に納まるように はめ 込 ん でください 。
※各パラメータの設定値の詳細は、カタログを参照してください。
●形H5CX-L8E□以外の場合
●形H5CX-L8E□の場合
形H5CX-L8E□の時のみ表示
端子台タイプの時のみ表示
形 H5CX-A□、形 H5CX-A11□の時
のみ表示
モニタ値の表示のみ。設定ではあり
ません。×1000
モニタ値の表示のみ。設定ではあり
ません。×1000
モニタ値の表示のみ。設定ではあり
ません。×1000
※各パラメータの設定値の詳細は、カタログを参照してください。
●出荷時はすべてOFFに設定しています。
●無電圧入力(NPN入力)
入力の接続
●電圧入力(PNP入力)
〈オープンコレクタ〉
〈無接点入力(NPNトランジスタ)〉〈無接点入力(PNPトランジスタ)〉〈有接点入力〉
〈電圧出力〉 〈有接点入力〉
モニタ値の表示のみ。設定では
ありません。×1000
JPN
形H5CX-L8E□は、toff、tonのみ
選択可能。

This manual suits for next models

4

Other Omron Timer manuals

Omron H5CR series User manual

Omron

Omron H5CR series User manual

Omron H5CX-N - User manual

Omron

Omron H5CX-N - User manual

Omron H5CR series User manual

Omron

Omron H5CR series User manual

Omron H8GN User manual

Omron

Omron H8GN User manual

Omron H3CR-F - User manual

Omron

Omron H3CR-F - User manual

Omron H3CR-AP User manual

Omron

Omron H3CR-AP User manual

Omron H3DE User manual

Omron

Omron H3DE User manual

Omron H3CR User manual

Omron

Omron H3CR User manual

Omron H5CX User manual

Omron

Omron H5CX User manual

Omron H5CC-AWSD User manual

Omron

Omron H5CC-AWSD User manual

Omron H3CA-A-101 User manual

Omron

Omron H3CA-A-101 User manual

Omron H2F-D User manual

Omron

Omron H2F-D User manual

Omron H5S - User manual

Omron

Omron H5S - User manual

Omron H5S - User manual

Omron

Omron H5S - User manual

Omron H3DS Series User manual

Omron

Omron H3DS Series User manual

Omron H7GP - User manual

Omron

Omron H7GP - User manual

Omron H3DE-M2 User manual

Omron

Omron H3DE-M2 User manual

Omron H8CA-S Series User manual

Omron

Omron H8CA-S Series User manual

Omron H2F - User manual

Omron

Omron H2F - User manual

Omron H5L Series User manual

Omron

Omron H5L Series User manual

Omron H5S-B User manual

Omron

Omron H5S-B User manual

Omron H8GN - V1.02 User manual

Omron

Omron H8GN - V1.02 User manual

Omron H5CC User manual

Omron

Omron H5CC User manual

Omron Ateg H3DT Series User manual

Omron

Omron Ateg H3DT Series User manual

Popular Timer manuals by other brands

Favero Electronics 154-01 Installation and user manual

Favero Electronics

Favero Electronics 154-01 Installation and user manual

Novus TM-619 user guide

Novus

Novus TM-619 user guide

Stanley TM-266 quick start guide

Stanley

Stanley TM-266 quick start guide

Sylvania SA 170 User instructions

Sylvania

Sylvania SA 170 User instructions

Orbit WaterMaster 57674 Installation manual & users manual

Orbit

Orbit WaterMaster 57674 Installation manual & users manual

FuseBox TD1 user manual

FuseBox

FuseBox TD1 user manual

Steren CLK-150 instruction manual

Steren

Steren CLK-150 instruction manual

DIG BO92A instruction manual

DIG

DIG BO92A instruction manual

WorkChoice WC2011 quick start guide

WorkChoice

WorkChoice WC2011 quick start guide

Flexcharge PROGRAMMABLE TIMER instructions

Flexcharge

Flexcharge PROGRAMMABLE TIMER instructions

Intermatic WH2725AT Installation and setup instructions

Intermatic

Intermatic WH2725AT Installation and setup instructions

WAREMA 1002 219 Operating and installation instructions

WAREMA

WAREMA 1002 219 Operating and installation instructions

Kübler CODIX 527 operating instructions

Kübler

Kübler CODIX 527 operating instructions

Green Brook T612-C user manual

Green Brook

Green Brook T612-C user manual

CO/Tech EMT448 quick start guide

CO/Tech

CO/Tech EMT448 quick start guide

red lion LD user manual

red lion

red lion LD user manual

Top Tronic TDDT7 operating instructions

Top Tronic

Top Tronic TDDT7 operating instructions

ACU-RITE 654 instruction manual

ACU-RITE

ACU-RITE 654 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.