manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Parker
  6. •
  7. Measuring Instrument
  8. •
  9. Parker Racor RK30880E User manual

Parker Racor RK30880E User manual

Other Parker Measuring Instrument manuals

Parker FTIR3 User manual

Parker

Parker FTIR3 User manual

Parker SensoControl Serviceman SCM-150-1-01 Installation guide

Parker

Parker SensoControl Serviceman SCM-150-1-01 Installation guide

Parker SCPSi User manual

Parker

Parker SCPSi User manual

Parker DIGI+ User manual

Parker

Parker DIGI+ User manual

Parker Service Master COMPACT User manual

Parker

Parker Service Master COMPACT User manual

Parker XRF User manual

Parker

Parker XRF User manual

Parker Porter F65 User manual

Parker

Parker Porter F65 User manual

Parker SensoControl Serviceman SCM-150 Series User manual

Parker

Parker SensoControl Serviceman SCM-150 Series User manual

Parker PFM1 Series User manual

Parker

Parker PFM1 Series User manual

Parker DPIT1 VS08MDC1 Series User manual

Parker

Parker DPIT1 VS08MDC1 Series User manual

Parker SciLog SciTemp Guide

Parker

Parker SciLog SciTemp Guide

Parker ServiceJunior SCJN Series User manual

Parker

Parker ServiceJunior SCJN Series User manual

Parker SensoControl ServiceJunior Series User manual

Parker

Parker SensoControl ServiceJunior Series User manual

Parker OSP-P User manual

Parker

Parker OSP-P User manual

Parker Service Master CONNECT User manual

Parker

Parker Service Master CONNECT User manual

Parker BD15 Series Installation and maintenance instructions

Parker

Parker BD15 Series Installation and maintenance instructions

Parker SciPres II Assembly instructions

Parker

Parker SciPres II Assembly instructions

Parker C3000 Instruction Manual

Parker

Parker C3000 Instruction Manual

Parker icountBS Series User manual

Parker

Parker icountBS Series User manual

Parker 023-064 Series User manual

Parker

Parker 023-064 Series User manual

Parker Serviceman Plus User manual

Parker

Parker Serviceman Plus User manual

Parker icountOS User manual

Parker

Parker icountOS User manual

Parker SensoControl ServiceJunior User manual

Parker

Parker SensoControl ServiceJunior User manual

Parker ChemTec II Assembly instructions

Parker

Parker ChemTec II Assembly instructions

Popular Measuring Instrument manuals by other brands

Powerfix Profi 278296 Operation and safety notes

Powerfix Profi

Powerfix Profi 278296 Operation and safety notes

Test Equipment Depot GVT-427B user manual

Test Equipment Depot

Test Equipment Depot GVT-427B user manual

Fieldpiece ACH Operator's manual

Fieldpiece

Fieldpiece ACH Operator's manual

FLYSURFER VIRON3 user manual

FLYSURFER

FLYSURFER VIRON3 user manual

GMW TG uni 1 operating manual

GMW

GMW TG uni 1 operating manual

Downeaster Wind & Weather Medallion Series instruction manual

Downeaster

Downeaster Wind & Weather Medallion Series instruction manual

Hanna Instruments HI96725C instruction manual

Hanna Instruments

Hanna Instruments HI96725C instruction manual

Nokeval KMR260 quick guide

Nokeval

Nokeval KMR260 quick guide

HOKUYO AUTOMATIC UBG-05LN instruction manual

HOKUYO AUTOMATIC

HOKUYO AUTOMATIC UBG-05LN instruction manual

Fluke 96000 Series Operator's manual

Fluke

Fluke 96000 Series Operator's manual

Test Products International SP565 user manual

Test Products International

Test Products International SP565 user manual

General Sleep Zmachine Insight+ DT-200 Service manual

General Sleep

General Sleep Zmachine Insight+ DT-200 Service manual

Sensa Core Lacto Spark user manual

Sensa Core

Sensa Core Lacto Spark user manual

VOLTCRAFT UTS-1980 operating instructions

VOLTCRAFT

VOLTCRAFT UTS-1980 operating instructions

EBCHQ 94915 Operation manual

EBCHQ

EBCHQ 94915 Operation manual

Balluff BIP LD2-T017-01-EP-S4 Series user guide

Balluff

Balluff BIP LD2-T017-01-EP-S4 Series user guide

Pulsar IMP Lite Series instruction manual

Pulsar

Pulsar IMP Lite Series instruction manual

ETCR 6800 user manual

ETCR

ETCR 6800 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

RK30880E
Water-In-Fuel (WIF) Detection Kit
This kit includes new and
enhanced detection electronics
built into the probe body and
works with 12 or 24 volt DC
systems.
Once the level of collected
water rises to make contact
between the two probe tips,
a yellow warning light will
illuminate, indicating time to
drain water and contaminants
from the collection bowl.
Follow draining instructions
provided with each fuel filter/
water separator to drain the
collection bowl. After water
has been drained, the warning
light will reset and no longer be
illuminated.
Instruction Part Number 14400 Rev B
Contact Information
Parker Hannifin Corporation
Racor Division
P.O. Box 3208
3400 Finch Road
Modesto, CA 95353
phone 800 344 3286
209 521 7860
fax 209 529 3278
racor@parker.com
parker.com/racor
Product Features
• Includes a warning light and
mounting panel
• WIF housing permanently
marked for identification
• Built-in detection amplifier
• Circuit board power controller
(10 volt continuous)
• Reverse polarity protection
• False detection prevention
(water slosh delay)
• Electromagnetic compatibility
(EMC)
Specifications
Port Thread Size 1/2"-20 UNF
Housing Glass-filled Nylon
Volts DC 12 or 24
Ohm (trigger threshold) 47K
Ambient Fuel Temperature -40oto +250oF (-40oto +121oC)
RK30880E
Disconnect the Negative terminal
from the battery to avoid the
potential hazard of electrical
shock. Run the wires in protected
locations and avoid hot surfaces
and places that could pinch or
rub on the wires.
1. Lubricate o-ring on water
probe with silicone lube or
clean motor oil, then install into
collection bowl. Tighten probe
body snugly by hand only.
2. Connect BLACK wire on
connector assembly to ground,
RED wire to +12/24 vdc, and
YELLOW wire to either wire of
supplied lamp (use a supplied
butt splice connector). This will
send a ground (-) signal once
water is detected.
Note: The yellow output wire
sends a ground signal (-) when
water is detected. This signal
can only support a 1 amp load
so the provided lamp is ideal.
Should you want this signal to
trigger a warning device that
draws more than 1 amp, use
a relay (customer supplied)
to drive the device. The
yellow wire (ground signal)
should be attached to the coil
ground terminal of the relay.
Once water is detected, the
ground signal will activate the
coil, thus closing the power
contacts to drive your device
(horn, buzzer, etc.).
3. Use loose black wire (supplied
with lamp) and butt splice
connector to connect other
side of lamp to 1 amp fuse,
then to +12/24 vdc.
4. Mount plastic under-dash
bracket and install lamp into
bracket hole or drill a 0.50˝
(12.7 mm) diameter hole in
panel and mount lamp directly
to panel.
5. Use cable ties to secure any
loose wires. Reconnect positive
battery terminal.
Installation Guidelines
Installation Schematic
Red Wire Black Wire
Yellow Wire
Fuse Box
(2 amp max.)
Lamp
+ -
+-
Battery
Ignition
Switch
Red Wire Black Wire
Yellow Wire
Fuse Box
(2 amp max.) Relay
+
-
+ -
Battery
Ignition
Switch
Installation Schematic Using
Customer-Supplied Relay
+
-
Horn, etc.
Installation Information
Typical clear collection bowl.
(This kit will work with other bowl types/
styles with 1/2”-20 UNF threads).
Probe Assembly
Warning Light (install in panel) -
0.50 in. (12.7 mm) diameter hole
Yellow wire to one side of warning light.
(This sends a ground (-) signal)
Black wire to ground
Red wire to
+12/24 VDC
Connector Assembly
Black wire from light kit to 1 amp
fuse, then to +12/24 vdc.
Water Probe Port
1/2"-20 UNF threads.
January 2013© Parker Hannin Corporation
All products manufactured
or distributed by Racor are
subject to the following, and
only the following, LIMITED
EXPRESS WARRANTIES, and
no others: For a period of
one (1) year from and after
the date of purchase of a new
Racor product, Racor warrants
and guarantees only to the
original purchaser-user that
such a product shall be free
from defects of materials
and workmanship in the
manufacturing process. The
warranty period for pumps and
motors is specifically limited
to ninety (90) days from date of
purchase. A product claimed to
be defective must be returned
to the place of purchase. Racor,
at its sole option, shall replace
the defective product with a
comparable new product or
repair the defective product.
This express warranty shall be
inapplicable to any product not
properly installed and properly
used by the purchaser-user
or to any product damaged or
impaired by external forces.
THIS IS THE EXTENT OF
WARRANTIES AVAILABLE
ON THIS PRODUCT. RACOR
SHALL HAVE NO LIABILITY
WHATSOEVER FOR
CONSEQUENTIAL DAMAGES
FLOWING FROM THE USE OF
ANY DEFECTIVE PRODUCT
OR BY REASON OF THE
FAILURE OF ANY PRODUCT.
RACOR SPECIFICALLY
DISAVOWS ALL OTHER
WARRANTIES, EXPRESS
OR IMPLIED INCLUDING,
WITHOUT LIMITATION, ALL
WARRANTIES OF FITNESS
FOR A PARTICULAR PURPOSE
(EXCEPT FOR THOSE WHICH
APPLY TO PRODUCT OR
PART THEREOF THAT IS
USED OR BOUGHT FOR USE
PRIMARILY FOR PERSONAL,
FAMILY, OR HOUSEHOLD
PURPOSES), WARRANTIES OF
DESCRIPTION, WARRANTIES
OF MERCHANTABILITY,
TRADE USAGE OR
WARRANTIES OR TRADE
USAGE.
Warning
Failure or improper selection
or improper use of the
products and/or systems
described herein or related
items can cause death,
personal injury and property
damage. This document and
other information from Parker
Hannifin Corporation, its
subsidiaries and authorized
distributors provide product
and/or system options for
further investigation by users
having technical expertise.
It is important that you
analyze all aspects of your
application and review the
information concerning the
product or system in the
current product catalog. Due
to the variety of operating
conditions and applications
for these products or systems,
the user, through its own
analysis and testing, is solely
responsible for making the
final selection of the products
and systems and assuring that
all performance, safety and
warning requirements of the
applications are met.
The products described
herein, including with
limitation, product features,
specifications, designs,
availability and pricing, are
subject to change by Parker
Hannifin Corporation and
its subsidiaries at any time
without notice.