Penn TC3B23 User manual

PENN | TC3B23 | Installation Guide Rev. B | Part No. 24-7664-03574 | Page 1 of 2 | 07 April 2020
TC3B23 Basic controller for refrigerated cabinets,
with energy-saving strategies
E ENGLISH
- Controller for low temperature units.
- Power supply for TC3B23N5V: 115 VAC.
- Power supply for TC3B23N7V: 230 VAC.
- Cabinet probe and auxiliary probe (NTC).
- Door switch/multi-purpose input.
- Cooling or heating operation.
1 MEASUREMENTS AND INSTALLATION
Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided.
INSTALLATION PRECAUTIONS
- The thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in)
- Ensure that the working conditions are within the limits stated in the TECHNICAL
SPECIFICATIONS section.
- Do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks.
- In compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be
fixed in such a way as to need the aid of a tool to remove them.
2 ELECTRICAL CONNECTION
Important
- Use cables of an adequate wire gauge for the current running through them.
- To reduce any electromagnetic interference connect the power cables as far away
as possible from the signal cables.
-Power supply for TC3B23N5V: 115 VAC.
- Power supply for TC3B23N7V: 230 VAC.
PRECAUTIONS FOR ELECTRICAL CONNECTION
- If you use an electrical or pneumatic screwdriver, adjust the torque to a maximum of
0.5 N•m (4 in. lb).
- If the device was moved from a cold to a warm place, the humidity may have caused
condensation to form inside. Wait about an hour before switching on the power.
- Make sure that the supply voltage, electrical frequency and power are within the set
limits. See the section TECHNICAL SPECIFICATIONS.
- Disconnect the power supply before doing any type of maintenance.
- Do not use the device as safety device.
- For repairs and for further information, contact the PENN sales network.
3 FIRST-TIME
1. Install following the instructions given in the section MEASUREMENTS AND INSTALLA-
TION.
2. Power up the device as shown in the section ELECTRICAL CONNECTION and an internal
test will be run.
The test normally takes a few seconds, when it is finished the display will switch off.
3. Configure the device as shown in Table 6.1 in the section SETTINGS.
Recommended configuration parameters for first-time use.
PAR. DEF. PARAMETER MIN... MAX.
SP 0.0 setpoint r1... r2
P2 0 temperature unit of measurement 0 = °C 1 = °F
d1 0 defrost type 0 = electric 1 = hot gas
2 = compressor stopped
Then check that the remaining settings are appropriate; see the section CONFIGURA-
TION PARAMETERS.
4. Disconnect the device from the mains.
5. Make the electrical connection as shown in the section ELECTRICAL CONNECTION with-
out powering up the device.
6. Power up the device.
4 USER INTERFACE AND MAIN FUNCTIONS
4.1 Switching the device on/off
1. If POF = 1, touch the ON/STAND-BY key for 4 s.
If the device is switched on, the display will show the P5 value ("cabinet temperature" default);
if the display shows an alarm code, see the section ALARMS.
LED ON OFF FLASHING
compressor on compressor off - compressor protection active
- setpoint setting active
defrost or pre-dripping
active - - defrost delay active
- dripping active
evaporator fan on evaporator fan off evaporator fan stop active
-if device on, energy
saving active
- if device off, low
consumption active
- -
°C/°F view temperature - -
device off device on device on/off active
If 30 s have elapsed without the keys being pressed, the display will show the “Loc” label and
the keypad will lock automatically.
4.2 Unlock keypad
Touch any key for 1 s: the display will show the label “UnL”.
4.3 Set the setpoint
Check that the keypad is not locked.
1. Touch the SET key.
2. Touch the UP or DOWN key within 15 s to set the value within
the limits r1 and r2 (default “-40... 50”)
3. Touch the SET key (or do not operate for 15 s).
4.4 Activate manual defrost (if r5 = 0, default)
Check that the keypad is not locked.
1. Touch the UP key for 2 s.
If P4 = 1 (default), defrost is activated provided that the evaporator temperature is lower than
the d2 threshold.
5 ADDITIONAL FUNCTIONS
5.1 View/delete compressor functioning hours
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
CH view compressor functioning hours (hundreds)
rCH delete compressor functioning hours
3. Touch the SET key.
4. Touch the UP or DOWN key to set “149” (when label “rCH” is se-
lected).
5. Touch the SET key.
6. Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
5.2 View the temperature detected by the probes
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
Pb1 cabinet temperature
Pb2 auxiliary temperature
3. Touch the SET key.
4. Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
6 SETTINGS
6.1 Setting configuration parameters
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15 s to set the PAS value (de-
fault “-19”).
4. Touch the SET key (or do not operate for 15 s): the display will
show the label “SP”.
5. Touch the UP or DOWN key to select a parameter.
6. Touch the SET key.
7. Touch the UP or DOWN key within 15 s to set the value.
8. Touch the SET key (or do not operate for 15 s).
9. Touch the SET key for 4 s (or do not operate for 60 s) to exit the
procedure.
6.2 Restore the factory settings (default) and store customized settings as default
Important
- Check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
- When you store customized settings, you overwrite the default.
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15 s to set the value.
VAL. DESCRIPTION
149 value to restore the factory settings (default)
161 value to store customized settings as default
4. Touch the SET key (or do not operate for 15 s): the display will
show the label “dEF” (when value “149” is set) or the label
“MAP” (when value “161” is set).
5. Touch the SET key.
6. Touch the UP or DOWN key within 15 s to set “4”.
7. Touch the SET key (or do not operate for 15 s): the display will
show for 4 s “- - -“ flashing, then the device will exit the proce-
dure.
8. Interrupt the power supply to the device.
9. Touch the SET key 2 s before action 6. to exit the procedure be-
forehand.
7 CONFIGURATION PARAMETERS
N. PAR. DEF. SETPOINT MIN... MAX.
1 SP 0.0 setpoint r1... r2
N. PAR. DEF. ANALOG INPUTS MIN... MAX.
2 CA1 0.0 cabinet probe offset -25... 25 °F/°C
3 CA2 0.0 auxiliary probe offset -25... 25 °F/°C
4 P0 1 probe type 0 = n/a 1 = NTC
5 P1 1 enable °C decimal point 0 = no 1 = yes
6 P2 0 temperature unit of
measurement 0 = °C 1 = °F
7 P4 1 auxiliary probe function 0 = disabled
1 = evaporator probe (de-
frost + fan)
2 = evaporator probe (fan)
3 = condenser probe
8 P5 0 value displayed 0 = cabinet temperature
1 = setpoint
2 = auxiliary temperature
9 P8 5 display refresh time 0... 250 s : 10
N. PAR. DEF. CONTROL MIN... MAX.
10 r0 2.0 setpoint differential 1... 15 °F/°C
11 r1 -40 minimum setpoint -99 °F/°C... r2
12 r2 50.0 maximum setpoint r1... 199 °F/°C
13 r4 0.0 setpoint offset in energy saving 0... 99 °F/°C
14 r5 0 cooling or heating operation 0 = cooling
1 = heating
15 r12 1 position of the r0 differential 0 = asymmetric
1 = symmetric
N. PAR. DEF. COMPRESSOR MIN... MAX.
16 C0 0 compressor on delay after pow-
er-on 0... 240 min
17 C2 3 compressor off minimum time 0... 240 min
18 C3 0 compressor on minimum time 0... 240 s
19 C4 0 compressor off time during cabi-
net probe alarm 0... 240 min
20 C5 10 compressor on time during cabi-
net probe alarm 0... 240 min
21 C6 80.0 threshold for high condenser
temperature warning 0... 199 °F/°C
differential = 4 °F/2 °C
22 C7 90.0 threshold for high condenser
temperature alarm 0... 199 °F/°C
23 C8 1 high condenser temperature
alarm delay 0... 15 min
N. PAR. DEF. DEFROST (if r5 = 0) MIN... MAX.
24 d0 8 automatic defrost interval 0... 99 h
0 = only manual
if d8 = 3, maximum interval
25 d1 0 defrost type 0 = electric
1 = hot gas
2 = compressor stopped
26 d2 2.0 threshold for defrost end -99... 99 °F/°C
27 d3 30 defrost duration 0... 99 min
if P3 = 1, maximum duration
28 d4 0 enable defrost at power-on 0 = no 1 = yes
29 d5 0 defrost delay after power-on 0... 99 min
30 d6 1 value displayed during defrost 0 = cabinet temperature
1 = display locked
2 = dEF label
31 d7 2 dripping time 0... 15 min
32 d8 0 defrost interval counting mode 0 = device on hours
1 = compressor on hours
2 = hours evaporator tem-
perature < d9
3 = adaptive
33 d9 0.0 evaporation threshold for auto-
matic defrost interval counting -99... 99 °F/°C
34 d11 0 enable defrost timeout alarm 0 = no 1 = yes
35 d15 0 compressor on consecutive time
for hot gas defrost 0... 99 min
36 d18 40 adaptive defrost interval 0... 999 min
if compressor on + evapora-
tor temperature < d22
0 = only manual
37 d19 3.0 threshold for adaptive defrost
(relative to optimal evaporation
temperature)
0... 40 °F/°C
optimal evaporation tempera-
ture - d19
38 d20 180 compressor on consecutive time
for defrost 0... 999 min
0 = disabled
39 d22 2.0 evaporation threshold for adap-
tive defrost interval counting
(relative to optimal evaporation
temperature)
0... 19 °F/°C
optimal evaporation tempera-
ture + d22
N. PAR. DEF. ALARMS MIN... MAX.
40 A1 10.0 threshold for low temperature
alarm (relative to setpoint) 0... 99 °F/°C
SP - A1
0 = disabled
41 A4 10.0 threshold for high temperature
alarm (relative to setpoint) 0... 99 °F/°C
SP + A4
0 = disabled
42 A6 12 high temperature alarm delay af-
ter power-on 0... 99 min x 10
43 A7 15 high/low temperature alarms de-
lay 0... 240 min
44 A8 15 high temperature alarm delay af-
ter defrost 0... 240 min
45 A9 15 high temperature alarm delay af-
ter door closing 0... 240 min
46 A11 2.0 high/low temperature alarms re-
set differential 1... 15 °F/°C
N. PAR. DEF. FANS MIN... MAX.
47 F0 3 evaporator fan mode during
normal operation 0 = off 1 = on
2 = on if compressor on
3 = thermoregulated (with
F1)
4 = thermoregulated (with
F1) if compressor on
48 F1 -1.0 threshold for evaporator fan op-
eration -99... 99 °F/°C
differential = 2 °F/1 °C
49 F2 0 evaporator fan mode during de-
frost and dripping 0 = off 1 = on
2 = according to F0
50 F3 2 evaporator fan off maximum
time 0... 15 min
51 F4 30 evaporator fan off time during
energy saving 0... 240 s x 10
52 F5 30 evaporator fan on time during
energy saving 0... 240 s x 10

PENN | TC3B23 | Installation Guide Rev. B | Part No. 24-7664-03574 | Page 2 of 2 | 07 April 2020
N. PAR. DEF. DIGITAL INPUTS MIN... MAX.
53 i0 1 door switch/multi-purpose input
function 0 = disabled
1 = compressor + evapora-
tor fan off
2 = evaporator fan off
3 = energy saving
4 = iA alarm
5 = iA alarm + compressor
off
54 i1 0 door switch/multi-purpose input
activation 0 = with contact closed
1 = with contact open
55 i2 30 open door alarm delay -1... 120 min
if i0 = 3, multi-purpose input
alarm delay
if i0 = 4, compressor on de-
lay after alarm reset
-1= disabled
56 i3 15 regulation inhibition maximum
time with door open -1... 120 min
-1= until the closing
57 i10 0 door closed consecutive time for
energy saving 0... 999 min
after regulation temperature
< SP
0 = disabled
58 i13 180 number of door openings for de-
frost 0... 240
0 = disabled
59 i14 32 door open consecutive time for
defrost 0... 240 min
0 = disabled
N. PAR. DEF. ENERGY SAVING (if r5 = 0) MIN... MAX.
60 HE2 0 energy saving maximum duration 0... 999 min
0 = until the door opening
61 HE3 2 no operation on the keyboard
consecutive time for low con-
sumption
0... 240 min
0 = disabled
N. PAR. DEF. SAFETIES MIN... MAX.
62 POF 0 enable ON/STAND-BY key 0 = no 1 = yes
63 PAS -19 password -99... 999
8 ALARMS
COD. DESCRIPTION RESET REMEDIES
Pr1 cabinet probe alarm automatic - check P0
Pr2 auxiliary probe alarm automatic - check probe integrity
- check electrical connection
AL low temperature alarm automatic check A1
AH high temperature alarm automatic check A4
id open door alarm automatic check i0 e i1
COH high condenser temperature
warning automatic check C6
CSd high condenser temperature
alarm manual - switch the device off and on
- check C7
iA multi-purpose input alarm automatic check i0 and i1
dFd defrost timeout alarm manual - touch any key
- check d2, d3 and d11
9 ELECTRICAL RATINGS
Output Units cULus (UL 60730) CE (EN 60730)
Applied voltage at 60 Hz 120 VAC 240 VAC 240 VAC
K1
compressor
relay
Resistive amperes 12 12 10
Inductive amperes — — 2
Full load amperes 10 10 —
Locked rotor amperes 60 60 —
K2 relay
Resistive amperes 8 8 5
Inductive amperes — — 2
Full load amperes 4.4 2.9 —
Locked rotor amperes 26.4 17.4 —
K3
evaporator
fan relay
Resistive amperes 5 5 5
Inductive amperes — — 1
Full load amperes 1.5 1.5 —
Locked rotor amperes 9 9 —
10 TECHNICAL SPECIFICATIONS
Purpose of the control device Function controller
Construction of the control device Built-in electronic device
Container Black, self-extinguishing
Category of heat and fire resistance D
Measurements 75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x
2 5/16 in)
Mounting methods for the control device Tobe fitted to a panel, snap-in brackets pro-
vided
Degree of protection provided by the cover-
ing IP65 (front)
Connection method Fixed screw terminal blocks for wires up to
2,5 mm²
Maximum permitted length for connection cables
Power supply: 10 m (32.8 ft) Analog inputs: 10 m (32.8 ft)
Digital inputs: 10 m (32.8 ft) Digital outputs: 10 m (32.8 ft)
Operating temperature From 32 to 131 °F (from 0 to 55 °C)
Storage temperature From -13 to 158 °F (from -25 to 70 °C)
Operating humidity Relative humidity without condensate from
10 to 90%
Pollution status of the control device 2
Compliance
Europe JCI declares product compliance meets requirements of EMC, LVD, and RoHS
Directives.
USA UL Recognized Component, SDFY2.SA516; FCC Part 15 Subpart B Class A
Canada UL Recognized Component, SDFY8.SA516; ICES-003 Class A
Power supply TC3B23N5V 115 VAC (+10% -15%), 50/60 Hz (+/- 3Hz), max. 2 VA
TC3B23N7V 230 VAC (+10% -15%), 50/60 Hz (+/- 3Hz), max. 2 VA
Grounding methods for the control device None
Rated impulse-withstand voltage 4 KV
Over-voltage category III
Software class and structure A
Analog inputs 2 for NTC probes (cabinet probe and auxiliary
probe)
NTC probes Sensor type ß3435 (10 K@ 77 °F, 25 °C)
Measurement field From -40 to 221 °F (from -40 to 105 °C)
Resolution 1 °F (0.1 °C)
Digital inputs 1 dry contact (door switch/multi-purpose)
Dry contact Contact type 5 VDC, 1.5 mA
Power supply None
Protection None
Digital outputs 3 electro-mechanical relays (compressor, defrost and evaporator fan)
Type 1 or Type 2 Actions Type 1
Additional features of Type 1 or Type 2 ac-
tions C
Displays 3 digits custom display, with function icons
11 PRODUCT WARRANTY
This product is covered by a limited warranty, details of which can be found at
www.johnsoncontrols.com/buildingswarranty
12 SOFTWARE TERMS
Use of the software that is in (or constitutes) this product, or access to the cloud, or hosted
services applicable to this product, if any, is subject to applicable terms set forth at
www.johnsoncontrols.com/techterms. Your use of this product constitutes an agreement to
such terms.
13 SINGLE POINT OF CONTACT
APAC Europe NA/SA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT
MANAGEMENT
NO. 32 CHANGJIJANG RD NEW
DISTRICT
WUXI JIANGSU PROVINCE
214028
CHINA
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
14 CONTACT INFORMATION
Contact your local branch office:
www.johnsoncontrols.com/locations
Contact Johnson Controls:
www.johnsoncontrols.com/contact-us
Important
The device must be disposed of according to local regulations governing the collection
of electrical and electronic waste.
This document and the solutions contained therein are the intellectual property of PENN and thus pro-
tected by the Italian Intellectual Property Rights Code (CPI). PENN imposes an absolute ban on the full or
partial reproduction and disclosure of the content other than with the express approval of PENN. The
customer (manufacturer, installer or end-user) assumes all responsibility for the configuration of the de-
vice. PENN accepts no liability for any possible errors in this document and reserves the right to make
any changes, at any time without prejudice to the essential functional and safety features of the equip-
ment.
Johnson Controls
507 E. Michigan St.
Milwaukee, WI 53202-5211
USA
www.penncontrols.com
Other manuals for TC3B23
2
Other Penn Controllers manuals