manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Penn
  6. •
  7. Controllers
  8. •
  9. Penn TC3224N9R User manual

Penn TC3224N9R User manual

PENN | TC3224N9R | Installation Guide Rev. B | PartNo. 24-7664-03531 | Page 1 of 3 | 07 April 2020
TC3224N9R Controller for refrigerated cabinets, counters and islands,
with energy-saving strategies
E ENGLISH
- Controller for low temperature units.
- Universal power supply 115... 230 VAC.
-Incorporated clock.
-Cabinet probe and evaporator probe (NTC, 10,000 ohm at 77 °F).
- Door switch input.
-Alarm buzzer.
- RS-485 MODBUS subordinate port for BMS.
- Cooling or heating operation.
1 MEASUREMENTS AND INSTALLATION
Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided.
INSTALLATION PRECAUTIONS
- The thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in)
- Ensure that the working conditions are within the limits stated in the TECHNICAL
SPECIFICATIONS section.
- Do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks.
- In compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be
fixed in such a way as to need the aid of a tool to remove them.
2 ELECTRICAL CONNECTION
Important
- Use cables of an adequate wire gauge for the current running through them.
- To reduce any electromagnetic interference connect the power cables as far away
as possible from the signal cables.
-Power supply for TC3224N9R: 115... 230 VAC.
PRECAUTIONS FOR ELECTRICAL CONNECTION
- If you use an electrical or pneumatic screwdriver, adjust the torque to a maximum of
0.5 N•m (4 in. lb).
- If the device was moved from a cold to a warm place, the humidity may have caused
condensation to form inside. Wait about an hour before switching on the power.
- Make sure that the supply voltage, electrical frequency and power are within the set
limits. See the section TECHNICAL SPECIFICATIONS.
- Disconnect the power supply before doing any type of maintenance.
- Do not use the device as safety device.
- For repairs and for further information, contact the PENN sales network.
3 FIRST-TIME
1. Install following the instructions given in the section MEASUREMENTS AND INSTALLA-
TION.
2. Power up the device as shown in the section ELECTRICAL CONNECTION and an internal
test will be run.
The test normally takes a few seconds, when it is finished the display will switch off.
3. Configure the device as shown in Table 6.1 in the section SETTINGS.
Recommended configuration parameters for first-time use.
PAR. DEF. PARAMETER MIN... MAX.
SP 0.0 setpoint r1... r2
P2 0 temperature unit of measurement 0 = °C 1 = °F
d1 0 defrost type 0 = electric 1 = hot gas
2 = compressor stopped
Then check that the remaining settings are appropriate; see the section CONFIGURA-
TION PARAMETERS.
4. Disconnect the device from the mains.
5. Make the electrical connection as shown in the section ELECTRICAL CONNECTION with-
out powering up the device.
6. Power up the device.
4 USER INTERFACE AND MAIN FUNCTIONS
4.1 Switching the device on/off
1. If POF = 1, touch the ON/STAND-BY key for 4 s.
If the device is switched on, the display will show the P5 value ("cabinet temperature" default);
if the display shows an alarm code, see the section ALARMS.
LED ON OFF FLASHING
compressor on compressor off - compressor protection active
- setpoint setting active
defrost or pre-dripping
active
- - defrost delay active
- dripping active
evaporator fan on evaporator fan off evaporator fan stop active
HACCP saved HACCP alarm - new HACCP alarm saved
energy saving active - -
request for compres-
sor service
- - settings active
-access to additional functions
active
°C/°F view temperature - overcooling or overheating active
AUX auxiliary load on auxiliary load off - auxiliary load on by digital input
- auxiliary load delay active
device off device on device on/off active
If 30 s have elapsed without the keys being pressed, the display will show the “Loc” label and
the keypad will lock automatically.
4.2 Unlock keypad
Touch any key for 1 s: the display will show the label “UnL”.
4.3 Set the setpoint
Check that the keypad is not locked.
1. Touch the SET key.
2. Touch the UP or DOWN key within 15 s to set the value within
the limits r1 and r2 (default “-50... 50”)
3. Touch the SET key (or do not operate for 15 s).
4.4 Activate manual defrost (if r5 = 0, default)
Check that the keypad is not locked and that overcooling is not active.
1. Touch the UP key for 2 s.
If P3 = 1 (default), defrost is activated provided that the evaporator temperature is lower than
the d2 threshold.
4.5 Cabinet light on/off (if u1 = 0, default)
1. Touch the ON/STAND-BY key.
- if u1 = 1, the anti-fog switches on for the u6 duration.
- if u1 = 2, r13 = 0 and the keypad is not locked, the key-operated load switches
on/off.
4.6 Key-operated load on/off (if u1 = 2 and r13 = 1)
1. Touch the UP key.
4.7 Silence buzzer (if A13 = 1)
Touch any key.
If u1 = 3 and u4 = 1, the alarm output switches off.
5 ADDITIONAL FUNCTIONS
5.1 Activate/deactivate overcooling, overheating and manual energy saving
Check that the keypad is not locked.
1. Touch the DOWN key.
FUNCTION CONDITION CONSEQUENCE
overcooling r5 = 0, r8 = 1 and defrost
not active
the setpoint becomes “setpoint -
r6”, for the r7 duration
overheating r5 and r8 = 1 the setpoint becomes “setpoint +
r6”, for the r7 duration
energy saving r5 = 0 and r8 = 2 the setpoint becomes “setpoint +
r4”, at maximum for HE2 duration
5.2 View/delete HACCP alarm information
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
LS view HACCP alarm information
rLS delete HACCP alarm information
3. Touch the SET key.
4. Touch the UP or DOWN key to select an alarm code (when label
“LS” is selected) or to set “149” (when label “rLS” is selected).
COD. DESCRIPTION
AL low temperature alarm
AH high temperature alarm
id door switch alarm
PF power failure alarm
5. Touch the SET key.
6. Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
Example of alarm information (e.g. a high temperature alarm).
8.0 critical value (cabinet/ calculated product temperature)
was 8.0 °F/°C
Sta
y15 alarm signalled in 2015
n03 alarm signalled in March
d26 alarm signalled on 26 March 2015
h16 alarm signalled at 16:00
n30 alarm signalled at 16:30
dur
h01 alarm lasted 1h
n15 alarm lasted 1h 15 min
5.3 View/delete compressor functioning hours and view compressor start-up
number
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
CH view compressor functioning hours (hundreds)
rCH delete compressor functioning hours
nS1 compressor start-up number (thousands)
3. Touch the SET key.
4. Touch the UP or DOWN key to set “149” (when label “rCH” is se-
lected).
5. Touch the SET key.
6. Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
5.4 View the temperature detected by the probes
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
Pb1 cabinet temperature (if P4 = 0, 1 or 2)
inlet air temperature (if P4 = 3)
Pb2 evaporator temperature (if P3 = 1 or 2)
Pb3 auxiliary temperature (if P4 = 1, 2 or 3)
Pb4 calculated product temperature (CPT) (if P4 = 3). See P7 in CONFIGURATION
PARAMETERS for information.
3. Touch the SET key.
4. Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
5.5 View the project number and the firmware revision
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
PrJ view the project number
rEU view the firmware revision
3. Touch the SET key.
4. Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
6 SETTINGS
6.1 Setting configuration parameters
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key. The display shows the label “PAS”.
3. Touch the UP or DOWN key within 15 s to set the password. The
default password is “-19”.
4. Touch the SET key (or do not operate for 15 s): the display will
show the label “SP”.
5. Touch the UP or DOWN key to select a parameter.
6. Touch the SET key.
7. Touch the UP or DOWN key within 15 s to set the value.
8. Touch the SET key (or do not operate for 15 s).
9. Touch the SET key for 4 s (or do not operate for 60 s) to exit the
procedure.
6.2 Set the date, time and day of the week
Important
Do not disconnect the device from the mains within two minutes since the setting of
the time and day of the week.
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select the label “rtc”.
3. Touch the SET key: the display will show the label “yy” followed
by the last two figures of the year.
4. Touch the UP or DOWN key within 15 s to set the year.
5. Repeat actions 3. and 4. to set the next labels.
LAB. DESCRIPTION OF THE NUMBERS FOLLOWING THE LABEL
n month (01… 12)
d day (01… 31)
h time (00… 23)
n minute (00… 59)
6. Touch the SET key: the display will show the label for the day of
the week.
7. Touch the UP or DOWN key within 15 s to set the day of the
week.
LAB. DESCRIPTION
Mon... Sun Monday... Sunday
8. Touch the SET key: the device will exit the procedure.
9. Touch the ON/STAND-BY key to exit the procedure beforehand.
6.3 Restore the factory settings (default) and store customized settings as default
Important
- Check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
- When you store customized settings, you overwrite the default.
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15 s to set the value.
VAL. DESCRIPTION
149 value to restore the factory settings (default)
161 value to store customized settings as default
4.
Touch the SET key (or do not operate for 15 s): the display will
show the label “dEF” (when value “149” is set) or the label
“MAP” (when value “161” is set).
5. Touch the SET key.
6. Touch the UP or DOWN key within 15 s to set “4”.
7.
Touch the SET key (or do not operate for 15 s): the display will
show for 4 s “- - -“ flashing, then the device will exit the proce-
dure.
8. Interrupt the power supply to the device.
9. Touch the SET key 2 s before action 6. to exit the procedure be-
forehand.
7 CONFIGURATION PARAMETERS
N. PAR. DEF. SETPOINT MIN... MAX.
1 SP 0.0 setpoint r1... r2
N. PAR. DEF. ANALOG INPUTS MIN... MAX.
2 CA1 0.0 cabinet probe offset -25... 25 °F/°C
if P4 = 3, air in probe offset
3 CA2 0.0 evaporator probe offset -25... 25 °F/°C
4 CA3 0.0 auxiliary probe offset -25... 25 °F/°C
5 P0 1 probe type 0 = n/a 1 = NTC
PENN | TC3224N9R | Installation Guide Rev. B | PartNo. 24-7664-03531 | Page 2 of 3 | 07 April 2020
6 P1 1 enable °C decimal point 0 = no 1 = yes
7 P2 0 temperature unit of
measurement
0 = °C 1 = °F
8 P3 1 evaporator probe function 0 = disabled
1 = defrost + fan
2 = fan
9 P4 0 configurable input function 0 = digital input
1 = condenser probe
2 =
critical temperature probe
3 = air out probe
if P4 = 3, regulation temperature
= product temperature (CPT)
10 P5 0 value displayed 0 = regulation temperature
1 = setpoint
2 = evaporator temperature
3 = auxiliary temperature
4 = air in temperature
11 P7 5 inlet air weight for calculated
product temperature (CPT)
0... 10 % x 10
CPT = {[(P7 x (inlet air T)] +
[(100 - P7) x (outlet air T)] :
100}
12 P8 5 display refresh time 0... 250 s : 10
N. PAR. DEF. CONTROL MIN... MAX.
13 r0 2.0 setpoint differential 1... 15 °F/°C
14 r1 -50 minimum setpoint -99 °F/°C... r2
15 r2 50.0 maximum setpoint r1... 199 °F/°C
16 r4 0.0 setpoint offset in energy saving 0... 99 °F/°C
17 r5 0 cooling or heating operation 0 = cooling
1 = heating
18 r6 0.0 setpoint offset in overcool-
ing/overheating
0... 99 °F/°C
19 r7 30 overcooling/overheating duration 0... 240 min
20 r8 0 DOWN key additional function 0 = disabled
1 = overcooling/overheating
2 = energy saving
21 r12 0 position of the r0 differential 0 = asymmetric around
setpoint
1 = setpoint + r0 differential
22 r13 0 UP key additional function 0 = none
1 = key-operated load
N. PAR. DEF. COMPRESSOR MIN... MAX.
23 C0 0 compressor on delay after pow-
er-on
0... 240 min
24 C2 3 compressor off minimum time 0... 240 min
25 C3 0 compressor on minimum time 0... 240 s
26 C4 10 compressor off time during cabi-
net probe alarm
0... 240 min
27 C5 10 compressor on time during cabi-
net probe alarm
0... 240 min
28 C6 80.0 threshold for high condenser
temperature warning
0... 199 °F/°C
differential = 4 °F/2 °C
29 C7 90.0 threshold for high condenser
temperature alarm
0... 199 °F/°C
30 C8 1 high condenser temperature
alarm delay 0... 15 min
31 C10 0 compressor hours for service 0... 999 h x 100
0 = disabled
32 C11 0 second compressor switch-on de-
lay
0... 240 s
33 C13 0 number of start-ups for compres-
sor rotation
0... 10
0 = disabled
N. PAR. DEF. DEFROST (if r5 = 0) MIN... MAX.
34 d0 8 automatic defrost interval 0... 99 h
0 = only manual
if d8 = 3, maximum interval
35 d1 0 defrost type 0 = electric
1 = hot gas
2 = compressor stopped
36 d2 8.0 threshold for defrost end -99... 99 °F/°C
37 d3 30 defrost duration 0... 99 min
if P3 = 1, maximum duration
38 d4 0 enable defrost at power-on 0 = no 1 = yes
39 d5 0 defrost delay after power-on 0... 99 min
40 d6 2 value displayed during defrost 0 = regulation temperature
1 = display locked
2 = dEF label
41 d7 2 dripping time 0... 15 min
42 d8 0 defrost interval counting mode 0 = device on hours
1 = compressor on hours
2 = hours evaporator tem-
perature < d9
3 = adaptive
4 = real time
43 d9 0.0 evaporation threshold for auto-
matic defrost interval counting
-99... 99 °F/°C
44 d11 0 enable defrost timeout alarm 0 = no 1 = yes
45 d15 0 compressor on consecutive time
for hot gas defrost
0... 99 min
46 d16 0 pre-dripping time for hot gas de-
frost
0... 99 min
47 d18 40 adaptive defrost interval 0... 999 min
if compressor on + evapora-
tor temperature < d22
0 = only manual
48 d19 3.0 threshold for adaptive defrost
(relative to optimal evaporation
temperature)
0... 40 °F/°C
optimal evaporation tempera-
ture - d19
49 d20 180 compressor on consecutive time
for defrost
0... 999 min
0 = disabled
50 d21 200 compressor on consecutive time
for defrost after power-on and
overcooling
0... 500 min
if (regulation temperature -
setpoint) > 20 °F/10°C
0 = disabled
51 d22 -2.0 evaporation threshold for adap-
tive defrost interval counting
(relative to optimal evaporation
temperature)
-10... 10 °F/°C
optimal evaporation tempera-
ture + d22
N. PAR. DEF. ALARMS MIN... MAX.
52 AA 0 select sensor for high/low tem-
perature alarms
0 = regulation temperature
1 = evaporator temperature
2 = auxiliary temperature
53 A1 -10.0 threshold for low temperature
alarm
-99... 99 °F/°C
54 A2 1 low temperature alarm type 0 = disabled
1 = relative to setpoint
2 = absolute
55 A4 10.0 threshold for high temperature
alarm
-99... 99 °F/°C
56 A5 1 high temperature alarm type 0 = disabled
1 = relative to setpoint
2 = absolute
57 A6 12 high temperature alarm delay af-
ter power-on
0... 99 min x 10
58 A7 15 high/low temperature alarms de-
lay
0... 240 min
59 A8 15 high temperature alarm delay af-
ter defrost
0... 240 min
60 A9 15 high temperature alarm delay af-
ter door closing
0... 240 min
61 A10 10 power failure duration for alarm
recording
0... 240 min
62 A11 2.0 high/low temperature alarms re-
set differential
1... 15 °F/°C
63 A12 2 power failure alarm notification
type
0 = HACCP LED
1 = HACCP LED + PF label +
buzzer
2 =
HACCP LED + PF label +
buzzer (if duration > A10)
64 A13 0 enable alarm buzzer 0 = no 1 = yes
N. PAR. DEF. FANS MIN... MAX.
65 F0 3 evaporator fan mode during
normal operation
0 = off 1 = on
2 = according to F15 and
F16 if compressor off, on
if compressor on
3 = thermoregulated (with
F1)
4 = thermoregulated (with
F1) if compressor on
66 F1 -1.0 threshold for evaporator fan op-
eration
-99... 99 °F/°C
differential = 2 °F/1 °C
67 F2 0 evaporator fan mode during de-
frost and dripping
0 = off 1 = on
2 = according to F0
68 F3 2 evaporator fan stop maximum
duration
0... 15 min
69 F4 0 evaporator fan off time during
energy saving
0... 240 s x 10
70 F5 10 evaporator fan on time during
energy saving
0... 240 s x 10
71 F7 5.0 threshold for evaporator fan on
after dripping (relative to set-
point)
-99... 99 °F/°C
setpoint + F7
72 F9 0 evaporator fan off delay after
compressor off
0... 240 s
if F0 = 2
73 F11 15.0 threshold for condenser fan on 0... 99 °F/°C
differential = 4 °F/2 °C
74 F12 30 condenser fan off delay after
compressor off
0... 240 s
if P4 ≠1
75 F15 0 evaporator fan off time with
compressor off
0... 240 s
if F0 = 2
76 F16 1 evaporator fan on time with
compressor off
0... 240 s
if F0 = 2
N. PAR. DEF. DIGITAL INPUTS MIN... MAX.
77 i0 5 door switch input function 0 = disabled
1 = compressor + evapora-
tor fan off
2 = evaporator fan off
3 = cabinet light on
4 = compressor + evapora-
tor fan off, cabinet light
on
5 = evaporator fan off +
cabinet light on
6 = n/a
78 i1 0 door switch input activation 0 = with contact closed
1 = with contact open
79 i2 30 open door alarm delay -1... 120 min
-1 = disabled
80 i3 15 regulation inhibition maximum
time with door open
-1... 120 min
-1 = until the closing
81 i5 2 multi-purpose input function 0 = disabled
1 = energy saving
2 = iA alarm
3 = key-operated load on
4 = device on/off
5 = Cth alarm
6 = th alarm
82 i6 0 multi-purpose input activation 0 = with contact closed
1 = with contact open
83 i7 0 multi-purpose input alarm delay -1... 120 min
-1 = disabled
if i5 = 5 or 6, compressor on
delay after alarm reset
84 i10 0 door closed consecutive time for
energy saving
0... 999 min
after regulation temperature
< SP
0 = disabled
85 i13 180 number of door openings for de-
frost
0... 240
0 = disabled
86 i14 32 door open consecutive time for
defrost
0... 240 min
0 = disabled
N. PAR. DEF. DIGITAL OUTPUTS MIN... MAX.
87 u1 0 auxiliary output configuration 0 = cabinet light
1 = anti-fog
2 = key-operated load
3 = alarm
4 = door heaters
5 = heater for neutral zone
6 = condenser fan
7 = on/stand-by
8 = second compressor
9 = energy saving
88 u2 0 enable cabinet light and key-
operated load in stand-by
0 = no 1 = yes
manual
89 u4 0 enable alarm output off silencing
the buzzer
0 = no 1 = yes
90 u5 -1.0 threshold for door heaters on -99... 99 °F/°C
differential = 4 °F/2 °C
91 u6 5 anti-fog output on duration 1... 120 min
92 u7 -5.0 neutral zone threshold for heat-
ing (relative to setpoint)
-99... 99 °F/°C
differential = 4 °F/2 °C
setpoint + u7
N. PAR. DEF. ENERGY SAVING (if r5 = 0) MIN... MAX.
93 HE2 0 energy saving maximum duration 1... 999 min
0 = until the door opening
N. PAR. DEF. REAL TIME ENERGY SAVING (if
r5 = 0)
MIN... MAX.
94 H01 0 energy saving time 0... 23 h
95 H02 0 energy saving duration 0... 24 h
96 HEd 7 energy saving day 0 = Monday 1 = Tuesday
2 = Wednesday
3 = Thursday 4 = Friday
5 = Saturday 6 = Sunday
7 = none
N. PAR. DEF. REAL TIME DEFROST (if d8 = 4) MIN... MAX. (h- = disabled)
97 Hd1 h- 1st daily defrost time h-, 1... 24
98 Hd2 h- 2nd daily defrost time h-, 1... 24
99 Hd3 h- 3rd daily defrost time h-, 1... 24
100 Hd4 h- 4th daily defrost time h-, 1... 24
101 Hd5 h- 5th daily defrost time h-, 1... 24
102 Hd6 h- 6th daily defrost time h-, 1... 24
N. PAR. DEF. SAFETIES MIN... MAX.
103 POF 0 enable ON/STAND-BY key 0 = no 1 = yes
104 PAS -19 password -99... 999
N. PAR. DEF. REAL TIME CLOCK MIN... MAX.
105 Hr0 0enable clock 0 = no 1 = yes
N. PAR. DEF. MODBUS MIN... MAX.
106 LA 247 MODBUS address 1... 247
107 Lb 2 MODBUS baud rate 0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
parity even
8 ALARMS
COD. DESCRIPTION RESET REMEDIES
Pr1 cabinet probe alarm automatic - check P0
Pr2 evaporator probe alarm automatic - check probe integrity
Pr3 auxiliary probe alarm automatic - check electrical connection
rtc clock alarm manual set date, time and day of the week
AL low temperature alarm automatic check AA, A1 and A2
AH high temperature alarm automatic check AA, A4 and A5
id open door alarm automatic check i0 e i1
PF power failure alarm manual - touch any key
- check electrical connection
COH high condenser temperature
warning
automatic check C6
CSd high condenser temperature
alarm
manual - switch the device off and on
- check C7
iA multi-purpose input alarm automatic check i5 and i6
Cth compressor thermal switch alarm automatic check i5 and i6
th global thermal switch alarm manual - switch the device off and on
- check i5 and i6
dFd defrost timeout alarm manual - touch any key
- check d2, d3 and d11
9 ELECTRICAL RATINGS
Output Units cULus (UL 60730) CE (EN 60730)
Applied voltage at 60 Hz 120 VAC 240 VAC 240 VAC
K1
compressor
relay
Resistive amperes 12 12 12
Inductive amperes — — 2
Full load amperes 10 10 —
Locked rotor amperes 60 60 —
K2 relay
Resistive amperes 8 8 5
Inductive amperes — — 2
Full load amperes 4.4 2.9 —
Locked rotor amperes 26.4 17.4 —
K3
evaporator
fan relay
Resistive amperes 5 5 5
Inductive amperes — — 1
Full load amperes 1.5 1.5 —
Locked rotor amperes 9 9 —
K4
cabinet
light/
configurable
relay
Resistive amperes 5 5 5
Inductive amperes — — 1
Full load amperes 1.5 1.5 —
Locked rotor amperes 9 9 —
10 TECHNICAL SPECIFICATIONS
Purpose of the control device Function controller
Construction of the control device Built-in electronic device
Container Black, self-extinguishing
Category of heat and fire resistance D
Measurements 75.0 x 33.0 x 74.0 mm (2 15/16 x 1 5/16 x
2 15/16 in)
Mounting methods for the control device To be fitted to a panel, snap-in brackets pro-
vided
Degree of protection provided by the cover-
ing
IP65 (front)
Connection method Removable screw terminal blocks for wires up
to 2,5 mm²
Maximum permitted length for connection cables
Power supply: 10 m (32.8 ft) Analog inputs: 10 m (32.8 ft)
Digital inputs: 10 m (32.8 ft) Digital outputs: 10 m (32.8 ft)
Operating temperature From 32 to 131 °F (from 0 to 55 °C)
Storage temperature From -13 to 158 °F (from -25 to 70 °C)
Operating humidity Relative humidity without condensate from
10 to 90%
Pollution status of the control device 2
Compliance
United States cURus Recognized; File SA32187 CCN SDFY2; FCC Compliant to CFR47, Part
15, Subpart B, Class A limits
Canada cURus Recognized; File SA32187 CCN SDFY8; Industry Canada (IC)
compliant to Canadian ICES-003, Class A limits
Europe
CE Mark – Johnson Controls declares that this product is in compliance with
the essential requirements and other relevant provisions of the EMC
Directive, Low Voltage Directive, and RoHS Directive
Power supply 115... 230 VAC (+10% -15%), 50/60 Hz (±3
Hz), max. 3.2 VA
Grounding methods for the control device None
Rated impulse-withstand voltage 2,5 KV
Over-voltage category II
Software class and structure A
Clock Incorporated secondary lithium battery
Clock drift ≤60 s/month at 77 °F (25 °C)
Clock battery autonomy in the absence of a
power supply
> 24 h at 77 °F (25 °C)
Clock battery charging time 24 h (the battery is charged by the power
supply of the device)
Analog inputs 2 for NTC probes (cabinet probe and evaporator probe)
NTC probes Sensor type ß3435 (10 K@ 77 °F, 25 °C)
Measurement field From -40 to 221 °F (from -40 to 105 °C)
Resolution 1 °F (0.1 °C)
Digital inputs 1 dry contact (door switch)
Dry contact Contact type 5 VDC, 1.5 mA
Power supply None
Protection None
Other inputs Input configurable for analog input (auxiliary probe) or digi-
tal input (multi-purpose input)
Digital outputs 4electro-mechanical relays (compressor, defrost, evapora-
tor fan and auxiliary relay)
Type 1 or Type 2 Actions Type 1
Additional features of Type 1 or
Type 2 actions
C
Displays 3 digits custom display, with function icons
Alarm buzzer Incorporated
Communication ports 1 RS-485 MODBUS subordinate port for BMS
PENN | TC3224N9R | Installation Guide Rev. B | PartNo. 24-7664-03531 | Page 3 of 3 | 07 April 2020
11 PRODUCT WARRANTY
This product is covered by a limited warranty, details of which can be found at
www.johnsoncontrols.com/buildingswarranty
12 SOFTWARE TERMS
Use of the software that is in (or constitutes) this product, or access to the cloud, or hosted services ap-
plicable to this product, if any, is subject to applicable terms set forth at
www.johnsoncontrols.com/techterms. Your use of this product constitutes an agreement to such terms.
13 SINGLE POINT OF CONTACT
APAC Europe NA/SA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT
MANAGEMENT
NO. 32 CHANGJIJANG RD NEW
DISTRICT
WUXI JIANGSU PROVINCE 214028
CHINA
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
14 CONTACT INFORMATION
Contact your local branch office:
www.johnsoncontrols.com/locations
Contact Johnson Controls:
www.johnsoncontrols.com/contact-us
Important
The device must be disposed of according to local regulations governing the collection
of electrical and electronic waste.
This document and the solutions contained therein are the intellectual property of PENN and thus protected by the
Italian Intellectual Property Rights Code (CPI). PENN imposes an absolute ban on the full or partial reproduction and
disclosure of the content other than with the express approval of PENN. The customer (manufacturer, installer or
end-user) assumes all responsibility for the configuration of the device. PENN accepts no liability for any possible er-
rors in this document and reserves the right to make any changes, at any time without prejudice to the essential
functional and safety features of the equipment.
Johnson Controls
507 E. Michigan St.
Milwaukee, WI 53202-5211
USA
www.penncontrols.com

Other Penn Controllers manuals

Penn P216 User manual

Penn

Penn P216 User manual

Penn MR5 Series Service manual

Penn

Penn MR5 Series Service manual

Penn P266 Series User manual

Penn

Penn P266 Series User manual

Penn TC3B23N5V-004 User manual

Penn

Penn TC3B23N5V-004 User manual

Penn A52 Series Service manual

Penn

Penn A52 Series Service manual

Penn P78 Series User manual

Penn

Penn P78 Series User manual

Penn System 450 Series User manual

Penn

Penn System 450 Series User manual

Penn A525 User manual

Penn

Penn A525 User manual

Penn A19 Series Guide

Penn

Penn A19 Series Guide

Penn TC3B22 User manual

Penn

Penn TC3B22 User manual

Penn P66AAB-1 User manual

Penn

Penn P66AAB-1 User manual

Penn TC3222 User manual

Penn

Penn TC3222 User manual

Penn TC3B23 User manual

Penn

Penn TC3B23 User manual

Penn A421 Series User manual

Penn

Penn A421 Series User manual

Penn MR5 Series User manual

Penn

Penn MR5 Series User manual

Penn A421ABC-03C User manual

Penn

Penn A421ABC-03C User manual

Penn TC3203 User manual

Penn

Penn TC3203 User manual

Penn TC3B23 User manual

Penn

Penn TC3B23 User manual

Penn A52 Series User manual

Penn

Penn A52 Series User manual

Penn TC3B21 User manual

Penn

Penn TC3B21 User manual

Penn A19ZBA User manual

Penn

Penn A19ZBA User manual

Penn A421ABD Series User manual

Penn

Penn A421ABD Series User manual

Penn P470 Manual

Penn

Penn P470 Manual

Penn TC3201 User manual

Penn

Penn TC3201 User manual

Popular Controllers manuals by other brands

Telonics Handy Patch MC100 user manual

Telonics

Telonics Handy Patch MC100 user manual

Sagola RC1 instruction manual

Sagola

Sagola RC1 instruction manual

TMS Lite ANGX-1000-CH1-24V user manual

TMS Lite

TMS Lite ANGX-1000-CH1-24V user manual

sisel ENDA ERPA1 Series quick start guide

sisel

sisel ENDA ERPA1 Series quick start guide

Omron OMNUC G5 R88M-K series user manual

Omron

Omron OMNUC G5 R88M-K series user manual

Honeywell 900U02-0100 User and installation manual

Honeywell

Honeywell 900U02-0100 User and installation manual

jablotron GD-06 ALLEGRO manual

jablotron

jablotron GD-06 ALLEGRO manual

HESCH HE 5697 MFC manual

HESCH

HESCH HE 5697 MFC manual

AERMEC CC2 User & installation manual

AERMEC

AERMEC CC2 User & installation manual

Leroy-Somer R452 Installation and Maintenance

Leroy-Somer

Leroy-Somer R452 Installation and Maintenance

Danfoss MCO 305 operating instructions

Danfoss

Danfoss MCO 305 operating instructions

Vega VEGATOR 131 operating instructions

Vega

Vega VEGATOR 131 operating instructions

EUROSTER UNI4 user manual

EUROSTER

EUROSTER UNI4 user manual

Meridian Sooloos Setup guide

Meridian

Meridian Sooloos Setup guide

Miboxer Mi Light FUT035SA user manual

Miboxer

Miboxer Mi Light FUT035SA user manual

Fisher 656 instruction manual

Fisher

Fisher 656 instruction manual

ez-wheel SWD Starter Kit instruction manual

ez-wheel

ez-wheel SWD Starter Kit instruction manual

Onbon Y Series user manual

Onbon

Onbon Y Series user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.