Raychem WinterGard self-regulating heating cables provide
convenient, reliable freeze protection for a wide variety of pro-
fessionally installed residential and commercial water-pipe and
roof-and-gutter de-icing applications in nonhazardous areas.
This data sheet is designed to assist in cable and accessory
selection and basic circuit design of pipe-freeze-prevention
applications.
Complete design guidelines, installation instructions, and safety
information are provided in the Commercial and Residential
Self-Regulating Heating Products Application and Design Guide
(H53585), the H900 Power Connection Kit, the H908 Plug-in
Power Connection Kit, and the H921 120-V ground-fault protect-
ed junction box.
For detailed information on roof and gutter de-icing applica-
tions, please refer to the WinterGard Wet Design, Installation
and Maintenance Guide (H56804).
16 AWG
bus wires
Conductive
core (black)
Inner jacket
(blue or red)
Tinned
copper braid
Water-proof
outer jacket
(black)
H612, H622 only
Construction
Pipe Applications
WinterGard systems must be installed correctly to
ensure proper operation and to prevent shock or
fire. Carefully read and follow the Commercial and
Residential Self-Regulating Heating Products
Application and Design Guide and the H900 series
connection kit installation instructions.
• Use only in ordinary (nonhazardous) areas. Do not
expose to any chemicals, oil or grease.
• In wet areas, use only WinterGard Wet.
• To minimize the danger of fire from sustained elec-
trical arcing if the heating cable is damaged or
improperly installed, and to comply with the
requirements of Pentair Thermal Management,
agency approvals, and national electrical codes,
ground-fault equipment protection must be used
on each heating cable branch circuit. Arcing may
not be stopped by conventional circuit protection.
• This selection guide does not take the place of the
installation instructions included in the
Commercial and Residential Self-Regulating
Heating Products Application and Design Guide and
in the H900 series accessory kits.
• System approvals and performance are based on
the use of only H900 series accessories with
WinterGard heating cables. These accessories
must be used. Do not substitute parts.
Water pipes in dry areas: H311/H611/H621
Water pipes in wet areas and refrigeration
condensate drains:
H612/H622
WARNING:
Product Specifications and Data
WinterGard
H311100
H311250
WinterGard Plus
H611050
H611100
H611250
WinterGard Plus
H621050
H621100
H621250
WinterGard Wet
H612050
H612100
H612250
H612500
H6121000
WinterGard Wet
H622050
H622100
H622250
H622500
H6221000
Service voltage 120 V 120 V 240 V 120 V 240 V
Power output at 40°F (W/ft) 3 6 6 6 6
Power output in refrigeration condensate
drains at 32°F (W/ft) n/a n/a n/a 8 8
Weight per 100 ft (lb) 6 6 6 7 7
Nom. cable width (in) 0.380 0.380 0.380 0.415 0.415
Nom. cable thickness (in) 0.180 0.180 0.180 0.215 0.215
Bus wire gauge (AWG) 16 16 16 16 16
Braid wire gauge equivalent (AWG) 14 14 14 14 14
Insulating jacket type Modified polyolefin
Outer jacket type n/a n/a n/a Modified polyolefin
Maximum exposure temp. (°F) 150 150 150 150 150
Environment Use only in ordinary (nonhazardous) areas. Do not expose to any chemicals.
Agency approvals*1, 3 1, 3 1, 3 1, 2, 3 1, 2, 3
*1 = UL System Listed 718K Pipe Heating Cable; 2 = UL System Listed 877Z De-Icing and Snow Melting Equipment; 3 = CSA Certified LR21133
Selection Guide (for PiPe freeze Protection APPlicAtionS)
WinterGard, WinterGard Plus, WinterGard Wet
2
WinterGard Selection Guide
Circuit Sizing Guide
Catalog References
Catalog Numbers
Reel length (ft):
50
100
250
500
1000
Cable construction:
1 = Braided metal
shield only
2 = Waterproof polyolefin
outer jacket over
metal shield
Nominal voltage:
1 = 120 Vac
2 = 240 Vac
Nominal wattage
(watts/ft):
3
6
H X X X XXX
0 20 40
0
2
4
6
8
10
60 80 100
Pipe temperature (F)
Power output (W/ft)
H6XX
H3XX
WinterGard Power Temperature Curves
Circuit breaker
rating (A)
Maximum heater length (ft)
per circuit at start-up temperature
Heating cable type 0°F 32°F 40°F
WinterGard 120 V
H311 on pipe
15 150 250
20 200 250
30 250 250
WinterGard Plus 120 V
H611 on pipe
15 125 150
20 140 195
30 200 200
WinterGard Plus 240 V
H621 on pipe
15 200 255
20 250 340
30 375 400
WinterGard Wet 120 V
H612 on pipe
15 125 150
20 140 195
30 200 200
WinterGard Wet 120 V
H612 in refrigeration
condensate drains
15 100 125
20 125 165
30 150 200
WinterGard Wet 240 V
H622 on pipe
15 200 255
20 250 340
30 375 400
WinterGard Wet 240 V
H622 in refrigeration
condensate drains
15 200 250
20 250 320
30 305 400
Note: Maximum circuit lengths are based on start-up load. Steady-state amps per foot is dependent
upon heating cable temperature.
Cable type
Catalog
number
Cable
construc-
tion*
Watts/ft
(on 40°F
metal pipe)
Nominal
voltage
Package
type**
WinterGard H311 H311100 1 3 120 TruckPak®box
H311250 1 3 120 250-ft reel
WinterGard Plus
H611
H611050 1 6 120 50-ft box
H611100 1 6 120 TruckPak box
H611250 1 6 120 250-ft reel
WinterGard Plus
H621
H621050 1 6 240 50-ft box
H621100 1 6 240 TruckPak box
H621250 1 6 240 250-ft reel
WinterGard Wet H612 H612050 2 6 120 50-ft box
H612100 2 6 120 TruckPak box
H612250 2 6 120 250-ft reel
H612500 2 6 120 500-ft reel
H6121000 2 6 120 1000-ft reel
WinterGard Wet H622 H622050 2 6 240 50-ft box
H622100 2 6 240 TruckPak box
H622250 2 6 240 250-ft reel
H622500 2 6 240 500-ft reel
H6221000 2 6 240 1000-ft reel
*Construction: 1 = braided metal shield only; 2 = waterproof polyolefin outer jacket over braid.
** TruckPak consists of 100-foot cable reel, 2 power connections, 1 splice/tee kit, 1 roll application tape, 10 "Electric
Traced" labels.
2 / 4THERMAL MANAGEMENT SOLUTIONS EN-RaychemWinterGardSelection-AR-H5523509/13
3
WinterGard Selection Guide
Selection Tables
Use one of the tables below to help select
the correct WinterGard heating cable for
your application. (Consult the
Commercial and Residential Application
and Design Guide or H900/H908
Installation Instructions for complete sys-
tem design information.)
Use Table 1 to select heating cables for
insulated metal pipes. Use Table 2 for
insulated plastic pipes.
Read across the table to find your pipe
diameter, then drop down to the line corre-
sponding to the lowest air temperature for
that application and the correct insulation
thickness. The cell at that intersection has
a particular shade and may have a num-
ber.
The shade indicates which heating cable to
use (key to the shades appears to the left of
Table 1). A number in the cell represents
the spiraling ratio (feet of heating cable per
foot of pipe). If no number appears in the
cell, straight trace the pipe. If a number
does appear in the cell, spiral trace the
pipe. If your spiraling ratio is 2.0,
multiple-trace the pipe using two straight
traces at the 4 o’clock and 8 o’clock posi-
tions.
If your spiraling ratio is 3.0, multiple-trace
the pipe using three straight traces at the
11 o’clock or 1 o’clock position and at the 4
o’clock and 8 o’clock positions.
1.3
Insulation
thickness
Lowest
air temp.
0°F
–20°F
–40°F
Pipe diameter (inches)
0.5 in
1.0 in
1.5 in
0.5 in
1.0 in
1.5 in
2.0 in
0.5 in
1.0 in
1.5 in
0.50 0.75 1.00 1.25 1.50 2.00 2.50 3.00 4.00 6.00
2.0 in
1.8
1.1 1.3 1.5
1.1 1.5
1.1
1.9
1.4
1.1
1.8
1.1 1.2
1.1 1.4
1.4 1.7 2.0 3.0
3.0
Insulation
thickness
Lowest
air temp.
0°F
–20°F
–40°F
Pipe diameter (inches)
0.5 in
1.0 in
1.5 in
0.5 in
1.0 in
1.5 in
2.0 in
0.5 in
1.0 in
1.5 in
0.50 0.75 1.00 1.25 1.50 2.00 2.50 3.00 4.00 6.00
2.0 in
2.0
1.7 3.0
1.2 1.6
1.2
1.1 1.3 1.5
1.4 1.8
1.1 1.3
3.0
1.7
1.4
3.0
1.8
1.8
1.1 1.2
1.11.1 1.5
1.9 3.0
1.8 2.0
1.2 1.4
3.0 3.0
1.1 1.2 1.4 1.6
1.4 1.7
1.1 1.3
1.1 1.2
2.0 3.0
Example 1
Pipe = 2-inch-diameter metal
Lowest air temperature = 0°F
Insulation thickness = 1 inch
Cable length and type = 1 foot of
WinterGard H311 per foot of pipe
Example 2
Pipe = 2.5-inch-diameter plastic
Lowest air temperature = –20°F
Insulation thickness = 1 inch
Cable length = 1.2 feet of WinterGard Plus
H611, H621 or WinterGard Wet H612, H622
H311 WinterGard
H611/621 WinterGard Plus
H612/H622 WinterGard Wet
Increase insulation thickness.
Key to Tables 1 and 2 Table 1. For metal pipes with fiberglass insulation or equivalent (based on 40°F maintain)
Table 2. For plastic pipes with fiberglass insulation or equivalent (based on 40°F maintain)
3 / 4THERMAL MANAGEMENT SOLUTIONS EN-RaychemWinterGardSelection-AR-H5523509/13

This manual suits for next models

17

Other Pentair Cables And Connectors manuals

Pentair TraceTek TT1100-OHP User manual

Pentair

Pentair TraceTek TT1100-OHP User manual

Pentair Raychem CCON25-100 User manual

Pentair

Pentair Raychem CCON25-100 User manual

Pentair Raychem FrostGuard User manual

Pentair

Pentair Raychem FrostGuard User manual

Pentair CodeLine 40E60 User manual

Pentair

Pentair CodeLine 40E60 User manual

Pentair DigiTrace E104 User manual

Pentair

Pentair DigiTrace E104 User manual

Pentair Raychem E-100-A User manual

Pentair

Pentair Raychem E-100-A User manual

Pentair Raychem T-100 User manual

Pentair

Pentair Raychem T-100 User manual

Pentair Raychem H900 User manual

Pentair

Pentair Raychem H900 User manual

Pentair Raychem C25-100-FHP User manual

Pentair

Pentair Raychem C25-100-FHP User manual

Pentair Raychem EMK-XP User manual

Pentair

Pentair Raychem EMK-XP User manual

Pentair Raychem JBS-100-ECP-A User manual

Pentair

Pentair Raychem JBS-100-ECP-A User manual

Pentair Raychem C25-100 User manual

Pentair

Pentair Raychem C25-100 User manual

Pentair Raychem FrostGuard 240 V User manual

Pentair

Pentair Raychem FrostGuard 240 V User manual

Pentair Raychem C25-21 User manual

Pentair

Pentair Raychem C25-21 User manual

Pentair Raychem S-150 User manual

Pentair

Pentair Raychem S-150 User manual

Popular Cables And Connectors manuals by other brands

Amazon B07RQ32D9H quick start guide

Amazon

Amazon B07RQ32D9H quick start guide

Mennekes AMTRON Compact 2.0 installation manual

Mennekes

Mennekes AMTRON Compact 2.0 installation manual

Hall Research Technologies Mini-Cat UV4-S user manual

Hall Research Technologies

Hall Research Technologies Mini-Cat UV4-S user manual

Anslut 417049+ operating instructions

Anslut

Anslut 417049+ operating instructions

Johnson Controls Metasys N2 manual

Johnson Controls

Johnson Controls Metasys N2 manual

Russound A-CB4 IR instruction manual

Russound

Russound A-CB4 IR instruction manual

HyperX Coiled Cable quick start guide

HyperX

HyperX Coiled Cable quick start guide

Philips SWV2141W Specifications

Philips

Philips SWV2141W Specifications

ODU AMC Assembly instruction

ODU

ODU AMC Assembly instruction

THORLABS M490F3 quick start guide

THORLABS

THORLABS M490F3 quick start guide

Renkforce 1404059 operating instructions

Renkforce

Renkforce 1404059 operating instructions

Lindy 38062 user manual

Lindy

Lindy 38062 user manual

HEIDENHAIN EIB 3392S operating instructions

HEIDENHAIN

HEIDENHAIN EIB 3392S operating instructions

Minicom 1VS21004 user guide

Minicom

Minicom 1VS21004 user guide

Spectra Premium FPW3 TECHNICAL NOTICE

Spectra Premium

Spectra Premium FPW3 TECHNICAL NOTICE

Sennheiser H-6 manual

Sennheiser

Sennheiser H-6 manual

LEONI MegaLine Connect45 Installation instruction

LEONI

LEONI MegaLine Connect45 Installation instruction

VORAGO CAB-308 quick guide

VORAGO

VORAGO CAB-308 quick guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.