EnglishDeutsch
 logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Pepperl+Fuchs
  6. •
  7. Industrial Equipment
  8. •
  9. Pepperl+Fuchs VisuNet FLX User manual

Pepperl+Fuchs VisuNet FLX User manual

Other Pepperl+Fuchs Industrial Equipment manuals

Pepperl+Fuchs VisuNet FLX User manual

Pepperl+Fuchs

Pepperl+Fuchs VisuNet FLX User manual

Pepperl+Fuchs PXV100AQS-F200-R4-V19- 6011 User manual

Pepperl+Fuchs

Pepperl+Fuchs PXV100AQS-F200-R4-V19- 6011 User manual

Pepperl+Fuchs LS611 Series User manual

Pepperl+Fuchs

Pepperl+Fuchs LS611 Series User manual

Pepperl+Fuchs ECHO-D Reference guide

Pepperl+Fuchs

Pepperl+Fuchs ECHO-D Reference guide

Pepperl+Fuchs PGV Series User manual

Pepperl+Fuchs

Pepperl+Fuchs PGV Series User manual

Pepperl+Fuchs PCV F200-B6-V15B Series User manual

Pepperl+Fuchs

Pepperl+Fuchs PCV F200-B6-V15B Series User manual

Pepperl+Fuchs 1001B Series User manual

Pepperl+Fuchs

Pepperl+Fuchs 1001B Series User manual

Pepperl+Fuchs VisuNet Control Center 6 User manual

Pepperl+Fuchs

Pepperl+Fuchs VisuNet Control Center 6 User manual

Pepperl+Fuchs Absolute Rotary Encoder User manual

Pepperl+Fuchs

Pepperl+Fuchs Absolute Rotary Encoder User manual

Pepperl+Fuchs FieldConnex KFD2-BR-1.PA.1500 User manual

Pepperl+Fuchs

Pepperl+Fuchs FieldConnex KFD2-BR-1.PA.1500 User manual

Pepperl+Fuchs ECHO-D-NA Reference guide

Pepperl+Fuchs

Pepperl+Fuchs ECHO-D-NA Reference guide

Pepperl+Fuchs KFU8-DW-1.D User manual

Pepperl+Fuchs

Pepperl+Fuchs KFU8-DW-1.D User manual

Pepperl+Fuchs KCDO-LGH User manual

Pepperl+Fuchs

Pepperl+Fuchs KCDO-LGH User manual

Pepperl+Fuchs PGV -F213-B16-1.5M Series User manual

Pepperl+Fuchs

Pepperl+Fuchs PGV -F213-B16-1.5M Series User manual

Pepperl+Fuchs 1001A Series User manual

Pepperl+Fuchs

Pepperl+Fuchs 1001A Series User manual

Pepperl+Fuchs 7500 Series User manual

Pepperl+Fuchs

Pepperl+Fuchs 7500 Series User manual

Pepperl+Fuchs KFD2-CD-1.32 Series User manual

Pepperl+Fuchs

Pepperl+Fuchs KFD2-CD-1.32 Series User manual

Pepperl+Fuchs LGS Series User manual

Pepperl+Fuchs

Pepperl+Fuchs LGS Series User manual

Pepperl+Fuchs M-LBAS-IA1. E Series User manual

Pepperl+Fuchs

Pepperl+Fuchs M-LBAS-IA1. E Series User manual

Pepperl+Fuchs KF DWB-1.D Series User manual

Pepperl+Fuchs

Pepperl+Fuchs KF DWB-1.D Series User manual

Pepperl+Fuchs R2-SP-N Series User manual

Pepperl+Fuchs

Pepperl+Fuchs R2-SP-N Series User manual

Pepperl+Fuchs IQT-F116-R4-V1 User manual

Pepperl+Fuchs

Pepperl+Fuchs IQT-F116-R4-V1 User manual

Pepperl+Fuchs FD0-VC-Ex4.FF User manual

Pepperl+Fuchs

Pepperl+Fuchs FD0-VC-Ex4.FF User manual

Pepperl+Fuchs MLV11 Series User manual

Pepperl+Fuchs

Pepperl+Fuchs MLV11 Series User manual

Popular Industrial Equipment manuals by other brands

ABB Unifix AD Instruction handbook

ABB

ABB Unifix AD Instruction handbook

Mark 7 Evolution user manual

Mark 7

Mark 7 Evolution user manual

Husky HyPET Original instructions

Husky

Husky HyPET Original instructions

bora PM-1800 user manual

bora

bora PM-1800 user manual

Grizzly T32428 owner's manual

Grizzly

Grizzly T32428 owner's manual

Siemens 8MF1 Series operating instructions

Siemens

Siemens 8MF1 Series operating instructions

ABB HT610965 Operation manual

ABB

ABB HT610965 Operation manual

ABB SafeLink Installation and operating instructions

ABB

ABB SafeLink Installation and operating instructions

Phoenix PHX-150 user guide

Phoenix

Phoenix PHX-150 user guide

ABB A165-L32 Operation manual

ABB

ABB A165-L32 Operation manual

ABB HT842936 Operation manual

ABB

ABB HT842936 Operation manual

Hermetica 10 Series user manual

Hermetica

Hermetica 10 Series user manual

HORNER OEE Solution manual

HORNER

HORNER OEE Solution manual

Hammerhead HG375 parts manual

Hammerhead

Hammerhead HG375 parts manual

SCHUNK VERO-S NSE-A3 138 Assembly and operating manual

SCHUNK

SCHUNK VERO-S NSE-A3 138 Assembly and operating manual

ABB HT566657 Operation manual

ABB

ABB HT566657 Operation manual

Webasto GSE CAN installation guide

Webasto

Webasto GSE CAN installation guide

ABB HT614003 Operation manual

ABB

ABB HT614003 Operation manual

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2026 Manuals.Online. All Rights Reserved.

Instruction Manual
1. Marking
VisuNet FLX – System with Enclosure
RemoteMonitorRM-320S-*
PersonalComputerPC-320S-*
EquipmentprotectionlevelGc
ATEXcertificate:PF21CERT6290X
ATEXmarking:1II3GExec[ic]IICT4Gc
EquipmentprotectionlevelDc
ATEXcertificate:PF21CERT6290X
ATEXmarking:1II3DExtc[ic]IIICT85°CDc
VisuNet FLX – System with Enclosure
DirectMonitorDM-320S-*
EquipmentprotectionlevelGc
ATEXcertificate:PF21CERT6290X
ATEXmarking:1II3GExecIICT4Gc
EquipmentprotectionlevelDc
ATEXcertificate:PF21CERT6290X
ATEXmarking:1II3DExtcIIICT85°CDc
The*-markedlettersofthetypecodeareplaceholdersforversionsofthe
device.
Pepperl+FuchsGroup
Lilienthalstraße200,68307Mannheim,Germany
Internet:www.pepperl-fuchs.com
2. Validity
Specificprocessesandinstructionsinthisinstructionmanualrequire
specialprovisionstoguaranteethesafetyoftheoperatingpersonnel.
3. Reference to Further Documentation
Observelaws,standards,anddirectivesapplicabletotheintendeduse
andtheoperatinglocation.ObserveDirective1999/92/ECinrelationto
hazardousareas.
Thecorrespondingdatasheets,manuals,declarationsofconformity,EU-
typeexaminationcertificates,certificates,andcontroldrawingsif
applicable(seedatasheet)areanintegralpartofthisdocument.Youcan
findthisinformationunderwww.pepperl-fuchs.com.
Duetoconstantrevisions,documentationissubjecttopermanentchange.
Pleasereferonlytothemostup-to-dateversion,whichcanbefoundunder
www.pepperl-fuchs.com.
4. Target Group, Personnel
Responsibilityforplanning,assembly,commissioning,operation,
maintenance,anddismountinglieswiththeplantoperator.
Thepersonnelmustbeappropriatelytrainedandqualifiedinordertocarry
outmounting,installation,commissioning,operation,maintenance,and
dismountingofthedevice.Thetrainedandqualifiedpersonnelmusthave
readandunderstoodtheinstructionmanual.
5. Intended Use
Thedeviceisonlyapprovedforappropriateandintendeduse.Ignoring
theseinstructionswillvoidanywarrantyandabsolvethemanufacturer
fromanyliability.
TheVisuNetFLXSystemsaredesignedforZone2/22andnon-Ex
applications.Thedifferentmountingandconfiguringoptionsleadtothe
highestapplicationflexibility.Duetoafullymodulardesign,thenew
platform,whichisgearedtotheneedsofthe(petro-)chemicaland
pharmaceuticalindustries,theHMIscanbeconfiguredtofitexactlyand
enablessimpleandfastadjustmentsinthefield.
Usethedeviceonlywithinthespecifiedambienttemperaturerange.
Usethedeviceonlywithinthespecifiedambientandoperatingconditions.
Taketheintendeduseoftheconnecteddevicesfromthecorresponding
documentation.
Taketheintendeduseoftheinstalleddevicesfromthecorresponding
documentation.
Thedeviceisanelectricalapparatusforhazardousareas.
Thedeviceisnotsuitableforseparatinghazardousareas.
DevicesforwhichspecificconditionsofuseapplyhavetheXmarkingat
theendofthecertificatenumber.
Onlyusethedevicestationary.
6. Improper Use
Protectionofthepersonnelandtheplantisnotensuredifthedeviceisnot
usedaccordingtoitsintendeduse.
Thedeviceisnotsuitabletoseparateintrinsicallysafecircuitsfromnon-
intrinsicallysafecircuits.
Thedeviceisnotsuitableforseparatinghazardousareas.
7. Mounting and Installation
Priortomounting,installation,andcommissioningofthedeviceyou
shouldmakeyourselffamiliarwiththedeviceandcarefullyreadthe
instructionmanual.
Donotstaybelowtheopendevice.Inordertoavoidpersonalinjuriesor
propertydamage,makeappropriateprovisionsforthemountingand
maintenanceprocedures.
Usemountingmaterialswhicharesuitabletosecurethedevicesafely.
Usemountingmaterialsthatfitthenatureofthemountingsurface.
Onlyuseaccessoriesspecifiedbythemanufacturer.
Mountthedeviceinaweatherprooflocation.
Ensurethattheoperatinglocationhasasufficientfloorloadcapacity.
Ifmountingtheenclosureonconcreteuseexpansionanchors.When
mountingtheenclosuretoasteelframeworkusevibrationresistant
mountingmaterial.
Ensurethatallfastenersarepresent.
Observethetighteningtorqueofthescrews.
Protectthedeviceagainstlong-termorexcessivemechanicalvibrations.
Thedeviceisheavy.Inordertoavoidpersonalinjuriesorproperty
damage,makeappropriateprovisionsforthemountingprocedure.
Donotmountthedeviceatlocationswhereanaggressiveatmosphere
maybepresent.
Donotdamagethebreatherdrain.
Donotcoverthebreatherdrain.
ObservetheinstallationinstructionsaccordingtoIEC/EN60079-14.
ObservetheinstallationinstructionsaccordingtoIEC/EN60079-25.
Ifthedevicehasalreadybeenoperatedingeneralelectricalinstallations,
thedevicemaysubsequentlynolongerbeinstalledinelectrical
installationsusedincombinationwithhazardousareas.
Ensurethattheequipotentialbondingconnectionsareingoodcondition,
andarenotdamagedorcorroded.
Ensurethattheterminalsareingoodconditionandarenotdamagedor
corroded.
Whenconnectingintrinsicallysafedeviceswithintrinsicallysafecircuitsof
associatedapparatus,observethemaximumpeakvalueswithregardto
explosionprotection(verificationofintrinsicsafety).Observethe
standardsIEC/EN60079-14orIEC/EN60079-25.
Provideatransientprotection.Ensurethatthepeakvalueofthetransient
protectiondoesnotexceed140%oftheratedvoltage.
Thedevicemustbeinstalledandoperatedonlyinacontrolled
environmentthatensuresapollutiondegree2(orbetter)accordingto
IEC/EN60664-1.
Thedevicemustbedisconnectedfromthepowersupplypriorto
installationandmaintenance.Thepowersupplymaybeactivatedonly
afterallthecircuitsrequiredforoperationhavebeenfullyassembledand
connected.
OnlyconnectadevicethatisinaccordancewithIEC/EN60950-1andis
designedassafetyextra-lowprotectivevoltage(SELV)system.
Protectthecircuitagainstovervoltage(e.g.,lightning).
Thedeviceprovidesagroundingterminaltowhichanequipotential
bondingconductorwithaminimumcrosssectionof4mm²mustbe
connected.
Requirements in Relation to Intrinsic Safety
IfcircuitswithtypeofprotectionExiareoperatedwithnon-intrinsically
safecircuits,theymustnolongerbeusedascircuitswithtypeof
protectionExi.
Observethemaximumvaluesofthedevice,whenconnectingthedevice
tointrinsicallysafeapparatus.
Keeptheseparationdistancesbetweenallnon-intrinsicallysafecircuits
andintrinsicallysafecircuitsaccordingtoIEC/EN60079-14.
Observethecomplianceoftheseparationdistancesbetweentwo
adjacentintrinsicallysafecircuitsaccordingtoIEC/EN60079-14.
Circuitsofintrinsicallysafeapparatuscanbeledintohazardousareas,
wherebyspecialattentionmustbepaidtomaintainingseparation
distancestoallnon-intrinsicallysafecircuitsaccordingtotherequirements
inIEC/EN60079-14.
ObservethegroundingrequirementsfortypeofprotectionExiaccording
toIEC/EN60079‑14.
Forintrinsicallysafecircuits,thedielectricstrengthoftheinsulationagainst
otherintrinsicallysafecircuitsandagainsttheshieldmustbe
atleast500VaccordingtoIEC/EN60079-14.
Equipotentialbondingmustbeachievedalongtheintrinsicallysafe
circuits.
Requirements for Cable Glands
Installthecablesandthecableglandsinaccordancewith
IEC/ENIEC60079-0andIEC/EN60079-14.
Onlyusecablesandconnectionlineswithatemperaturerange
appropriatetotheapplication.
Useonlyoneconnectionlineperopening.
Useonlyoneconductorperterminal.
Adjustthesealingelementofthecableglandtothediameterofthecables
andconnectionlinesused.
Observethetighteningtorqueofthecableglands.
DOCT-7048C/2021-10 1/2
Tightenallcableglandswiththeappropriatetorque.
Ensurethatallcableglandsareingoodconditionandaresecurely
tightened.
Closeallunusedcableglandswiththeappropriatesealingplugs.
Requirements for Cables and Connection Lines
Observethemaximumpermissiblelengthofcablesandconnectionlines.
Thedielectricstrengthoftheinsulationmustbeatleast500Vaccordingto
IEC/EN60079-14.
Observethepermissiblecorecrosssectionoftheconductor.
Theinsulationstrippinglengthmustbeconsidered.
Wheninstallingtheconductorstheinsulationmustreachuptothe
terminal.
Whenusingstrandedconductors,crimpwireendferrulesonthe
conductorends.
Observetheminimumbendingradiusoftheconductors.
Thenominalcorecrosssectionofaconnectedconductoris2.5mm2
(solid,finelystranded,andstranded).
Unusedcablesandconnectionlinesmustbeeitherconnectedtoterminals
orsecurelytieddownandisolated.
Installthecablesandconnectionlinesinsuchawaythattheyare
protectedfromultravioletradiation.
Installcablesandcableglandsinawaythattheyarenotexposedto
mechanicalhazards.
Equipotentialbondingmustbeachievedalongthefieldcircuits.
Requirements in Relation to Electrostatics
Avoidelectrostaticchargeswhichcouldresultinelectrostaticdischarges
whileinstalling,operating,ormaintainingthedevice.
Avoidinadmissiblyhighelectrostaticchargeofthecablesandconnection
lines.
Includethemetalhousingcomponentsintheequipotentialbonding.
Anelectrostaticchargeposesanignitionhazardincaseofdischarge.
Includethefastenersintheequipotentialbonding.
Requirements for Surrounding Enclosures
Ifadditionalsurroundingenclosuresarerequired,thefollowingpointsmust
beconsideredduringinstallation:
lDegreeofprotectionaccordingtoIEC/EN60529
lResistancetolightaccordingtoIEC/EN60079-0
lResistancetoimpactaccordingtoIEC/EN60079-0
lResistancetochemicalagentsaccordingtoIEC/EN60079-0
lThermalenduranceaccordingtoIEC/EN60079-0
lElectrostaticsaccordingtoIEC/EN60079-0
Mountthesurroundingenclosureinawaythatallhousingoutlets,e.g.,
cableglandsandbreatherdrainsfacedownwards.
Whentheenclosurecoverisfitted,ensurethatallfastenersarefully
tightened.
Mountthedevicesothatitcomplieswiththespecifieddegreeof
protectionaccordingtoIEC/EN60529.
Forcableglandsonlyuseincomingcablediametersoftheappropriate
size.
Ensurethatthesurroundingenclosureisnotdamaged,distorted,or
corroded.
Ensurethatallsealsareclean,undamaged,andcorrectlyfitted.
Tightenallscrewsofthesurroundingenclosure/surroundingenclosure
coverwiththeappropriatetorque.
Closeallunusedenclosureholeswiththeappropriatestoppingplugs.
8. Operation, Maintenance, Repair
Priortousingtheproductmakeyourselffamiliarwithit.Readthe
instructionmanualcarefully.
Donotstaybelowtheopendevice.Inordertoavoidpersonalinjuriesor
propertydamage,makeappropriateprovisionsforthemountingand
maintenanceprocedures.
ObserveIEC/EN60079-17formaintenanceandinspection.
Donotuseadamagedorpolluteddevice.
Ifthereisadefect,thedevicemustberepairedbyPepperl+Fuchs.
Thedevicemustnotberepaired,changed,ormanipulated.Incaseof
failure,alwaysreplacethedevicewithanoriginaldevice.
Observethewarningmarkings.
Donotremovethewarningmarkings.
Ifthedeviceisinstalledinpotentiallyexplosivedustatmosphere,remove
dustlayerswhichexceed5mminregularintervals.
Removethedustbeforeopeningthesurroundingenclosure.
Connectionordisconnectionofenergizednon-intrinsicallysafecircuitsis
onlypermittedintheabsenceofapotentiallyexplosiveatmosphere.
Ifcleaningisnecessarywhilethedeviceislocatedinahazardousarea,in
ordertoavoidelectrostaticchargingonlyuseacleandampcloth.
Thedevicecangetveryhotduringoperation.Toprotectthedevicefrom
excessiveheating,observetherequiredclearancesandsufficient
ventilationwheninstallingthedevice.
9. Delivery, Transport, Disposal
Checkthepackagingandcontentsfordamage.
Checkifyouhavereceivedeveryitemandiftheitemsreceivedarethe
onesyouordered.
Keeptheoriginalpackaging.Alwaysstoreandtransportthedeviceinthe
originalpackaging.
Storethedeviceinacleananddryenvironment.Thepermittedambient
conditionsmustbeconsidered,seedatasheet.
Thedevice,built-incomponents,packaging,andanybatteriescontained
withinmustbedisposedincompliancewiththeapplicablelawsand
guidelinesoftherespectivecountry.
DOCT-7048C/2021-10 2/2