Pilz P1HZ X1 User manual

P1HZ X1
Operating Manual-20067-EN-09
-Safety relays

Preface
This document is the original document.
Where unavoidable, for reasons of readability, the masculine form has been selected when
formulating this document. We do assure you that all persons are regarded without discrim-
ination and on an equal basis.
All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made
for the user's internal purposes. Suggestions and comments for improving this documenta-
tion will be gratefully received.
Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,
SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks
of Pilz GmbH & Co. KG in some countries.
SD means Secure Digital

Contents
Operating Manual P1HZ X1
20067-EN-09 | 3
Introduction ............................................................................................................................4
Validity of documentation ..........................................................................................................4
Using the documentation ..........................................................................................................4
Definition of symbols .................................................................................................................4
Safety ......................................................................................................................................5
Intended use .............................................................................................................................5
Safety regulations .....................................................................................................................6
Safety assessment....................................................................................................................6
Use of qualified personnel.........................................................................................................6
Warranty and liability.................................................................................................................6
Disposal ....................................................................................................................................6
For your safety ..........................................................................................................................7
Unit features ...........................................................................................................................7
Safety features .......................................................................................................................7
Block diagram/terminal configuration .................................................................................8
Function Description .............................................................................................................8
Operating modes.......................................................................................................................8
Timing diagram .........................................................................................................................9
Installation ..............................................................................................................................9
Wiring ......................................................................................................................................10
Preparing for operation .........................................................................................................10
Operation ................................................................................................................................11
Status indicators........................................................................................................................11
Faults – Interference ..............................................................................................................11
Dimensions in mm .................................................................................................................12
Technical details ....................................................................................................................12
Safety characteristic data..........................................................................................................15
Supplementary data ...............................................................................................................16
Service life graph ......................................................................................................................16
Order reference ......................................................................................................................17
EC declaration of conformity ................................................................................................17
UKCA-Declaration of Conformity .........................................................................................17

P1HZ X1
Operating Manual P1HZ X1
20067-EN-09 | 4
Introduction
Validity of documentation
This documentation is valid for the product P1HZ X1. It is valid until new documentation is
published.
This operating manual explains the function and operation, describes the installation and
provides guidelines on how to connect the product.
Using the documentation
This document is intended for instruction. Only install and commission the product if you
have read and understood this document. The document should be retained for future ref-
erence.
Definition of symbols
Information that is particularly important is identified as follows:
DANGER!
This warning must be heeded! It warns of a hazardous situation that poses
an immediate threat of serious injury and death and indicates preventive
measures that can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation that could
lead to serious injury and death and indicates preventive measures that can
be taken.
CAUTION!
This refers to a hazard that can lead to a less serious or minor injury plus
material damage, and also provides information on preventive measures
that can be taken.
NOTICE
This describes a situation in which the product or devices could be dam-
aged and also provides information on preventive measures that can be
taken. It also highlights areas within the text that are of particular import-
ance.

P1HZ X1
Operating Manual P1HZ X1
20067-EN-09 | 5
INFORMATION
This gives advice on applications and provides information on special fea-
tures.
Safety
Intended use
The two-hand control relay P1HZ X1 meets the requirements of EN ISO13851 Type IIIA. It
forces the operator to keep his hands outside the hazardous area during the hazardous
movement. It is designed for use in two-hand control devices. Please note the type of two-
hand control devices as stated in the relevant C standard.
NOTICE
The two-hand control relay may not be used on press controllers. It is only
suitable for use where the risk analysis has established a low level of risk
(e.g. PL c (Cat. 1) in accordance with EN ISO 13849-1).
Improper use
The following is deemed improper use in particular:
}Any component, technical or electrical modification to the product,
}Use of the product outside the areas described in this operating manual,
}Use of the product outside the technical details (see chapter entitled Technical
Details [ 12]).
NOTICE
EMC-compliant electrical installation
The product is designed for use in an industrial environment. The product
may cause interference if installed in other environments. If installed in other
environments, measures should be taken to comply with the applicable
standards and directives for the respective installation site with regard to in-
terference.

P1HZ X1
Operating Manual P1HZ X1
20067-EN-09 | 6
Safety regulations
Safety assessment
Before using a device, a safety assessment in accordance with the Machinery Directive is
required.
The product as an individual component fulfils the functional safety requirements in accord-
ance with EN ISO 13849 and ENIEC62061. However, this does not guarantee the func-
tional safety of the overall plant/machine. To achieve the relevant safety level of the overall
plant/machine’s required safety functions, each safety function needs to be considered sep-
arately.
Use of qualified personnel
The products may only be assembled, installed, programmed, commissioned, operated,
maintained and decommissioned by persons who are competent to do so.
A competent person is a qualified and knowledgeable person who, because of their train-
ing, experience and current professional activity, has the specialist knowledge required. To
be able to inspect, assess and operate devices, systems and machines, the person has to
be informed of the state of the art and the applicable national, European and international
laws, directives and standards.
It is the company’s responsibility only to employ personnel who
}Are familiar with the basic regulations concerning health and safety / accident prevention,
}Have read and understood the information provided in the section entitled Safety
}Have a good knowledge of the generic and specialist standards applicable to the specific
application.
Warranty and liability
All claims to warranty and liability will be rendered invalid if
}The product was used contrary to the purpose for which it is intended,
}Damage can be attributed to not having followed the guidelines in the manual,
}Operating personnel are not suitably qualified,
}Any type of modification has been made (e.g. exchanging components on the PCB
boards, soldering work etc.).
Disposal
}In safety-related applications, please comply with the mission time TM in the safety-related
characteristic data.
}When decommissioning, please comply with local regulations regarding the disposal of
electronic devices (e.g. Electrical and Electronic Equipment Act).

P1HZ X1
Operating Manual P1HZ X1
20067-EN-09 | 7
For your safety
The unit meets all the necessary conditions for safe operation. However, please note the
following:
}Note for overvoltage category III: If voltages higher than low voltage (>50 VAC or >120
VDC) are present on the unit, connected control elements and sensors must have a rated
insulation voltage of at least 250 V.
Unit features
}Positive-guided relay outputs:
– 2 safety contacts (N/O), instantaneous
}Connection options for:
– 2 control elements (pushbuttons)
}LED display for:
– Supply voltage
– Switch status of the safety contacts
Safety features
The two-hand control relay meets the following safety requirements:
}The two-hand control relay prevents the plant from being enabled in the following cases:
– Power supply failure
– Component failure
– Short circuit on an input circuit
– Coil defect
– Open circuit
– Earth fault
}In each on-off cycle, the output relays on the safety device are tested to ensure they open
and close correctly

P1HZ X1
Operating Manual P1HZ X1
20067-EN-09 | 8
Block diagram/terminal configuration
*Insulation between the non-marked area and the relay contacts: Basic insulation (over-
voltage category III), Protective separation (overvoltage category II)
Function Description
The two-hand control relay is activated by simultaneously operating the two operator ele-
ments (simultaneity see Technical details [ 12]). If one or both of the operator elements
are released, the device interrupts the control command for the hazardous movement. The
device is ready for operation when the supply voltage is applied and the feedback loop Y1-
Y2 is closed. The "POWER" LED lights up.
}Both operator elements are operated within the simultaneity:
– Safety contacts 13-14 and 23-24 close, the device is active.
– LEDs "CH1" and "CH2" will light.
}One operator element is released following simultaneous operation:
– Safety contacts 13-14 and 23-24 are opened
– The LED "CH1" or "CH2" goes out.
}To activate the device again, both operator elements have to be released and then oper-
ated again within the simultaneity.
Operating modes
}Dual-channel operation with detection of shorts across contacts: Redundant input circuit,
P1HZ X1 detects
– earth faults in the start and input circuit,
– short circuits in the input circuit,
– shorts across contacts in the input circuit.

P1HZ X1
Operating Manual P1HZ X1
20067-EN-09 | 9
Timing diagram
POWER
Feedback loop
Output safe
Button 1
t0t1t2t3t3t1
Button 2
t1
Legend
}POWER: Supply voltage
}Button 1/Button 2: Pushbutton in the input circuit
}Feedback loop: Feedback loop
}Output safe: Safety contacts
}t0: Recovery time after power on
}t1: Simultaneity, channel 1 and 2
}t2: Operating cycle ended through pushbutton 1 or 2
}t3: Feedback loop must be closed before the pushbutton is operated (recovery time)
Shaded area: State irrelevant
Installation
}The unit should be installed in a control cabinet with a protection type of at least IP54.
}Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).
}When installed vertically: Secure the unit by using a fixing element (e.g. retaining bracket
or end angle).
WARNING!
Loss of the safety function due to too short distance of the operator
elements to the hazardous area!
The distance of the two-hand control relay to the nearest hazardous area
must be large enough so that if one of the operator elements is released,
the hazardous movement is interrupted before the operator reaches the
hazardous area or can reach into the hazardous area. You must maintain
the minimum distance in accordance with EN ISO 13855.
Depending on the application, serious injury or death may result.

P1HZ X1
Operating Manual P1HZ X1
20067-EN-09 | 10
Wiring
Please note:
}Information given in the "Technical details [ 12]" must be followed.
}The outputs 13-14, 23-24 are safety contacts.
}To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details [ 12]).
}Fit the input terminal block of the control cabined with additional terminals for the supply
voltage.
}Calculation of the max. cable length lmax in the input circuit:
Rlmax
Rl / km
Imax =
Rlmax = max. overall cable resistance (see Technical details [ 12])
Rl/km = cable resistance/km
}Use copper wiring with a temperature stability of 60/75 °C.
}To prevent EMC interferences (particularly common-mode interferences) the measures
described in EN60204-1 must be executed. This includes the separate routing of cables
of the control circuits (input, start and feedback loop) from other cables for energy trans-
mission or the shielding of cables, for example.
}The supply voltage must be switched off with the operating energy of the machine.
}Adequate protection must be provided on all output contacts with capacitive and inductive
loads.
}Do not switch low currents using contacts that have been used previously with high cur-
rents.
}The power supply must comply with the regulations for extra low voltages with protective
electrical separation (SELV, PELV) in accordance with VDE 0100, Part 410.
Preparing for operation
Supply voltage AC DC
A1
A2
L+
L-
F1
Input circuit Single-channel Dual-channel
Two-hand pushbuttons
with detection of shorts across
contacts
S23
S13
S14
S24
S1
S2

P1HZ X1
Operating Manual P1HZ X1
20067-EN-09 | 11
Feedback loop
Contacts from external contactors
Legend
}S1/S2: Two-hand pushbuttons
Operation
NOTICE
The safety functions should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.
Status indicators
LEDs indicate the status and errors during operation:
LED on
POWER
Supply voltage is present and E-STOP pushbutton not operated.
CH.1
Safety contacts of channel 1 are closed.
CH.2
Safety contacts of channel 2 are closed.
Faults – Interference
}Earth fault: When in accordance with EN 60204 T 9.4.3.1 the phase L (-) of the supply
voltage is connected to the earth potential, earth faults are detected. In case of earth
faults in the input circuit or feedback loop, the internal supply voltage fails and the safety
contacts open or they will not be closed in the following start. Once the cause of the re-
spective fault has been removed and the supply voltage is switched off for approx.
1minute, the device is ready for operation again.
}Contact malfunctions: If the contacts have welded, reactivation will not be possible after
the input circuit has opened.

P1HZ X1
Operating Manual P1HZ X1
20067-EN-09 | 12
Dimensions in mm
121 (4.8")
75 (2.95")
87 (3.42")
22,5
(0,89")
Technical details
General
Certifications CCC, CE, EAC, TÜV, UKCA, cULus Listed
Electrical data
Supply voltage
Voltage 24 V
Kind DC
Voltage tolerance -15 %/+10 %
Output of external power supply (DC) 2 W
Residual ripple DC 10 %
Duty cycle 100 %
Current at
N/O contact 10 mA
Max. overall cable resistance Rlmax per input circuit 14 Ohm
External unit fuse protection F1 min. 1 A
External unit fuse protection F1 max. Max. conductor cross section
Two-hand control relay type
in accordance with the standard EN ISO 13851
Type III A
Inputs
Quantity 2
Voltage at
Input circuit DC 24 V
Feedback loop DC 24 V
Current at
Feedback loop DC 40 mA

P1HZ X1
Operating Manual P1HZ X1
20067-EN-09 | 13
Relay outputs
Number of output contacts
Safety contacts (N/O), instantaneous 2
Max. short circuit current IK 1 kA
Utilisation category
in accordance with the standard EN 60947-4-1
Utilisation category of safety contacts
AC1 at 240 V
Min. current 0,01 A
Max. current 6 A
Max. power 1500 VA
DC1 at 24 V
Min. current 0,01 A
Max. current 6 A
Max. power 150 W
Utilisation category
in accordance with the standard EN 60947-5-1
Utilisation category of safety contacts
AC15 at 230 V
Max. current 5 A
DC13 (6 cycles/min) at 24 V
Max. current 2,5 A
Utilisation category in accordance with UL
Voltage 240 V AC G. P.
with current 6 A
Voltage 24 V DC Resistive
with current 6 A
Pilot Duty C300, R300
External contact fuse protection, safety contacts
in accordance with the standard EN 60947-5-1
Max. melting integral 240 A²s
Blow-out fuse, quick 6 A
Blow-out fuse, slow 4 A
Blow-out fuse, gG 6 A
Circuit breaker 24V AC/DC, characteristic B/C 4 A
Conventional thermal current 6 A
Contact material AgSnO2 + 0,2µ Au
Times
Delay-on de-energisation (response time tA in ac-
cordance with EN ISO 13851)
N/O contact 15 ms
Recovery time 150 ms
Simultaneity, channel 1 and 2 max. 500 ms
Environmental data
Climatic suitability EN 60068-2-78

P1HZ X1
Operating Manual P1HZ X1
20067-EN-09 | 14
Environmental data
Ambient temperature
Temperature range -25 - 55 °C
Storage temperature
Temperature range -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C
Condensation during operation Not permitted
EMC EN 60947-5-1, EN 61000-6-2
Vibration
in accordance with the standard EN 60068-2-6
Frequency 10 - 55 Hz
Amplitude 0,35 mm
Airgap creepage
in accordance with the standard EN 60947-1
Overvoltage category III / II
Pollution degree 2
Rated insulation voltage 250 V
Rated impulse withstand voltage 4 kV
Protection type
Housing IP40
Terminals IP20
Mounting area (e.g. control cabinet) IP54
Mechanical data
Mounting position Any
Mechanical life 10,000,000 cycles
Material
Bottom PPO UL 94 V1
Front ABS UL 94 V0
Top PPO UL 94 V1
Connection type Screw terminal
Mounting type Fixed
Conductor cross section with screw terminals
1 core flexible 0,2 - 4 mm², 24 - 10 AWG
2 core with the same cross section, flexible with
crimp connectors, no plastic sleeve 0,2 - 2,5 mm², 24 - 14 AWG
2 core with the same cross section, flexible without
crimp connectors or with TWIN crimp connectors 0,2 - 2,5 mm², 24 - 14 AWG
Torque setting with screw terminals 0,5 Nm
Stripping length with screw terminals 6 mm
Dimensions
Height 87 mm
Width 22,5 mm
Depth 121 mm
Weight 200 g
Where standards are undated, the 2022-09 latest editions shall apply.

P1HZ X1
Operating Manual P1HZ X1
20067-EN-09 | 15
Safety characteristic data
NOTICE
You must comply with the safety characteristic data in order to achieve the
required safety level for your plant/machine.
Operating
mode
EN ISO
13849-1:
2015
PL
EN ISO
13849-1:
2015
Category
EN IEC
62061
SIL CL/
maximum
SIL
EN IEC
62061
PFHD [1/h]
EN/IEC
61511
SIL
EN/IEC
61511
PFD
EN ISO
13849-1:
2015
TM [year]
–PL c Cat. 1 SIL 1 8,53E-08 SIL 1 7,27E-03 20
Explanatory notes for the safety-related characteristic data:
}Safety characteristic data in accordance with EN IEC 62061 and EN/IEC 61511 was cal-
culated based on EN/IEC 61508.
}TM is the maximum mission time in accordance with EN ISO 13849-1. The value also ap-
plies as the retest interval in accordance with EN/IEC 61508-6 and EN/IEC 61511 and as
the proof test interval and mission time in accordance with EN IEC 62061.
All the units used within a safety function must be considered when calculating the safety
characteristic data.
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.

P1HZ X1
Operating Manual P1HZ X1
20067-EN-09 | 16
Supplementary data
CAUTION!
It is essential to consider the relay's service life graphs. The relay outputs'
safety-related characteristic data is only valid if the values in the service life
graphs are met.
The PFH value depends on the switch frequency and the load of the relay output.
If the service life graphs are not accessible, the stated PFH value can be used irrespective
of the switch frequency and the load, as the PFH value already considers the relay's B10d
value as well as the failure rates of the other components.
Service life graph
The service life graphs indicate the number of cycles from which failures due to wear must
be expected. The wear is mainly caused by the electrical load; the mechanical load is negli-
gible.
Number of cycles x 1000
Switching current (A)
Example
}Inductive load: 0.2 A
}Utilisation category: AC15
}Contact service life: 4 000 000 cycles
Provided the application to be implemented requires fewer than 4 000 000 cycles, the PFH
value (see Technical details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With DC con-
tactors, use flywheel diodes for spark suppression.

P1HZ X1
Operating Manual P1HZ X1
20067-EN-09 | 17
Order reference
Product type Features Connection type Order no.
P1HZ X1 24 V DC Screw terminals 774360
EC declaration of conformity
This product/these products meet the requirements of the directive 2006/42/EC on ma-
chinery of the European Parliament and of the Council. The complete EC Declaration of
Conformity is available on the Internet at www.pilz.com/downloads.
Representative: Hansjürgen Horter, Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760
Ostfildern, Germany
UKCA-Declaration of Conformity
This product(s) complies with following UK legislation: Supply of Machinery (Safety) Regu-
lation 2008.
The complete UKCA Declaration of Conformity is available on the Internet at www.pilz.com/
downloads.
Representative: Pilz Automation Technology, Pilz House, Little Colliers Field,
Corby, Northamptonshire, NN18 8TJ United Kingdom, eMail: [email protected]

We are represented internationally. Please refer to our homepage www.pilz.com
for further details or contact our headquarters.
Headquarters: Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected], Internet: www.pilz.com
CECE®, CHRE®, CMSE®, InduraNET p®, Leansafe®, Master of Safety®, Master of Security®, PAS4000®, PAScal®, PASconfig®, Pilz®, PIT®, PLID®, PMCprimo®, PMCprotego®, PMCtendo®,
PMD®, PMI®, PNOZ®, PRBT®, PRCM®, Primo®, PRTM®, PSEN®, PSS®, PVIS®, SafetyBUS p®, SafetyEYE®, SafetyNET p®, THE SPIRIT OF SAFETY®are registered and protected trademarks
of Pilz GmbH & Co. KG in some countries. We would point out that product features may vary from the details stated in this document, depending on the status at the time of publication
and the scope of the equipment. We accept no responsibility for the validity, accuracy and entirety of the text and graphics presented in this information. Please contact our Technical Support
if you have any questions.
1800XXXX-en-0X, 2021-01 Printed in Germany
© Pilz GmbH & Co. KG, 2021
Support
Technical support is available from Pilz round the clock.
Pilz develops environmentally-friendly products using
ecological materials and energy-saving technologies.
Oces and production facilities are ecologically designed,
environmentally-aware and energy-saving. So Pilz oers
sustainability, plus the security of using energy-ecient
products and environmentally-friendly solutions.
Americas
Brazil
+55 11 97569-2804
Canada
+1 888 315 7459
Mexico
+52 55 5572 1300
USA (toll-free)
+1 877-PILZUSA (745-9872)
Asia
China
+86 21 60880878-216
Japan
+81 45 471-2281
South Korea
+82 31 778 3300
Australia and Oceania
Australia
+61 3 95600621
New Zealand
+64 9 6345350
Europe
Austria
+43 1 7986263-0
Belgium, Luxembourg
+32 9 3217570
France
+33 3 88104003
Germany
+49 711 3409-444
Ireland
+353 21 4804983
Italy, Malta
+39 0362 1826711
Scandinavia
+45 74436332
Spain
+34 938497433
Switzerland
+41 62 88979-32
The Netherlands
+31 347 320477
Turkey
+90 216 5775552
United Kingdom
+44 1536 462203
You can reach our
international hotline on:
+49 711 3409-222
suppor[email protected]
Back cover
20067-EN-09, 2023-07 Printed in Germany
© Pilz GmbH & Co. KG, 2019