PZEX5
OperatingManualPZEX5
1003301EN05 5
INFORMATION
Thisgivesadviceonapplicationsandprovidesinformationonspecialfea
tures.
Intendeduse
TheunitmeetstherequirementsofEN6094751,EN602041andVDE01131.Thecon
tactexpansionmoduleisusedtoincreasethenumberofinstantaneoussafetycontacts
availableonabaseunit.Baseunitsareallsafetyrelayswithfeedbackloopmonitoring.
ThecategorythatcanbeachievedinaccordancewithENISO138491dependsonthe
categoryofthebaseunit.Thecontactexpansionmodulemaynotexceedthis.
Foryoursafety
}Onlyinstallandcommissiontheunitifyouhavereadandunderstoodtheseoperating
instructionsandarefamiliarwiththeapplicableregulationsforhealthandsafetyatwork
andaccidentprevention.
EnsureVDEandlocalregulationsaremet,especiallythoserelatingtosafety.
}Anyguaranteeisrenderedinvalidifthehousingisopenedorunauthorisedmodifica
tionsarecarriedout.
}NoteforovervoltagecategoryIII:Ifvoltageshigherthanlowvoltage(>50VACor>120
VDC)arepresentontheunit,connectedcontrolelementsandsensorsmusthavea
ratedinsulationvoltageofatleast250V.
Unitfeatures
}Positiveguidedrelayoutputs:
– 5safetycontacts(N/O),instantaneous
}LEDdisplayfor:
– Switchstatuschannel1/2
– Supplyvoltage
}Connectionforfeedbackloop
}Operation:singleordualchannel
Safetyfeatures
Theunitmeetsthefollowingsafetyrequirements:
}Thecontactexpandermoduleexpandsanexistingcircuit.Astheoutputrelaysare
monitoredviathebaseunit'sfeedbackloop,thesafetyfunctionsontheexistingcircuit
aretransferredtothecontactexpandermodule.
}Thesafetyfunctionremainseffectiveinthecaseofacomponentfailure.
}Earthfaultinthefeedbackloop:
Detected,dependingonthebaseunitthatisused.