
NOTE: Before cleaning, notify the proper authorities that the system
is undergoing maintenance. Disable the loop or system undergoing
maintenance to prevent unwanted alarms. It is recommended that the
detector be removed from its mounting base for easier cleaning and
that detectors be cleaned at least once a year. Use a vacuum cleaner
remove dust from the sensing chamber.
POTTER warrants that the equipment herein shall conform to
said descriptions as to all armation of fact and shall be free from
defects of manufacture, labeling, and packaging for a period of ve
(5) years from the invoice date to the original purchaser, provided
that representative samples are returned to POTTER for inspection.
e product warranty period is stated on the exterior of the product
package. Upon a determination by POTTER that a product is not as
warranted, POTTER shall, at its exclusive option, replace or repair
said defective product or parts thereof at its own expense, except
that Purchaser shall pay all shipping, insurance, and similar charges
incurred in connection with the replacement of the defective product
or parts thereof. is Warranty is void in the case of abuse, misuse,
abnormal usage, faulty installation, or repair by unauthorized per-
sons, or if for any other reason POTTER determines that said prod-
uct is not operating properly as a result of causes other than defective
manufacture, labeling, or packaging.
H. Warranty
G. CleaningE. Addressing
According to NFPA72, remote testing is NOT necessary
for duct applications. But if testing is still desired, it is
recommended to follow guidelines as described below.
Smoke Aerosol Test
Use a canned aerosol to spray directly to the side of the
detector. SmokeCheck 25S from HSI Fire and Smoke Centurion
from SDi are acceptable. Please contact local re and safety
equipment distributors to see which products are available.
Units failing the aerosol test should be immediately cleaned.
If cleaning cannot restore the unit to normal, it should be
replaced.
Air Sampling Verication
is detector is designed to be used in air handling systems with
air velocities of 300 to 3000 feet per minute. To ensure that the air
velocity in the duct falls within these parameters, use a velocity meter
(anemometer) to check the air velocity in the duct.
Magnet Test
e magnet test provides a quick test to verify the connections
and the detector electronically. is test should not replace the
aerosol test, which is required as part of regular testing and
maintenance per NFPA 72.
1. Hold the test magnet in the magnet test area as shown
below.
2. e LED ashes rapidly to indicate the detector is in
alarm.
3. Remove magnet.
4. Alarm on the re alarm panel should be reset.
5. If the unit fails the magnet test, test the unit with
an aerosol testing spray to conrm any failures.
F. Testing
NOTIFY APPROPRIATE AUTHORITY BEFORE
TESTING THE DETECTOR. PLACE FIRE PANEL IN
WALK TEST
MODE BEFORE CONDUCTING THE FOLLOWING TEST. REFER
TO THE PANEL INSTALLATION MANUAL FOR DETAIL.
Magnet Location
Pry the four (4) elastic arms
gently with a small, slotted
screwdriver to remove detector
cover.
Pry the elastic arm gently with a small, slotted screwdriver to
remove cage for cleaning.
Detector address can be congured using the
table below for DIP switch position settings.
POS DIP Switch on POS DIP Switch on POS DIP Switch on
1 1 43 1,2,4,6 85 1,3,5,7
2 2 44 3,4,6 86 2,4,5,7
3 1,2 45 1,3,4,6 87 1,2,3,5,7
4 3 46 2,3,4,6 88 4,5,8
5 1,3 47 1,2,3,4,6 89 1,4,5,7
6 2,3 48 5,6 90 2,4,5,7
7 1,2,3 49 1,5,6 91 1,2,4,5,7
8 4 50 2,5,6 92 3,4,5,7
9 1,4 51 1,2,5,6 93 1,3,4,5,7
10 2,4 52 3,5,6 94 2,3,4,5,7
11 1,2,4 53 1,3,5,6 95 1,2,3,4,5,7
12 3,4 54 2,3,5,6 96 6,7
13 1,3,4 55 1,2,3,5,6 97 1,6,7
14 2,3,4 56 4,5,6 98 2,6,7
15 1,2,3,4 57 1,4,5,6 99 1,2,6,7
16 5 58 2,4,5,6 100 3,6,7
17 1,5 59 1,2,4,5,6 101 1,3,6,7
18 2,5 60 3,4,5,6 102 2,3,6,7
19 1,2,5 61 1,3,4,5,6 103 1,2,3,6,7
20 3,5 62 2,3,5,5,6 104 4,6,7
21 1,3,5 63 1,2,3,4,5,6 105 1,4,6,7
22 2,3,5 64 7 106 2,4,6,7
23 1,2,3,5 65 1,7 107 1,2,4,6,7
24 4,5 66 2,7 108 3,4,6,7
25 1,4,5 67 1,2,7 109 1,3,4,6,7
26 2,4,5 68 3,7 110 2,3,4,6,7
27 1,2,4,5 69 1,3,7 111 1,2,3,4,6,7
28 3,4,5 70 2,3,7 112 5,6,7
29 1,3,4,5 71 1,2,3,7 113 1,5,6,7
30 2,3,4,5 72 4,7 114 2,5,6,7
31 1,2,3,4,5 73 1,2,4,7 115 1,2,5,6,7
32 6 74 3,4,7 116 3,5,6,7
33 1,6 75 1,3,4,7 117 1,3,5,6,7
34 2,6 76 2,3,4,7 118 2,3,5,6,7
35 1,2,6 77 1,3,4,7 119 1,2,3,5,6,7
36 3,6 78 2,3,4,7 120 4,5,6,7
37 1,3,6 79 1,2,3,4,7 121 1,4,5,6,7
38 2,3,6 80 5,7 122 2,4,5,6,7
39 1,2,3,6 81 1,5,7 123 1,2,4,5,6,7
40 4,6 82 2,5,7 124 3,4,5,6,7
41 1,4,6 83 1,2,5,7 125 1,3,4,5,6,7
42 2,4,6 84 3,5,7 126 2,3,4,5,6,7
127 1,2,3,4,5,6,7 Manual Number:
54035217X_A
Manual Issue Date:
07/01/2022