manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Potter
  6. •
  7. Security Sensor
  8. •
  9. Potter PAD300-DD User manual

Potter PAD300-DD User manual

PAD300-DD (In-Duct/Plenum Mount Applications)
Contents
A. Introduction E. Addressing
B. Specications F.Testing
C.Installation G. Cleaning
D. Locking Feature H. Warranty
PAD300-DD
Operating Voltage 24 VDC
Standby Current (*) 300 A
Alarm Indicator Current 1.4 mA
Alarm Set Point 2.5%/
Installation Temp Range 32F to 120F
Operating Humidity Range 0% - 93% (Non-condensing)
Air Velocity (In-duct) 300 to 3,000 fpm
Dimension Φ 3.93 in
Weight 3.20 oz
Height 1.42 in
*Standby current is the current the device consumes when the device
is in a non-activated condition and where no communication current
is transmitted to the re alarm control panel.
e PAD300-DD is an intelligent addressable photoelectric duct
smoke detector designed and built to meet both UL268A and NFPA
regulations. It is intended for indoor use within a duct (In-duct) or
in plenums. It can also be mounted in a PAD300-DUCT or PAD300-
DUCTR with sampling tubes extending into a duct. Maximum air
velocity for In-duct/plenum applications is 3,000 fpm. Maximum air
velocity for PAD300-DUCT and PAD300-DUCTR is 4,000 fpm. To
minimize false alarms, avoid placing in areas where excessive dust,
humidity, air movement, or extreme temperature is present.
is manual only covers the installation guidelines for In-duct/
plenum applications. For standard external mount duct applications,
please refer to the installation manual for PAD300-DUCT and
PAD300-DUCTR.
Each detector includes one (1) LED to indicate the device status.
e LED ashes momentarily in normal conditions and ashes
at a fast rate when activated. e LED can be turned o using the
programming soware.
e PAD300-DD communicates on a proprietary protocol to the
addressable re alarm control panel. It must be connected to either
the IPA series, AFC series, or ARC re alarm control panel for proper
operation. For detector sensitivity settings and supervision, please
refer to the panel installation instructions.
Refer to the company website for the latest revision of this manual.
B. Specications
A. Introduction
Installation must meet the requirements of the Authority Having
Jurisdiction (AHJ). It is recommended to follow guidelines as
described in NFPA 72 and NFPA 90A.
1. Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the SLC or device.
• Use only the PAD300 series bases PAD300-4DB and
PAD300-6DB (supplied separately).
• Conrm the eld wiring on device is correctly installed on
the base. Refer to the base manual.
• Enable the locking feature if needed. Refer to section D for
details of the locking feature.
2. Set the desired address using the DIP switch located on back of
the sensor. See section E for addressing instructions.
3. Plug detector into base and turn clockwise to secure in place.
C. Installation
KEEP DUST COVER ON DETECTOR DURING
CONSTRUCTION. REMOVE DUST COVER TO ALLOW THE
DETECTOR TO DETECT SMOKE.
DETECTORS ARE NOT TO BE USED WITH DETECTOR
GUARDS UNLESS THE COMBINATION HAS BEEN EVALUATED
AND FOUND SUITABLE FOR THAT PURPOSE.
CAUTION
1. To minimize the impact of air turbulence and stratication
on performance, detector should be located as far as possible
downstream from any obstruction. Conrmation of velocity
within specications is required.
2. Identify a code compliant location (supply or return side, or
both) for the installation of the duct unit that will permit easy
access for inspection and serviceability.
3. When mounted in plenum space or duct handling space, it is
critical that the detector is situated such that the airstream ows
through the opening of the head. See below.
Airow
e device includes a tamperproof feature that locks the detector and
does not allow removal without the use of a tool.
D. Locking Feature
Break o tab (gray area in
image). e locking feature
is enabled.
Insert a small
screwdriver into slot
to remove detector.
1609 Park 370 Pl, Hazelwood, MO 63042
www.pottersignal.com
NOTE: Before cleaning, notify the proper authorities that the system
is undergoing maintenance. Disable the loop or system undergoing
maintenance to prevent unwanted alarms. It is recommended that the
detector be removed from its mounting base for easier cleaning and
that detectors be cleaned at least once a year. Use a vacuum cleaner
remove dust from the sensing chamber.
POTTER warrants that the equipment herein shall conform to
said descriptions as to all armation of fact and shall be free from
defects of manufacture, labeling, and packaging for a period of ve
(5) years from the invoice date to the original purchaser, provided
that representative samples are returned to POTTER for inspection.
e product warranty period is stated on the exterior of the product
package. Upon a determination by POTTER that a product is not as
warranted, POTTER shall, at its exclusive option, replace or repair
said defective product or parts thereof at its own expense, except
that Purchaser shall pay all shipping, insurance, and similar charges
incurred in connection with the replacement of the defective product
or parts thereof. is Warranty is void in the case of abuse, misuse,
abnormal usage, faulty installation, or repair by unauthorized per-
sons, or if for any other reason POTTER determines that said prod-
uct is not operating properly as a result of causes other than defective
manufacture, labeling, or packaging.
H. Warranty
G. CleaningE. Addressing
According to NFPA72, remote testing is NOT necessary
for duct applications. But if testing is still desired, it is
recommended to follow guidelines as described below.
Smoke Aerosol Test
Use a canned aerosol to spray directly to the side of the
detector. SmokeCheck 25S from HSI Fire and Smoke Centurion
from SDi are acceptable. Please contact local re and safety
equipment distributors to see which products are available.
Units failing the aerosol test should be immediately cleaned.
If cleaning cannot restore the unit to normal, it should be
replaced.
Air Sampling Verication
is detector is designed to be used in air handling systems with
air velocities of 300 to 3000 feet per minute. To ensure that the air
velocity in the duct falls within these parameters, use a velocity meter
(anemometer) to check the air velocity in the duct.
Magnet Test
e magnet test provides a quick test to verify the connections
and the detector electronically. is test should not replace the
aerosol test, which is required as part of regular testing and
maintenance per NFPA 72.
1. Hold the test magnet in the magnet test area as shown
below.
2. e LED ashes rapidly to indicate the detector is in
alarm.
3. Remove magnet.
4. Alarm on the re alarm panel should be reset.
5. If the unit fails the magnet test, test the unit with
an aerosol testing spray to conrm any failures.
F. Testing
NOTIFY APPROPRIATE AUTHORITY BEFORE
TESTING THE DETECTOR. PLACE FIRE PANEL IN
WALK TEST
MODE BEFORE CONDUCTING THE FOLLOWING TEST. REFER
TO THE PANEL INSTALLATION MANUAL FOR DETAIL.
CAUTION
Magnet Location
Pry the four (4) elastic arms
gently with a small, slotted
screwdriver to remove detector
cover.
Pry the elastic arm gently with a small, slotted screwdriver to
remove cage for cleaning.
Detector address can be congured using the
table below for DIP switch position settings.
POS DIP Switch on POS DIP Switch on POS DIP Switch on
1 1 43 1,2,4,6 85 1,3,5,7
2 2 44 3,4,6 86 2,4,5,7
3 1,2 45 1,3,4,6 87 1,2,3,5,7
4 3 46 2,3,4,6 88 4,5,8
5 1,3 47 1,2,3,4,6 89 1,4,5,7
6 2,3 48 5,6 90 2,4,5,7
7 1,2,3 49 1,5,6 91 1,2,4,5,7
8 4 50 2,5,6 92 3,4,5,7
9 1,4 51 1,2,5,6 93 1,3,4,5,7
10 2,4 52 3,5,6 94 2,3,4,5,7
11 1,2,4 53 1,3,5,6 95 1,2,3,4,5,7
12 3,4 54 2,3,5,6 96 6,7
13 1,3,4 55 1,2,3,5,6 97 1,6,7
14 2,3,4 56 4,5,6 98 2,6,7
15 1,2,3,4 57 1,4,5,6 99 1,2,6,7
16 5 58 2,4,5,6 100 3,6,7
17 1,5 59 1,2,4,5,6 101 1,3,6,7
18 2,5 60 3,4,5,6 102 2,3,6,7
19 1,2,5 61 1,3,4,5,6 103 1,2,3,6,7
20 3,5 62 2,3,5,5,6 104 4,6,7
21 1,3,5 63 1,2,3,4,5,6 105 1,4,6,7
22 2,3,5 64 7 106 2,4,6,7
23 1,2,3,5 65 1,7 107 1,2,4,6,7
24 4,5 66 2,7 108 3,4,6,7
25 1,4,5 67 1,2,7 109 1,3,4,6,7
26 2,4,5 68 3,7 110 2,3,4,6,7
27 1,2,4,5 69 1,3,7 111 1,2,3,4,6,7
28 3,4,5 70 2,3,7 112 5,6,7
29 1,3,4,5 71 1,2,3,7 113 1,5,6,7
30 2,3,4,5 72 4,7 114 2,5,6,7
31 1,2,3,4,5 73 1,2,4,7 115 1,2,5,6,7
32 6 74 3,4,7 116 3,5,6,7
33 1,6 75 1,3,4,7 117 1,3,5,6,7
34 2,6 76 2,3,4,7 118 2,3,5,6,7
35 1,2,6 77 1,3,4,7 119 1,2,3,5,6,7
36 3,6 78 2,3,4,7 120 4,5,6,7
37 1,3,6 79 1,2,3,4,7 121 1,4,5,6,7
38 2,3,6 80 5,7 122 2,4,5,6,7
39 1,2,3,6 81 1,5,7 123 1,2,4,5,6,7
40 4,6 82 2,5,7 124 3,4,5,6,7
41 1,4,6 83 1,2,5,7 125 1,3,4,5,6,7
42 2,4,6 84 3,5,7 126 2,3,4,5,6,7
127 1,2,3,4,5,6,7 Manual Number:
54035217X_A
Manual Issue Date:
07/01/2022

Other Potter Security Sensor manuals

Potter EVD-1 User manual

Potter

Potter EVD-1 User manual

Potter Amseco EBP-401 User manual

Potter

Potter Amseco EBP-401 User manual

Potter PAD300-SB User manual

Potter

Potter PAD300-SB User manual

Potter LFH-24 Series User manual

Potter

Potter LFH-24 Series User manual

Potter PAD100-DUCTR User manual

Potter

Potter PAD100-DUCTR User manual

Potter PAD300-RB User guide

Potter

Potter PAD300-RB User guide

Potter Amseco EBP-401 Quick start guide

Potter

Potter Amseco EBP-401 Quick start guide

Potter FEP-A Series User manual

Potter

Potter FEP-A Series User manual

Potter RA-6006 User manual

Potter

Potter RA-6006 User manual

Potter PAD300-CD User manual

Potter

Potter PAD300-CD User manual

Potter CS-24 Series User manual

Potter

Potter CS-24 Series User manual

Potter PAD300-HD User manual

Potter

Potter PAD300-HD User manual

Potter PAD100-LFSB User manual

Potter

Potter PAD100-LFSB User manual

Potter EVD-2 User manual

Potter

Potter EVD-2 User manual

Potter PAD200-DUCT User manual

Potter

Potter PAD200-DUCT User manual

Potter PAD300-IB User manual

Potter

Potter PAD300-IB User manual

Potter RA-6500R User manual

Potter

Potter RA-6500R User manual

Potter PAD300-4DB User manual

Potter

Potter PAD300-4DB User manual

Potter PAD100-IB User manual

Potter

Potter PAD100-IB User manual

Potter amseco SB24 Series User manual

Potter

Potter amseco SB24 Series User manual

Potter PAD200-DUCTR User manual

Potter

Potter PAD200-DUCTR User manual

Potter PAD100-RB User manual

Potter

Potter PAD100-RB User manual

Potter PAD100-DUCT User manual

Potter

Potter PAD100-DUCT User manual

Potter PAD100-PD User manual

Potter

Potter PAD100-PD User manual

Popular Security Sensor manuals by other brands

System Sensor B501A Installation and maintenance instructions

System Sensor

System Sensor B501A Installation and maintenance instructions

EUCHNER CES-A-AEA-02B operating instructions

EUCHNER

EUCHNER CES-A-AEA-02B operating instructions

ChinaPST PST-WIP-350 installation manual

ChinaPST

ChinaPST PST-WIP-350 installation manual

System Sensor Innovair SSK451 Installation and maintenance instructions

System Sensor

System Sensor Innovair SSK451 Installation and maintenance instructions

BST Flamonitec IFC 400 operating manual

BST

BST Flamonitec IFC 400 operating manual

BFT SIBOX instructions

BFT

BFT SIBOX instructions

Siemens L-852A-D Dualite manual

Siemens

Siemens L-852A-D Dualite manual

THORLABS PDA8A2 quick reference

THORLABS

THORLABS PDA8A2 quick reference

Wenglor Y1TA Series operating instructions

Wenglor

Wenglor Y1TA Series operating instructions

Vega VEGATRENN 149A EX operating instructions

Vega

Vega VEGATRENN 149A EX operating instructions

Nortek Security & Control 2GIG 2GIG-FT6-345 installation instructions

Nortek Security & Control

Nortek Security & Control 2GIG 2GIG-FT6-345 installation instructions

Motorline professional M1601 User's and installer's manual

Motorline professional

Motorline professional M1601 User's and installer's manual

SMC Sierra Monitor 3600-U manual

SMC Sierra Monitor

SMC Sierra Monitor 3600-U manual

Fieldpiece SCM4 Operator's manual

Fieldpiece

Fieldpiece SCM4 Operator's manual

Overhead door RAPIDFLEX 990 instructions

Overhead door

Overhead door RAPIDFLEX 990 instructions

PCB Load & Torque 4115K-13A Installation and operating manual

PCB

PCB Load & Torque 4115K-13A Installation and operating manual

Saxby Lighting 90978 instruction manual

Saxby Lighting

Saxby Lighting 90978 instruction manual

Elko iNELS RFWD-100 manual

Elko

Elko iNELS RFWD-100 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.