ProSoft MVI56E-GEC User manual

MVI56E-GEC
ControlLogix Platform
Generic ASCII Ethernet
Communication Module
February 24, 2020
USER MANUAL

Your Feedback Please
We always want you to feel that you made the right decision to use our products. If you have suggestions, comments,
compliments or complaints about our products, documentation, or support, please write or call us.
ProSoft Technology, Inc.
+1 (661) 716-5100
+1 (661) 716-5101 (Fax)
www.prosoft-technology.com
MVI56E-GEC User Manual
February 24, 2020
ProSoft Technology®, is a registered copyright of ProSoft Technology, Inc. All other brand or product names are or
may be trademarks of, and are used to identify products and services of, their respective owners.
In an effort to conserve paper, ProSoft Technology no longer includes printed manuals with our product shipments.
User Manuals, Datasheets, Sample Ladder Files, and Configuration Files are provided at our website:
www.prosoft-technology.com
Content Disclaimer
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of
these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate
and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or
use thereof. Neither ProSoft Technology nor any of its affiliates or subsidiaries shall be responsible or liable for
misuse of the information contained herein. Information in this document including illustrations, specifications and
dimensions may contain technical inaccuracies or typographical errors. ProSoft Technology makes no warranty or
representation as to its accuracy and assumes no liability for and reserves the right to correct such inaccuracies or
errors at any time without notice. If you have any suggestions for improvements or amendments or have found errors
in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including
photocopying, without express written permission of ProSoft Technology. All pertinent state, regional, and local safety
regulations must be observed when installing and using this product. For reasons of safety and to help ensure
compliance with documented system data, only the manufacturer should perform repairs to components. When
devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use ProSoft Technology software or approved software with our hardware products may result in injury,
harm, or improper operating results. Failure to observe this information can result in injury or equipment damage.
© 2020 ProSoft Technology. All Rights Reserved.
Printed documentation is available for purchase. Contact ProSoft Technology for pricing and availability.
For professional users in the European Union
If you wish to discard electrical and electronic equipment (EEE), please contact your dealer or supplier
for further information.
Warning –Cancer and Reproductive Harm –www.P65Warnings.ca.gov

Important Installation Instructions
Power, Input, and Output (I/O) wiring must be in accordance with Class I, Division 2 wiring methods, Article 501-4 (b)
of the National Electrical Code, NFPA 70 for installation in the U.S., or as specified in Section 18-1J2 of the Canadian
Electrical Code for installations in Canada, and in accordance with the authority having jurisdiction. The following
warnings must be heeded:
A WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR
CLASS I, DIV. 2;
B WARNING - EXPLOSION HAZARD - WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE
REPLACING OR WIRING MODULES
C WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
D Class 2 Power
MVI (Multi-Vendor Interface) Modules
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
AVERTISSEMENT - RISQUE D'EXPLOSION - AVANT DE DÉCONNECTER L'ÉQUIPEMENT, COUPER LE
COURANT OU S'ASSURER QUE L'EMPLACEMENT EST DÉSIGNÉ NON DANGEREUX.
Warnings
North America Warnings
Power, Input, and Output (I/O) wiring must be in accordance with Class I, Division 2 wiring methods, Article 501-4 (b)
of the National Electrical Code, NFPA 70 for installation in the U.S., or as specified in Section 18-1J2 of the Canadian
Electrical Code for installations in Canada, and in accordance with the authority having jurisdiction. The following
warnings must be heeded:
A Warning - Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2.
B Warning - Explosion Hazard - When in hazardous locations, turn off power before replacing or rewiring modules.
C Warning - Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is
known to be non-hazardous.
D Suitable for use in Class I, Division 2 Groups A, B, C and D Hazardous Locations or Non-Hazardous Locations.
ATEX Warnings and Conditions of Safe Usage
Power, Input, and Output (I/O) wiring must be in accordance with the authority having jurisdiction.
A Warning - Explosion Hazard - When in hazardous locations, turn off power before replacing or wiring modules.
B Warning - Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is
known to be non-hazardous.
C These products are intended to be mounted in an IP54 enclosure. The devices shall provide external means to
prevent the rated voltage being exceeded by transient disturbances of more than 40%. This device must be used
only with ATEX certified backplanes.
D DO NOT OPEN WHEN ENERGIZED.
Electrical Ratings
Backplane Current Load: 800 mA @ 5.1 Vdc; 3 mA @ 24 Vdc
Operating Temperature: 0°C to 60°C (32°F to 140°F)
Storage Temperature: -40°C to 85°C (-40°F to 185°F)
Shock: 30 g, operational; 50 g, non-operational; Vibration: 5 g from 10 Hz to 150 Hz
Relative Humidity: 5% to 95% (without condensation)
All phase conductor sizes must be at least 1.3 mm2and all earth ground conductors must be at least 4 mm2.
Agency Approvals & Certifications
Please visit our website: www.prosoft-technology.com

MVI56E-GEC ♦ ControlLogix Platform Start Here
Generic ASCII Ethernet Communication Module User Manual
ProSoft Technology, Inc. Page 4 of 80
Contents
Your Feedback Please...................................................................................................2
Content Disclaimer.........................................................................................................2
Important Installation Instructions...................................................................................3
MVI (Multi-Vendor Interface) Modules............................................................................3
Warnings ........................................................................................................................3
1Start Here 6
1.1 System Requirements ..........................................................................6
1.2 Package Contents ................................................................................7
1.3 Installing ProSoft Configuration Builder Software.................................7
1.4 Setting Jumpers....................................................................................7
1.5 Installing the Module in the Rack..........................................................8
1.6 Opening the Sample Ladder Logic.......................................................9
1.6.1 Determining the Firmware Version of Your Processor.........................9
1.6.2 Selecting the Slot Number for the Module..........................................10
1.7 Downloading the Sample Program to the Processor..........................11
2Using ProSoft Configuration Builder 12
2.1 ProSoft Configuration Builder.............................................................12
2.1.1 Adding the MVI56E-GEC Module to the Project.................................12
2.1.2 Renaming PCB Objects......................................................................13
2.2 [Server x].............................................................................................15
2.2.1 Enabled...............................................................................................15
2.2.2 Service Port Number ..........................................................................15
2.2.3 Connection Timeout............................................................................15
2.2.4 Connection Close Type ......................................................................15
2.2.5 Swap Rx Data Bytes...........................................................................15
2.2.6 Swap Tx Data Bytes ...........................................................................16
2.3 Ethernet 1 Configuration.....................................................................17
2.4 Assigning a Temporary IP Address....................................................18
2.5 Downloading the Configuration File to the Module.............................21
3Configuring the Module in Studio 5000 Logix Designer 23
3.1 Configuring the MVI56E-GEC in Studio 5000 Logix Designer ...........23
3.2 Ladder Logic.......................................................................................26
3.2.1 Exporting the MVI56E-GEC .L5X File ................................................26
3.2.2 Importing the MVI56E-GEC .L5X file Into an Studio 5000 Project .....28
3.3 Optional Add-On Instruction ...............................................................31
3.3.1 Setting Up the Optional AOI ...............................................................33
4Sending and Receiving ASCII Data 35
4.1 Sending ASCII Data............................................................................35
4.1.1 Sending ASCII Text as a Client..........................................................35

MVI56E-GEC ♦ ControlLogix Platform Start Here
Generic ASCII Ethernet Communication Module User Manual
ProSoft Technology, Inc. Page 5 of 80
4.1.2 Sending ASCII Text as a Server.........................................................36
4.2 Receiving ASCII Data.........................................................................37
4.2.1 Receiving ASCII Text as a Client .......................................................37
4.2.2 Receiving ASCII Text as a Server......................................................38
5Diagnostics and Troubleshooting 39
5.1 LED Indicators ....................................................................................39
5.1.1 Ethernet LED Indicators......................................................................39
5.1.2 Scrolling LED......................................................................................40
5.1.3 Clearing a Fault Condition..................................................................40
5.1.4 Troubleshooting..................................................................................41
5.2 ProSoft Configuration Builder Diagnostics Menu ...............................42
5.2.1 Diagnostics Menu Navigation.............................................................44
5.2.2 Viewing Module Information ...............................................................44
5.2.3 Monitoring Backplane Information......................................................45
5.2.4 Monitoring MVI56E-GEC Server X Information..................................46
5.2.5 Monitoring MVI56E-GEC Client X Information ...................................47
5.3 MVI56E-GEC Status Controller Tags.................................................48
5.4 Connecting to the Module’s Webpage................................................51
6Reference 52
6.1 Product Specifications ........................................................................52
6.1.1 General Specifications........................................................................52
6.1.2 Hardware Specifications.....................................................................53
6.1.3 Functional Specifications....................................................................54
6.2 Functional Overview...........................................................................55
6.2.1 General Concepts...............................................................................55
6.3 Status Data.........................................................................................68
6.4 Configuration Data..............................................................................74
7Support, Service & Warranty 76
7.1 Contacting Technical Support.............................................................76
7.2 Warranty Information..........................................................................78
Index 79

Start Here MVI56E-GEC ♦ ControlLogix Platform
User Manual Generic ASCII Ethernet Communication Module
Page 6 of 80 ProSoft Technology, Inc.
1 Start Here
To get the most benefit from this User Manual, you should have the following
skills:
Studio 5000 Logix Designer®: launch the program, configure ladder logic,
and transfer the ladder logic to the processor
Microsoft Windows: install and launch programs, execute menu commands,
navigate dialog boxes, and enter data
Hardware installation and wiring: install the module, and safely connect
Generic Ethernet ASCII and ControlLogix devices to a power source and to
the MVI56E-GEC module’s Ethernet port
1.1 System Requirements
The MVI56E-GEC module requires the following minimum hardware and
software components:
Rockwell Automation ControlLogix®processor (firmware version 10 or
higher), with compatible power supply, and one free slot in the rack for the
MVI56E-GEC module. The module requires 800 mA of available 5 VDC
power and 3 mA of available 24 VDC power.
Rockwell Automation Studio 5000 Logix Designer programming software
oVersion 16 or higher required for Add-On Instruction
oVersion 15 or lower must use Sample Ladder, available from
www.prosoft-technology.com
Rockwell Automation RSLinx®communication software version 2.51 or higher
ProSoft Configuration Builder (PCB) (included)
ProSoft Discovery Service (PDS) (included in PCB)
Pentium®II 450 MHz minimum.
Supported operating systems:
oMicrosoft Windows®10
oMicrosoft Windows®8
oMicrosoft Windows®7 Professional (32-or 64-bit)
oMicrosoft Windows®XP Professional with Service Pack 1 or 2
128 Mbytes of RAM minimum, 256 Mbytes of RAM recommended
100 Mbytes of free hard disk space or more
256-color VGA graphics adapter, 800 x 600 minimum resolution (True Color
1024 768 recommended)
Note: The Hardware and Operating System requirements in this list are the minimum
recommended to install and run software provided by ProSoft Technology®. Other third party
applications may have different minimum requirements. Refer to the documentation for any third
party applications for system requirements.
Note: You can install the module in a local or remote rack. For remote rack installation, the module
requires EtherNet/IP or ControlNet communication with the processor.

MVI56E-GEC ♦ ControlLogix Platform Start Here
Generic ASCII Ethernet Communication Module User Manual
ProSoft Technology, Inc. Page 7 of 80
1.2 Package Contents
Qty.
Part Name
Part Number
Part Description
1
MVI56E-GEC Module
MVI56E-GEC
Generic ASCII Ethernet Communication
Module
1.3 Installing ProSoft Configuration Builder Software
You must install the ProSoft Configuration Builder (PCB) software to configure
the module. You can always get the newest version of ProSoft Configuration
Builder from the ProSoft Technology website.
Installing ProSoft Configuration Builder from the ProSoft website
1 Open your web browser and navigate to http://www.prosoft-
technology.com/pcb
2 Click the DOWNLOAD HERE link to download the latest version of ProSoft
Configuration Builder.
3 Choose SAVE or SAVE FILE when prompted.
4 Save the file to your Windows Desktop, so that you can find it easily when
you have finished downloading.
5 When the download is complete, locate and open the file, and then follow the
instructions on your screen to install the program.
1.4 Setting Jumpers
The Setup Jumper acts as "write protection" for the module’s flash memory. In
"write protected" mode, the Setup pins are not connected, and the module’s
firmware cannot be overwritten. Do not jumper the Setup pins together unless
you are directed to do so by ProSoft Technical Support.
The following illustration shows the MVI56E-GEC jumper configuration.
Note: If you are installing the module in a remote rack, you may prefer to leave the Setup pins
jumpered. That way, you can update the module’s firmware without requiring physical access to
the module.

Start Here MVI56E-GEC ♦ ControlLogix Platform
User Manual Generic ASCII Ethernet Communication Module
Page 8 of 80 ProSoft Technology, Inc.
1.5 Installing the Module in the Rack
If you have not already installed and configured your ControlLogix processor and
power supply, please do so before installing the MVI56E-GEC module. Refer to
your Rockwell Automation product documentation for installation instructions.
Warning: You must follow all safety instructions when installing this or any other electronic
devices. Failure to follow safety procedures could result in damage to hardware or data, or even
serious injury or death to personnel. Refer to the documentation for each device you plan to
connect to verify that suitable safety procedures are in place before installing or servicing the
device.
After you have checked the placement of the jumpers, insert MVI56E-GEC into
the ControlLogix chassis. Use the same technique recommended by Rockwell
Automation to remove and install ControlLogix modules.
Warning: When you insert or remove the module while backplane power is on, an electrical arc
can occur. This could cause an explosion in hazardous location installations. Verify that power is
removed or the area is non-hazardous before proceeding. Repeated electrical arcing causes
excessive wear to contacts on both the module and its mating connector. Worn contacts may
create electrical resistance that can affect module operation.
1 Turn power OFF.
2 Align the module with the top and bottom guides, and slide it into the rack
until the module is firmly against the backplane connector.
3 With a firm but steady push, snap the module into place.
4 Check that the holding clips on the top and bottom of the module are securely
in the locking holes of the rack.
5 Make a note of the slot location. You must identify the slot in which the
module is installed in order for the sample program to work correctly. Slot
numbers are identified on the green circuit board (backplane) of the
ControlLogix rack.
6 Turn power ON.

MVI56E-GEC ♦ ControlLogix Platform Start Here
Generic ASCII Ethernet Communication Module User Manual
ProSoft Technology, Inc. Page 9 of 80
1.6 Opening the Sample Ladder Logic
The sample program for your MVI56E-GEC module includes custom tags, data
types and ladder logic for data I/O and status monitoring. For most applications,
you can run the sample ladder program without modification, or, for advanced
applications, you can incorporate the sample program into your existing
application.
Please download the latest MVI56E-GEC ladder logic file from:
www.prosoft-technology.com.
1.6.1 Determining the Firmware Version of Your Processor
Important: The RSLinx service must be installed and running on your computer in order for Studio
5000 Logix Designer to communicate with the processor. Refer to your RSLinx and Studio 5000
Logix Designer documentation for help configuring and troubleshooting these applications.
1 Start Studio 5000 Logix Designer® and close any existing project that may be
loaded.
2 Open the COMMUNICATIONS menu and choose GO ONLINE. Studio 5000 Logix
Designer will establish communication with the processor. This may take a
few moments.
3 When Studio 5000 Logix Designer has established communication with the
processor, the Connected To Go Online dialog box will open.

Start Here MVI56E-GEC ♦ ControlLogix Platform
User Manual Generic ASCII Ethernet Communication Module
Page 10 of 80 ProSoft Technology, Inc.
4 On the Connected To Go Online dialog box, click the GENERAL tab. This tab
shows information about the processor, including the Revision (firmware)
version. In the following illustration, the firmware version is 17.2.
1.6.2 Selecting the Slot Number for the Module
This sample application is for a module installed in Slot 1 in a ControlLogix rack.
The ladder logic uses the slot number to identify the module. If you are installing
the module in a different slot, you must update the ladder logic so that program
tags and variables are correct, and do not conflict with other modules in the rack.
Changing the slot number
1 In the Controller Organization list, select the module and then click the right
mouse button to open a shortcut menu.
2 On the shortcut menu, choose PROPERTIES. This action opens the Module
Properties dialog box.
3 In the Slot field, adjust the slot location and then click OK.
Studio 5000 Logix Designer will automatically apply the slot number change to all
tags, variables and ladder logic rungs that use the MVI56E-GEC slot number for
computation.

MVI56E-GEC ♦ ControlLogix Platform Start Here
Generic ASCII Ethernet Communication Module User Manual
ProSoft Technology, Inc. Page 11 of 80
1.7 Downloading the Sample Program to the Processor
Note: The key switch on the front of the ControlLogix processor must be in the REM or PROG
position.
1 If you are not already online with the processor, open the Communications
menu, and then choose DOWNLOAD.Studio 5000 Logix Designer will
establish communication with the processor.
2 When communication is established, Studio 5000 Logix Designer will open a
confirmation dialog box. Click the DOWNLOAD button to transfer the sample
program to the processor.
3 Studio 5000 Logix Designer will compile the program and transfer it to the
processor. This process may take a few minutes.
4 When the download is complete, Studio 5000 Logix Designer will open
another confirmation dialog box. If the key switch is in the REM position, click
OK to switch the processor from PROGRAM mode to RUN mode.
Note: If you receive an error message during these steps, refer to your Studio 5000 Logix Designer
documentation to interpret and correct the error.

Using ProSoft Configuration Builder MVI56E-GEC ♦ ControlLogix Platform
User Manual Generic ASCII Ethernet Communication Module
Page 12 of 80 ProSoft Technology, Inc.
2 Using ProSoft Configuration Builder
2.1 ProSoft Configuration Builder
ProSoft Configuration Builder (PCB) provides a quick and easy way to manage
module configuration files customized to meet your application needs. PCB also
allows you to import information from previously installed (known working)
configurations to new projects.
2.1.1 Adding the MVI56E-GEC Module to the Project
1 Use the mouse to select DEFAULT MODULE in the tree view, and then click the
right mouse button to open a shortcut menu. Select CHOOSE MODULE TYPE.
This action opens the Choose Module Type dialog box.
2 In the Product Line Filter area of the dialog box, select MVI56E. In the Select
Module Type dropdown list, select MVI56E-GEC, and then click OK.

MVI56E-GEC ♦ ControlLogix Platform Using ProSoft Configuration Builder
Generic ASCII Ethernet Communication Module User Manual
ProSoft Technology, Inc. Page 13 of 80
2.1.2 Renaming PCB Objects
At this time, you may wish to rename the Default Project and Default Location
folders in the tree view.
1 Select the object, and then click the right mouse button to open a shortcut
menu. From the shortcut menu, choose RENAME.
2 Type the name to assign to the object.
3 Click away from the object to save the new name.
Configuring Module Parameters
1 Click on the [+] sign next to the module icon to expand module information.
2 Click on the [+] sign next to any icon to view module information and
configuration options.
3 Double-click any icon to open an Edit dialog box.
4 To edit a parameter, select the parameter in the left pane and make your
changes in the right pane.
5 Click OK to save your changes.

Using ProSoft Configuration Builder MVI56E-GEC ♦ ControlLogix Platform
User Manual Generic ASCII Ethernet Communication Module
Page 14 of 80 ProSoft Technology, Inc.
Creating Optional Comment Entries
1 Click the [+] to the left of the icon to expand the module
comments.
2 Double-click the icon. The Edit - Module Comment dialog box
appears.
3 Enter your comment and click OK to save your changes.
Printing a Configuration File
1 Select the module icon, and then click the right mouse button to open a
shortcut menu.
2 On the shortcut menu, choose VIEW CONFIGURATION.This action opens the
View Configuration window.
3 In the View Configuration window, open the FILE menu, and choose PRINT.
This action opens the Print dialog box.
4 In the Print dialog box, choose the printer to use from the drop-down list,
select printing options, and then click OK.

MVI56E-GEC ♦ ControlLogix Platform Using ProSoft Configuration Builder
Generic ASCII Ethernet Communication Module User Manual
ProSoft Technology, Inc. Page 15 of 80
2.2 [Server x]
You can configure up to five servers ([Server 0] through [Server 4]). The
configuration section for each server contains the same set of parameters. You
can configure the parameters for each server to meet the requirements of your
application.
2.2.1 Enabled
Yes or No
This parameter determines if the server will be utilized by the module. If a value
of "Yes" is entered, the server will be used. Any other value will disable the
server.
2.2.2 Service Port Number
1 to 65535
This parameter sets the TCP/IP service port for this server. Each server can
have its own unique service port or can share the same number with other
servers.
2.2.3 Connection Timeout
0 or 5000 to 65535
This parameter specifies the number of milliseconds the server will permit the
server to be inactive after a connection is made before closing the socket. This
timeout period is reset on each read or write packet. If the parameter is set to 0,
the connection will not timeout.
2.2.4 Connection Close Type
0, 1 or 2
This coded parameter defines the personality of the server after a connection is
made. If the parameter is set to 0, the socket will only be closed when a request
from the client is received or the connection timeout is exceeded. If a value of 1
is selected, the server will close the socket after it transmits a single message. If
a value of 2 is selected, the server will close the socket after it receives a
message.
2.2.5 Swap Rx Data Bytes
Yes or No
This parameter determines if the data received by the server will have the byte
order of the data swapped. If the parameter is set to No, no byte swapping will
occur. If the parameter is set to Yes, the odd byte will be swapped with the even
byte in each word of data received.

Using ProSoft Configuration Builder MVI56E-GEC ♦ ControlLogix Platform
User Manual Generic ASCII Ethernet Communication Module
Page 16 of 80 ProSoft Technology, Inc.
2.2.6 Swap Tx Data Bytes
Yes or No
This parameter determines if the data to be transmitted by the module will have
the byte order of the data swapped. If the parameter is set to No, no byte
swapping will occur. If the parameter is set to Yes, the odd byte will be swapped
with the even byte in each word of data received.

MVI56E-GEC ♦ ControlLogix Platform Using ProSoft Configuration Builder
Generic ASCII Ethernet Communication Module User Manual
ProSoft Technology, Inc. Page 17 of 80
2.3 Ethernet 1 Configuration
Use this procedure to configure the Ethernet settings for your module. You must
assign an IP address, subnet mask and gateway address. After you complete
this step, you can connect to the module with an Ethernet cable.
1 Determine the network settings for your module, with the help of your network
administrator if necessary. You will need the following information: IP address
(fixed IP required), Subnet mask, Gateway address
Note: The gateway address is not required for networks that do not use a default gateway.
2 Double-click the ETHERNET 1icon.
3 This action opens the Edit –Ethernet 1 dialog box.
4 Edit the values for my_ip, netmask (subnet mask) and gateway (default
gateway).
5 When you are finished editing, click OK to save your changes and return to
the ProSoft Configuration Builder window.

Using ProSoft Configuration Builder MVI56E-GEC ♦ ControlLogix Platform
User Manual Generic ASCII Ethernet Communication Module
Page 18 of 80 ProSoft Technology, Inc.
2.4 Assigning a Temporary IP Address
You can assign a temporary IP address to the module using the ProSoft
Discovery Service utility. This utility is installed within ProSoft Configuration
Builder (PCB).
1 In PCB, click on the Diagnostics icon in the shortcuts menu, or right-click on
the module’s icon and select DIAGNOSTICS.
2 The Diagnostics dialog opens. Click on the Connection Setup icon, or select
CONNECTION >CONNECTION SETUP.

MVI56E-GEC ♦ ControlLogix Platform Using ProSoft Configuration Builder
Generic ASCII Ethernet Communication Module User Manual
ProSoft Technology, Inc. Page 19 of 80
3 In the Connection Setup dialog box, click BROWSE DEVICE(S)to start ProSoft
Discovery Service.
4 ProSoft Discovery Service scans the network for ProSoft devices. Click on
the icon to manually initiate a search.

Using ProSoft Configuration Builder MVI56E-GEC ♦ ControlLogix Platform
User Manual Generic ASCII Ethernet Communication Module
Page 20 of 80 ProSoft Technology, Inc.
5 Right-click the module icon and select ASSIGN TEMPORARY IP.
6 Enter the Temporary IP and Network Mask.
7 To view the current parameters of the MVI56E-GEC, right-click on the module
icon and select Device Details.
Table of contents
Other ProSoft Control Unit manuals

ProSoft
ProSoft inRAx MVI46-BSAPS User manual

ProSoft
ProSoft MVI46-S3964R User manual

ProSoft
ProSoft MVI56-HART User manual

ProSoft
ProSoft MVI56E-MNETCR User manual

ProSoft
ProSoft inRAx MVI56-MNETCR User manual

ProSoft
ProSoft MVI56E-MCMR User manual

ProSoft
ProSoft MVI69E-MBS User manual

ProSoft
ProSoft ProLinx 6104-WA-PDPM User manual

ProSoft
ProSoft MVI69E-MBTCP User manual

ProSoft
ProSoft PLX51-DF1-MSG User manual