3.
Model F156 EC Pendent & F156 Recessed
EC Pendent Sprinklers
Application
Model F156 EC and F156 EC Recessed sprinklers are
used in fixed fire protection systems: Wet, Dry, Deluge or
Preaction. Care must exercised that the orifice size, tem-
perature rating, deflector style and sprinkler type are in
accordance with the latest published standards of the Na-
tional Fire Protection Association or the approving Author-
ity Having Jurisdiction.
Installation
Model F156 EC sprinklers are standard response sprin-
klers intended for installation as specified in NFPA 13. They
must also be installed with the Model D Sprinkler Wrench
specifically designed by Reliable for use with these sprin-
klers.
The Model F156 EC Recessed Sprinklers are to be in-
stalled with a maximum recess of ¾ inch (19mm). The
Model F1, F2, and FP Escutcheons illustrated are the only
recessed escutcheons to be used with the Model F156 EC
Sprinklers. The use of any other recessed escutcheon will
void all approvals and negate all warranties. When install-
ing Model F156 EC Recessed Pendent and EC Pendent
Sprinklers, use the Model GFR2 Sprinkler Wrench. Any
other type of wrench may damage these sprinklers.
Glass bulb sprinklers have orange covers to protect
the bulb during the installation process. REMOVE THIS
PROTECTION ONLY AFTER THE SYSTEM HAS BEEN
HYDROSTATICALLY TESTED AND, WHEN APPLICABLE,
THE ESCUTCHEONS HAVE BEEN INSTALLED. RASCO
wrenches are designed to install sprinklers when covers
are in place.
Maintenance
The Models F156 EC and F156 EC Recessed Sprinklers
should be inspected and the sprinkler system maintained
in accordance with NFPA 25. Do not clean sprinklers with
soap and water, ammonia or any other cleaning fluid. Re-
move any sprinkler which has been painted (other than
factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replace-
ment of damaged or operated sprinklers. Prior to instal-
lation, sprinklers should be maintained in the original car-
tons and packaging until used to minimize the potential for
damage to sprinklers that would cause improper opera-
tion or non-operation.
Escutcheon Data
Escutcheon
Model Adjustment “A”
Dimension
Face of Fitting
to Ceiling or Wall
Dimension
F1 Max Recessed
Min Recessed
11/2” (38.1mm)
3/4” (19.1mm)
3/16” - 15/16”
(5m - 24mm)
F2 Max Recessed
Min Recessed
11/2” (38.1mm)
1” (25mm)
3/16” - 11/16”
(5m - 17mm)
FP Push-on/
Thread-off
Max Recessed
Min Recessed
7/16” (11mm)
15/16” (24mm)
11/2” (38.1mm)
1” (25mm)
Standard Temperature Rating
Classification
Sprinkler
Temperature
Maximum
Ambient
Temperature
Bulb
Color
°F °C °F °C
Ordinary
Ordinary
135
155
57
68
100
100
38
38
Orange
Red
Maximum Working Pressure
175 psi (12 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)
Finishes (1)
Standard Finishes
Sprinkler Escutcheon
Bronze
Chrome
White or Black
Polyester Coated(5)
Brass
Chrome
White Painted
Special Applications Finishes
Sprinkler Escutcheon
Electroless Nickel
PTFE(Teflon®)*(5)
Bright Brass(2)
Black Plating
Black Paint
Off White
Satin Chrome
Lead Plated(3)
Wax Coated(3)(4)
Wax Over Lead(3)
Electroless Nickel
PTFE (Teflon®)*
Bright Brass
Black Plating
Black Paint
Off White
Chrome Dull
(1) Other colors and finishes are available on special order. Consult fac-
tory for details.
(2) 200°F (93°C) maximum.
(3) 155°F to 200°F (68°C to 93°C) ratings only.
(4) 286°F (141°C) sprinklers may be coated for ambient conditions not
exceeding 150°F (66°C).
(5) Corrosion Resistant
Note: Paint or any other coating applied over the factory finish will void
approvals and waranties.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6. Sprinkler Finish
7. Escutcheon Finish (where applicable)
Note: When Model F156 EC Recessed Pendent Sprinklers
are ordered, the sprinklers and escutcheons are
packaged separately.
*DuPont Registered Trademark