Guarantee
For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms,
and conditions, visit www.reliablesprinkler.com.
Ordering Information
Specify the following when ordering:
Model
• [F1FR56SS] [F1FR80SS]
Orientation
• [Upright] [Pendent]
Temperature Rating
• See sprinkler pages
Threads
• [NPT] [ISO7-1]
Sprinkler Finish
• See Table B
Recessed Escutcheon (SS)
• [F1] [F2] [FP]
One-Piece Escutcheon (SS)
• B
Escutcheon Finish
• See Table B
Sprinkler Wrench
• Model W2 (upright, non-recessed pendent)
• Model W4 (recessed pendent)
Maintenance
Model F1FR-SS series sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25. Do
not clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by gentle vacuuming. Replace any
sprinkler which has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinklers should be main-
tained to allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained in the
original cartons and packaging until used to minimize the potential
for damage to sprinklers that would cause improper operation or
non-operation.
Bulletin 065
November 2022
Page 7 of 7
www.reliablesprinkler.com
Listings and Approvals
• cULus Listed
• FM Approved
• VdS Approved, CE Listed (see sprinkler pages for number)
P/N 9999970522
Installation
Glass bulb sprinklers have orange bulb protectors to minimize bulb
damage during shipping, handling, and installation. Reliable sprin-
kler installation wrenches are designed to install sprinklers with bulb
protectors in place. Remove the bulb protector at the time when the
sprinkler system is placed in service for re protection. Removal of
the bulb protector before this time may leave the bulb vulnerable to
damage. Remove bulb protectors by undoing the clasp by hand. Do
not use tools to remove bulb protectors.
Model F1FR-SS series sprinklers must be installed with the Reli-
able sprinkler installation wrench identied in this Bulletin. Any other
wrench may damage the sprinkler. Recommended installation torque
is 8 to 18 lb/ft (11 to 24 N/m) for 1/2” NPT and ISO7-1R1/2 sprinklers
or 14 to 20 lb/ft (19 to 27 N/m) for 3/4” NPT and ISO7-1R3/4 sprin-
klers. Do not tighten sprinklers over the maximum recommended in-
stallation torque. Exceeding the maximum recommended installation
torque may cause leakage or impairment of the sprinkler.
Recessed pendent sprinklers are to be installed as shown in Fig. 5.
Model F1FR-SS series recessed pendent sprinklers may only be in-
stalled with the Reliable Model F1 stainless steel, Model F2 stainless
steel, or Model FP stainless steel recessed escutcheon. The use of
any other recessed escutcheon will void all approvals and negate all
warranties.
Application
Model F1FR-SS series sprinklers are standard spray, quick-re-
sponse sprinklers intended for installation in accordance with
NFPA 13 and the requirements of applicable Authorities Having
Jurisdiction. Model F1FR-SS series sprinklers are cULus Listed
and FM Approved as Corrosion Resistant sprinklers. Verify com-
patibility with the environment where the sprinkler will be located
prior to installation.
Wrench
Model W2 (upright, non-recessed pendent) Model W4 (recessed pendent)
Sprinkler Finishes Escutcheon Finishes
None
White Polyester
Custom Color Polyester
None
White Polyester
Custom Color Polyester
Table B
Finishes