Ordering Information
Specify:
Sprinkler
• Model F1FR-FS42 Sprinkler
• Model F1FR-FS56 Sprinkler
Temperature Rating
• 135°F (57°C)
• 155°F (68°C)
• 175°F (79°C)
• 200°F (93°C)
• 286°F (141°C)
End Connection
• 1/2 NPT
• ISO7-1R1/2 (BSPT)
Finish
• Bronze
Shield (Optional, order separately)
• Galvanized (PN 6999995574)
Note: When shields are ordered, the sprinklers and shields are
packaged separately.
Wrenches Figure 3
W2 Wrench (pendent)
W4 Wrench (w/shield)
Installation
Model F1FR-FS Series sprinklers must be installed in accordance
with CEA 4001 and EN 12845, and the requirements of all
applicable authorities having jurisdiction. Model F1FR-FS Series
sprinklers must be installed with the Reliable sprinkler installation
wrench identied in this Bulletin. Any other wrench may damage
the sprinkler.
When installed without a water shield, the Model W2 wrench
must be used. When installed with a water shield, the Model
W4 wrench must be used. The Models W2 and W4 wrenches
have two sets of jaws. Use the smallest set of jaws that t on
the wrench flats of the sprinkler. A leak tight sprinkler joint can
be obtained with a torque of 8 to 18 lb-ft (11 to 24 N.m). Do not
tighten sprinklers over the maximum recommended installation
torque. Exceeding the maximum recommended installation torque
may cause leakage or impairment of the sprinkler.
Glass bulb sprinklers have orange bulb protectors to minimize
bulb damage during shipping, handling and installation. Reliable
sprinkler installation wrenches are designed to install sprinklers
with bulb protectors in place. Remove the bulb protector at
the time when the sprinkler system is placed in service for re
protection. Removal of the bulb protector before this time may
leave the bulb vulnerable to damage. Remove bulb protectors
by undoing the clasp by hand. Do not use tools to remove bulb
protectors.
Maintenance
Reliable Model F1FR-FS Series sprinklers should be inspected
and the sprinkler system maintained in accordance with NFPA 25,
as well as the requirements of any Authorities Having Jurisdiction.
Prior to installation, sprinklers should remain in the original
cartons and packaging until used. This will minimize the potential
for damage to sprinklers that could cause improper operation or
non-operation.
Do not clean sprinklers with soap and water, ammonia liquid or
any other cleaning fluids. Remove dust by gentle vacuuming
without touching the sprinkler.
Replace any sprinkler which has been painted (other than factory
applied). A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprinklers.
Failure to properly maintain sprinklers may result in inadvertent
operation or non-operation during a re event.
Guarantee
For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms,
and conditions, visit www.reliablesprinkler.com.
Bulletin 022
May 2023
Page 3 of 3
www.reliablesprinkler.com
P/N 9999970360