
3
Installation
Quick response sprinklers are intended for installation as
specified in NFPA 13, FM Global Loss Prevention Data Sheet
2-8N or other applicable standards. Quick response sprinklers
and standard response sprinklers should not be intermixed.
The Model F1FR LO Recessed Quick Response Sprinklers
are to be installed as shown. The Model F1 or F2 Escutcheons
illustrated are the only recessed escutcheons to be used with
the Model F1FR LO Sprinklers. The use of any other recessed
escutcheon will void all approvals and negate all warranties.
When installing Model F1FR LO Sprinklers, use the Model D
Sprinkler Wrench. When installing Model F1FR LO Recessed
Pendent or Sidewall Sprinklers, use the Model GFR1 Sprinkler
Wrench. Any other type of wrench may damage these sprinklers.
Glass bulb sprinklers have orange bulb protectors to minimize
bulb damage during shipping, handling and installation.
REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER
SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION.
Removal of the protectors before this time may leave the bulb
vulnerable to damage. RASCO wrenches are designed to install
sprinklers when covers are in place. REMOVE PROTECTORS
BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS
TO REMOVE THE PROTECTORS.
Temperature Ratings
Classification
Sprinkler
Temperature
Maximum
Ambient
Temperature
Bulb
Color
°F °C °F °C
Ordinary 135 57 100 38 Orange
Ordinary 155 68 100 38 Red
Intermediate 175 79 150 66 Yellow
Intermediate 200 93 150 66 Green
High(1) 286 141 225 107 Blue
(1) Not Available for recessed sprinklers.
Escutcheon Data
Escutcheon
Model Adjustment “A”
Dimension
Face of Fitting to
Ceiling or Wall
Dimension
F1 Max Recess
Min Recess 1
1/2” (38.1 mm)
3/4” (19.1 mm)
3/16” - 15/16”
(5 mm - 24 mm)
F2 Max Recess
Min Recess 1
1/2” (38.1 mm)
1” (24.5 mm)
3/16” - 11/16”
(5 mm - 17 mm)
FP Push-on/
Thread-off Max Recessed
Min Recessed
5/16” (8 mm)
15/16” (24 mm) 1
1/2” - 1”
(38.1 mm - 25.4 mm)
Maintenance
TheModelsF1FRLOandF1FRLORecessedSprinklersshould
be inspected quarterly and the sprinkler system maintained in
accordance with NFPA 25. Do not clean sprinklers with soap
and water, ammonia or any other cleaning fluids. Remove
dust by using a soft brush or gentle vacuuming. Remove any
sprinkler which has been painted (other than factory applied)
or damaged in any way. A stock of spare sprinklers should be
maintained to allow quick replacement of damaged or operated
sprinklers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to minimize the
potential for damage to sprinklers that would cause improper
operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Recessed Pendent
Finishes(1)(2)
Standard Finishes
Sprinkler Escutcheon
Bronze
Chrome Plated
White Polyester Coated
Brass
Chrome Plated
White Painted
Special Application Finishes
Sprinkler Escutcheon
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
(1) Other finishes and colors are available on special order. Consult the
factory for details.
(2) FP Push-on/Thread-off escutcheon.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6. Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where applicable)
Note: When Model F1FR LO Recessed sprinklers are ordered,
the sprinklers and escutcheons are packaged separately.