  9. Reliable F1FR40 Manual

Reliable F1FR40 Manual

Other Reliable Irrigation System manuals

Reliable F1FR80 Series User manual

Reliable

Reliable F1FR80 Series User manual

Reliable JL-14 User manual

Reliable

Reliable JL-14 User manual

Reliable J112SS Series Manual

Reliable

Reliable J112SS Series Manual

Reliable F3QR56 User manual

Reliable

Reliable F3QR56 User manual

Reliable N252 EC User manual

Reliable

Reliable N252 EC User manual

Reliable F3-80 Dry Pendent User manual

Reliable

Reliable F3-80 Dry Pendent User manual

Reliable F1FR LO Series Manual

Reliable

Reliable F1FR LO Series Manual

Reliable G4 User manual

Reliable

Reliable G4 User manual

Reliable DH56 HSW-PL User manual

Reliable

Reliable DH56 HSW-PL User manual

Reliable F156 Series Manual

Reliable

Reliable F156 Series Manual

Reliable F1FR-FS LO Manual

Reliable

Reliable F1FR-FS LO Manual

Reliable F1FR80VdS Series Manual

Reliable

Reliable F1FR80VdS Series Manual

Reliable N252 EC User manual

Reliable

Reliable N252 EC User manual

Reliable F1 LO User manual

Reliable

Reliable F1 LO User manual

Reliable JL-14 User manual

Reliable

Reliable JL-14 User manual

Reliable G4 User manual

Reliable

Reliable G4 User manual

Reliable G User manual

Reliable

Reliable G User manual

Reliable KFR-CCS User manual

Reliable

Reliable KFR-CCS User manual

Reliable F1 Series Manual

Reliable

Reliable F1 Series Manual

Reliable XL Series User manual

Reliable

Reliable XL Series User manual

Reliable DH56 HSW-PL User manual

Reliable

Reliable DH56 HSW-PL User manual

Reliable F1-300 User manual

Reliable

Reliable F1-300 User manual

Reliable LT56 Series User manual

Reliable

Reliable LT56 Series User manual

Reliable G Series Manual

Reliable

Reliable G Series Manual

Popular Irrigation System manuals by other brands

Tyco TY-B Series manual

Tyco

Tyco TY-B Series manual

Toro ZSERIES 570Z brochure

Toro

Toro ZSERIES 570Z brochure

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Tyco Fire Product Star Galaxy SGQR instruction manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR instruction manual

Tyco Fire Product CENTRAL A instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL A instruction manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Tyco Fire Product Gem F892 instruction manual

Tyco Fire Product

Tyco Fire Product Gem F892 instruction manual

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Tyco Fire Product CENTRAL ELO-231 instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231 instruction manual

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Model F1FR40 Pendent
Note: Not all versions of
the product are shown.
F1FR Series Sprinklers Summary
Sprinkler
Model
K-Factor gpm/psi1/2
(lpm/bar1/2)Orientation Listings & Approvals Max. Working Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
F1FR40 4.0 (57) Pendent VdS 175 psi (12 bar) RA1418
Table A
Model F1FR40 Pendent
Recessed, FP Escutcheon
Model F1FR40 Pendent
Recessed, F1 Escutcheon
(F2 escutcheon similar)
Features
• Standard coverage quick response sprinklers
• Pendent and recessed pendent application
• Low profile, compact design
• Available in a wide variety of finishes
Product Description
The Reliable Model F1FR40 is a quick-response, standard
spray pendent automatic fire sprinkler utilizing a sensitive 3.0 mm
glass bulb thermal element.
The Model F1FR40 pendent sprinkler may be installed
exposed or surface mounted using escutcheons such as the
Reliable Models B, C, or HB (reference Technical Bulletin 204).
When installed recessed the sprinkler is specifically listed
and may only be installed with listed escutcheons. Refer to
the technical information on the following pages for specific
listings for recessed sprinklers, and refer to Figure 2 for
dimensional information.
Table A provides a summary of the approvals and availability
for the Model F1FR40 sprinkler.
www.reliablesprinkler.com
K-factor 4.0 (57)
F1FR40 (VdS)
Standard Spray Sprinkler
Bulletin 183 October 2020
Model F1FR40 Pendent Sprinkler SIN RA1418
Technical Specifications
Style: Pendent or Recessed Pendent
Threads: 1/2” NPT or ISO 7-R1/2
Nominal K-Factor: 4.0 (57 metric)
Max. Working Pressure: 175 psi (12 bar)
Material Specifications
Thermal Sensor: 3 mm Glass Bulb
Sprinkler Frame: Brass Alloy
Cap: Bronze Alloy
Sealing Washer: Nickel with PTFE
Load Screw: Copper Alloy
Deflector: Brass Alloy
Sprinkler Finishes
(See Table B)
Sensitivity
Quick-response
Temperature Ratings
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)*
Recessed Escutcheons
Model F1
Model F2
Model FP
Sprinkler Wrenches
Model W2 (pendent)
Model W4 (recessed pendent)
Listings and Approvals
VdS
*Note: 286°F (141°C) temperature rated sprinkler not listed for recessed use.
Model F1FR40 Pendent Sprinkler Components and Dimensions Figure 1
Bulletin 183
October 2020
Page 2 of 4
www.reliablesprinkler.com
Recessed Installation: Pendent Sprinklers Figure 2
Wrenches
Model W2 (pendent)
Model W4 (recessed pendent)
Installation
Model F1FR Series sprinklers must be installed with the
W2 (pendent) or W4 (recessed pendent) Reliable sprinkler
installation wrench as identified in this Bulletin. Any other wrench
may damage the sprinkler. The Models W2 and W4 wrenches
have two sets of jaws. Use the smallest set of jaws that fit the
wrench flats of the sprinkler. A leak tight sprinkler joint can be
obtained with a torque of 8 to 18 lb-ft (11 to 24 N-m). Do not
tighten sprinklers over the maximum recommended installation
torque. Exceeding the maximum recommended installation
torque may cause leakage or impairment of the sprinkler.
Both the Model W2 and W4 wrench have two sets of jaws.
Use the smallest set of jaws that fit on the wrench flats of the
sprinkler. The Model W4 wrench is used in conjunction with
a nominal 1/2” square drive ratchet with a nominal 5” long
extension (not provided).
Glass bulb sprinklers have orange bulb protectors or protective
caps to minimize bulb damage during shipping, handling
and installation. Reliable sprinkler installation wrenches are
designed to install sprinklers with bulb protectors in place.
Remove the bulb protector at the time when the sprinkler
system is placed in service for fire protection. Removal of the
bulb protector before this time may leave the bulb vulnerable
to damage. Remove bulb protectors by undoing the clasp by
hand. Do not use tools to remove bulb protectors.
Bulletin 183
October 2020
Page 3 of 4
www.reliablesprinkler.com
Standard Finishes Special Application Finishes
Sprinkler F1, F2 and FP(3)
Escutcheons Sprinkler F1, F2 and FP(3)
Escutcheons
Bronze Brass Electroless Nickel PTFE Bright Brass
Chrome Plated Chrome Plated Bright Brass(4) Black Plated
White Polyester White Polyester Black Plated Black Paint
Black Paint Off White
Off White Chrome Dull
Chrome Dull
Notes:
1. Other finishes and colors are available on special order. Consult your Reliable sales representative for details.
2. Paint or any other coating applied over the factory finish will void all approvals and warranties.
3. The Model FP assembly consists of a sprinkler mounted in a galvanized steel cup with a finished trim ring.
4. For 200°F (93°C) maximum temperature rated sprinklers only.
Sprinkler and Escutcheon Finishes(1)(2) Table B
Maintenance
Reliable Model F1FR series sprinklers should be inspected
and the sprinkler system maintained in accordance with NFPA
25, as well as the requirements of any Authorities Having
Jurisdiction.
Prior to installation, sprinklers should remain in the original
cartons and packaging until used. This will minimize the
potential for damage to sprinklers that could cause improper
operation or non-operation.
Do not clean sprinklers with soap and water, ammonia
liquid or any other cleaning fluids. Remove dust by gentle
vacuuming without touching the sprinkler.
Replace any sprinkler which has been painted (other than
factory applied). A stock of spare sprinklers should be
maintained to allow quick replacement of damaged or
operated sprinklers. Failure to properly maintain sprinklers
may result in inadvertent operation or non-operation during a
fire event.
Guarantee
For the guarantee, terms, and conditions, visit www.
reliablesprinkler.com.
Ordering Information
F1FR40 Ordering Information
Specify the following when ordering:
• Deflector/Orientation
Pendent
Pendent - FP
• Temperature Rating
• Sprinkler Finish
See Table B
• Recessed Escutcheon*
F1
F2
FP
• Escutcheon Finish
See Table B
• Sprinkler Wrench
Model W-2 (pendent)
Model W-4 (recessed pendent)
*Note: 286°F (141°C) sprinklers are not listed to be used
recessed.
P/N 9999970607
Bulletin 183
October 2020
Page 4 of 4
www.reliablesprinkler.com