The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Application and Installation
Model F1FR QREC Concealed Sprinklers use 135°F (57°C)
or 155°F (68°C) Model F1FR QREC Pendent Sprinklers with a
threaded Model CCP cup which is factory attached to the sprin-
kler. The assembly is completed by the installation of the attrac-
tive, low profile, 135°F (57°C) rated cover plate assembly. The
cover plate and sprinkler cup are joined using a flexible tooth
threaded engagement. A choice of two cover plate assemblies
provides either ½” (13mm) or 5
/
16” (8mm) of cover adjustment.
Do not install these sprinklers in ceilings which have positive
pressure in the space above.
The sprinkler cup is factory attached to the Model F1FR QREC
Sprinkler. A Teflon*-based thread sealant should be applied to
the sprinkler threads only.
After a 25
/
8 inch (67mm) diameter hole is cut in the ceiling,
the sprinkler is easily installed with the Model GFR2 Wrench.
When installing a sprinkler, the protective cap is removed and
the wrench is positioned into the sprinkler/cup assembly until
the two wrench faces engage the wrenching flats on the Model
F1FR QREC Sprinkler. The sprinkler is then tightened into the
pipe fitting. When inserting or removing the wrench from the
sprinkler/cup assembly, care should be taken to prevent dam-
age to the sprinkler. DO NOT WRENCH ON ANY OTHER
PART OF THE SPRINKLER. The cover plate assembly is then
pressed into the cup. Final adjustment is made by turning the
cover plate until the skirt flange makes full contact with the ceil-
ing surface. Cover plate removal requires turning in the counter
clockwise direction.
After installation, inspect all sprinklers to ensure that there is
a gap between the cover plate and ceiling and that the four
cup slots are open and free from any air flow impediment to the
space above.
Concealed cover plate/cup assemblies are listed only for use
with specific sprinklers. The use of any other concealed cover
plate/cup assembly with the Model F1FR QREC Pendent Sprin-
kler or the use of the Model CCP concealed cover plate assem-
bly on any sprinkler with which it is not specifically listed may
prevent good fire protection and will void all guarantees, warran-
ties, listings and approvals.
Maintenance
Model F1FR QREC Concealed Sprinklers should be inspect-
ed and the sprinkler system maintained in accordance with
NFPA 25. Do not clean sprinklers with soap and water, ammo-
nia or any other cleaning fluids. Remove dust by using a soft
brush or gentle vacuuming. Remove any sprinkler cover plate
assembly which has been painted (other than factory applied)
or damaged in any way. A stock of spare sprinklers should be
maintained to allow quick replacement of damaged or operated
sprinklers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to minimize the
potential for damage to sprinklers that would cause improper
operation or non-operation.
* DuPont Registered Trademark.
Approval Organizations
1. Underwriters Laboratories, Inc.
(UL)
2. Underwriters’ Laboratories of
Canada (ULC)
3. NYC MEA 258-93-E
UL Listing Category
Sprinklers, Automatic and Open.
Quick Response Extended Cover-
age Sprinklers.
Ordering Information
Specify:
1. Sprinkler Model:
F1FR QREC Pendent
17
/
32” (20mm) Orifice, ¾” NPT
(R¾).
2. Sprinkler Temp. Rating(1):
135°F (57°C) or
155°F (68°C).
3. Cover plate Model: CCP
4. Cover plate thread size:
¾” NPT (R¾).
5. Cover plate temp. rating:
135°F (57°C).
6. Cover plate adjustment:
Either ½” (13mm) or 5
/
16” (8mm)
(approximate adjustment).
7. Cover plate finish.
(1)135°F (57°C) required for
20’ x 20’ (6.0m x 6.0m).
Installation Wrench
Model GFR2 Sprinkler Wrench
Installation Aid
A protective cap is included for
use during installation.
Cover Plate Finishes(1)
Standard Finishes
Chrome
White
Special Application Finishes
Bright Brass
Black Plating
Black Paint
Off White
Satin Chrome
(1) Other finishes and colors are
available on special order.
Consult factory for details.
Note: Paint or any other coatings
applied over the factory finish will
void all approvals and warranties.
Important: The F1FR QREC
Sprinkler with the Model CCP
cover plate is not an FM Approved
combination.