Standard Finishes Special Application Finishes
Sprinkler(1) FV, FP(4)
Escutcheons
CCP, G4
Cover Plate Sprinkler FV, FP(3)
Escutcheons
CCP, G4
Cover Plate
Bronze Brass Bright Brass Bright Brass Bright Brass
Chrome Plated Chrome Plated Chrome Plated Dull Chrome Dull Chrome Chrome Dull
White Polyester(3) White Polyester White Paint Black Polyester(3) Black Polyester Black Paint
Custom Color
Polyester
Custom Color
Polyester Custom Color Paint
Electroless Nickel
PTFE(3)
Electroless Nickel
PTFE
Notes:
1. Model LT56, LT56L, LT56-300, and LT56L-300 only.
2. Paint or any other coating applied over the factory finish will void all approvals and warranties.
3. cULus Listed Corrosion Resistant, Models LT56 (RA5814) and LT56-300 (RA5914) only.
4. The Model FP escutcheon assembly consists of an unfinished galvanized cup with a finished escutcheon ring.
Sprinkler, Escutcheon, & Cover Plate Finishes(2) Table H
Application
Model LT56 series sprinklers are cULus Listed Specific Applica-
tion sprinklers for use in Light Hazard corridors and hallways in
accordance with NFPA 13. The sprinklers are classified as Spe-
cial Sprinklers based on the maximum and minimum allowable
spacing, but shall otherwise be designed in accordance with the
requirements of NFPA 13 for Extended Coverage Pendent Spray
sprinklers. Model LT56 series sprinklers are quick-response sprin-
klers for use in Light Hazard occupancies only.
The sprinklers must be hydraulically designed using the minimum
flow and pressure specified in the Hydraulic Design Criteria ta-
bles in this Bulletin. Figure 7 outlines the maximum coverage area
of Model LT56 series sprinklers. Figure 8 identifies the sprinklers
that can be located adjacent to Model LT56 series sprinklers; note
that LT56 series sprinkler are not permitted to be installed with the
short coverage length oriented towards the short coverage length
of an adjacent LT56 series sprinkler. An example layout of Model
LT56 series sprinklers is illustrated in Figure 9.
escutcheons, and Model CCP cover plate, are the only recessed
escutcheons and concealed cover plate to be used with Mod-
el LT56, LT56L, LT56-300 and LT56L-300 sprinklers. The Model
G4 cover plate is the only concealed cover plate permitted for
use with the Model LT56C sprinkler. Use of any other recessed
escutcheon or cover plate will void all approvals and warranties.
Do not install Model FV and FP escutcheons or Model CCP and
G4 cover plates in ceilings that are positively pressurized with
respect to the occupied space below.
When installing Model LT56, LT56L, LT56-300, and LT56L-300
sprinklers use only the Model D wrench for pendent installations
and the Model GFR2 wrench for recessed pendent and concealed
installation. The Model LT56C sprinkler must be installed with the
Model FC wrench. Use of wrenches other than those specified
may damage these sprinklers.
Model LT56 series sprinklers must be installed with the frame arms
or towers perpendicular to the length of the corridor or hallway.
The deflector is marked with “<-28 FT->” to indicate the direction
of the 28 ft. (8.5 m) coverage length. Model LT56 series sprinklers
need not be installed with the frame arms or towers parallel to the
sprinkler pipe.
Recommended installation torque is 8-18 ft-lbs (11 – 24 N-m). Do
not tighten sprinklers over the maximum recommended torque.
Exceeding the maximum recommended torque may cause leak-
age or impairment of the sprinklers.
Do not install any glass bulb sprinklers where the bulb is cracked
or there is a loss of liquid from the bulb.
Glass bulb sprinklers have orange bulb protectors to minimize
bulb damage during shipping, handling and installation. Remove
the bulb protector at the time the sprinkler system is placed in
service for fire protection. Removal of the bulb protectors before
this time may leave the bulb vulnerable to damage. The required
sprinkler wrenches are designed to install sprinklers with bulb
protectors in place. Remove bulb protectors by undoing the clasp
by hand. Do not use tools to remove the bulb protectors.
Listings and Approvals
Listed by Underwriters Laboratories, Inc. and UL Certified for
Canada (cULus)
UL Listing Category
Sprinklers, Automatic and Open
UL Guide Number
VNIV
Installation
Model LT56 series sprinklers must be installed in accordance with
the requirements of the MFPA 13 for pendent sprinklers and may
also be installed as a recessed sprinkler or concealed sprinkler as
shown in Figure 6. The Model FV and FP recessed
Bulletin 058 Rev. B
November 2016
Page 8 of 10
www.reliablesprinkler.com