The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Bulletin 146 Rev. H
Bulletin 146 Rev. H
Model G VELO Pendent
Very Extra Large Orice Sprinkler
Low Pressures for High Hazards
0.70” Orice, 14.0 K, 7psi (0,5 bar)
Minimum End - Head Pressure
(SIN R4613)
Features
The Reliable Model G VELO pendent sprinkler
offers opportunity for:
1. Pipe size reduction.
2. Fewer sprinklers.
3. Elimination of booster pumps.
4. The best choice for densities of 0.38 gpm/ft2
(15 L/min /m2) or larger.
5. Simplifies future ESFR conversions.
US Patents: 5.890.657 and 5.915.479
Listings & Approvals
1. Listed by Underwriters Laboratories, Inc. and
Certified by UL for Canada (cULus).
2. Approved by Factory Mutual (FM) as a storage sprinkler.
3. NYC MEA 258-93-E
UL Guide Number
VNIV
UL Listing Category
Sprinklers, Automatic and Open; Sprinklers for Storage
Protection (Control Mode Density Area)
Technical Data
Sprinkler
Type
Nominal
K Factor Sprinkler
Height
Sprinkler Identication
Number (SIN)
US Metric
Pendent 0.70
orifice with ¾”
NPT (R¾)
14.0 200.0 3.10”
(79mm) R4613
Note: This product has been tested and listed for storage applications
to qualify its use in lieu of 5.6K or 8.0K Factor sprinklers for the
protection of high-piled storage
Product Description
The Reliable Model G VELO sprinkler is a Very Extra
Large Orifice pendent sprinkler that has been designed
to control high challenge fires in both palletized and rack
storage occupancies utilizing lower water pressures. The
Model G VELO pendent utilizes a center strut solder in
compression fusible element.
It has been proven in UL and FM full-scale fire testing
and complies with all applicable mechanical and hydrau-
lic requirements of the latest sprinkler standards.
This product is intended for use as a standard response
standard spray sprinkler in hydraulically designed systems
with a minimum pressure of 7 psi (0,5 bar) in accordance
with the area/density curves of NFPA 13*.
Design Criteria
The following criteria apply when designing an automatic
sprinkler system utilizing the Model G VELO sprinkler for
NFPA 13* applications.
• Sprinkler spacing shall be a minimum of 6 ft. (1.8m).
• Minimum design pressure 7 psi (0,5 bar).
• Factory Mutual (FM) Approval for Model G VELO sprin-
kler allows installation into drops or branch line fittings.
• Factory Mutual (FM) Loss Prevention Data Sheets con-
tain requirements which differ from NFPA. The Model G
VELO is Approved by Factory Mutual installations gov-
erned by Data Sheets 8-9 and 2-0.
Note: The Model G VELO sprinkler is not a “Large Drop”
or “ESFR sprinkler”.
Temperature Ratings
Classication
Sprinkler
Rating
Maximum Ceiling
Temperature Frame
Color
°F °C °F °C
Ordinary
Intermediate
High
165
212
286
74
100
141
100
150
225
38
66
107
Uncolored
White
Blue
* For sprinkler standards prior to 1999 edition of NFPA 13 use NFPA
standards 231, 231C, 231D & 231F.