Three Phase Duplex Control Panel
Installation and Operation Manual
OSD3P-30XX
SEE WATER, INC.
Remote Monitoring Dry Contacts:
• Normally Open dry contacts for high oil, high level,
pump run, and pump fault. Rated 0-60V AC/DC
www.seewaterinc.com
951.487.8073 • 888.733.9283 • [email protected]
22220 Opportunity Way, Suite 101 • Riverside, CA 92518
Oil Smart® Duplex System
The Oil Smart® OSD3P system incorporates pump controls and alarm
sensors that differentiate between oil and water, allowing companies to
responsibly discharge the water without the risk of pumping oil. Installation
of the OSD3P keeps companies in compliance with Elevator Code
ASME A17.1 and State/Federal regulations while reducing the risk of adverse
publicity, nes, and expensive cleanup cost.
Model FLA Range
OSD3P-3021 (1.0-1.6 FLA)
OSD3P-3022 (1.6-2.5 FLA)
OSD3P-3023 (2.5-4.0 FLA)
OSD3P-3024 (4.0-6.3 FLA)
OSD3P-3025 (6.0-10.0 FLA)
OSD3P-3026 (9.0-14.0 FLA)
OSD3P-3027 (13.0-18.0 FLA)
OSD3P-3028 (17.0-23.0 FLA)
OSD3P-3029 (20.0-25.0 FLA)
OSD3P-3030 (24.0-32.0 FLA)
OSD3P-3031 (30.0-40.0 FLA)
OSD3P-3032 (37.0-50.0 FLA)
OSD3P-3033 (48.0-65.0 FLA)
Page 1-3 IM 804 REV. 02/20
Panel Installation:
1. Caution: To maintain the NEMA 4X rating, make
all wiring connections with seal tight cable grips or
conduit connections.
2. Run pump cable and Oil Smart® cables through
conduit. Make eld connections as shown on wiring
schematic.
3. Run power line conductor through conduit. Wire to
terminals per enclosed schematic.
4. Branch circuit protection to be provided by
installer.
5. Panel circuit breakers are closed.
6. Mount Oil Smart® pump switch and Liquid Smart®
alarm sensor with provided mounting hardware to
pump discharge pipe. The ‘OFF’ sensor of the Oil
Smart® pump switch shall be positioned at least 3”
above the impeller of the pump.
7. Mounting of the High Water Lag Sensor is
application driven and is to be placed where high
demand pump is to be activated.
8. Mounting of the Liquid Smart® sensor is
application driven and is to be placed where a high
liquid is deemed necessary. The Liquid Smart®
sensor is typically mounted 3” - 6” above the Oil
Smart® pump switch.
9. Connect service conductors 208/240/480V to
proper location
Enclosure Mounting: NEMA 4X RATED
Mounting Brackets - A mounting bracket and screw pack are provided
with the premium enclosures. To assemble, turn the enclosure upside down
on a at surface, place the mounting bracket over the square boss either
horizontally or vertically, and fasten the mounting bracket with the 1/4”-20
x 0.5 SS, countersunk phillips drive screws or vertically, with the mounting
brackets in any cong., using any acceptable fastening technique.
Covers/Doors - Covers/doors have a gasket pre-assembled to seal against
the base.
Note: The control panel should not be mounted in a location that may be
subject to submersion.
W
Your Trusted Source for Quality Control Panels.
®
SEE WATER, INC.
Sequence of Operation:
Typical Installation of Oil Smart® Duplex Control Panel
Oil Smart® Duplex Control Panel
Liquid Smart® Alarm Sensor
Oil Smart® Pump Switch
Submersible Pump #1
High Water Sensor
Submersible Pump #2
Normal Condition (Water Only)
When water comes in contact with the
short (on) sensor, the pump will turn
on. The pump will remain on until
water clears the long (off) sensor.
Oil Present Condition
If oil comes in contact with the (on)
sensor, the pump will not turn on.
Operation of Oil Smart®
Water (Oil Present Condition)
If the water level rises enough to
contact the (on) sensor under the
oil layer, the pump will turn on and
remain on until the (off) sensor clears
WATER
WATER
OIL
LAYER
WATER
OIL
LAYER
WATER
WATER
OIL
LAYER
WATER
OIL
LAYER
Operation of Liquid Smart®
High Water Level
When water comes in contact will both
sensors, the white water indicator on
the front panel will illuminate. This
condition will turn on the red beacon
alarm light and sound the alarm buzzer.
High Oil Level
If oil comes in contact with both sensors,
the yellow oil indicator on the front panel
will illuminate. This condition will turn on
the red beacon alarm light and sound the
alarm buzzer.
Three Phase Duplex Control Panel
Installation and Operation Manual
OSD3P-30XX
Testing:
Oil Smart® Pump Switch Testing:
• Place your thumb on the short stainless steel sensor
of the Oil Smart® pump switch, and the pump will
turn on. While touching the short ‘ON’ sensor, touch
the long ‘OFF’ sensor with your ngers; remove your
thumb from the short ‘ON’ sensor and begin to move
your ngers down the ‘OFF’ sensor simulating water
being pumped down. Once ngers are removed from
‘OFF’ sensor, the pump will turn off.
• Optional: Fill the sump area with ground water, when
water reaches the ‘ON’ sensor, the pump will turn on
and remain on until water clears the ‘OFF’ sensor.
Liquid Smart® Alarm Testing:
• Submerge both sensors in oil and the yellow oil
indicator on the front panel will illuminate. To test
water sensor, submerge both sensor in ground water
and the white water light will illuminate.
• Both test will illuminate the 360-degree visible beacon
and sound an 85 decibel at 10’ buzzer.
www.seewaterinc.com
951.487.8073 • 888.733.9283 • [email protected]
22220 Opportunity Way, Suite 101 • Riverside, CA 92518
Page 2-3 IM 804 REV. 02/20
SEE WATER, INC.
Troubleshooting:
Caution: Before checking electrical connections within the control or
attempting to replace any components, turn off all branch circuits supplying
power to the main control panel.
Pump control does not activate the pump or pump does not run
• Verify polarity is correct.
• Conrm all connections are tight and secure.
• White plastic case must be kept clean. Clean with house hold rubbing
alcohol and rag.
• Keep control 1” - 2” clear of any metallic material. Mount to PVC pipe
or if mounted to metal pipe, make sure to mount with See Water quick
mount PVC bracket.
Alarm will NOT activate
• Conrm separate 120VAC power to circuit board TS1-1 and TS1-2.
Power can be jumpered from incoming voltage if needed.
• Check for any visual damage to optic or stainless steel sensor on the
Liquid Smart® Sensor.
Preventive Maintenance
• The Oil Smart® Pump Switch and Liquid Smart® Sensor must be kept
clean. If the switches are submerged during install or maintenance,
clean the white plastic case with rubbing alcohol. Consistent inspection
and preventive maintenance ensures longevity and proper operation of
components.
Three Phase Duplex Control Panel
Installation and Operation Manual
OSD3P-30XX
Additional Panel Options:
24 - Pump Exerciser
• Auto cycles pumps daily, weekly or monthly.
Run Time Options:
• Position A: 50ms (DIP Switch 1,2, and 3)
• Position B: 100ms
• Position C: 4s
• Position D: 8s
28
3R
6P
AF
AH
C
CCD
DPR
ETD
LAD/
LAW
MD
PM
PX
SFD
ST
= Power On Dry Contact
= Painted Steel Enclosure
= Upgraded Enclosure (NEMA 6P Rated); Removes
Buzzer and Beacon
= Alarm Flasher
= Anti-Condensation Heater
= Additional Cord Length Greater Than 20’*
= Cycle Counter w/ LCD Display and Reset
= Dry Contact for Pump Run
= Elapsed Time Meter w/ LCD Display and Reset
= Lightning Secondary Surge Arrestor
= Main Disconnect
= Phase Monitoring
= Pump Portal® Wireless Remote Panel Control and
System Monitoring
= Seal Failure Circuit w/ Indicator Lights
= Upgraded Enclosure (Stainless Steel)
*Additional cord length greater than 20’. Specify after
C. Example: (OSD3P-3021-C50). Indicates 50’ cord
lengths for all components.
Warranty:
See Water, Inc. warrants that products of its manufacture are
free from defects in material and workmanship for a period of 5
years from the date of purchase. This date shall be determined
by the date on the invoice and the serial number on the product.
Replacement of the product is at the discretion of See Water,
Inc. This warranty is valid when the product is installed in
compliance with the manufacturer’s installation instructions.
The manufacturer’s obligation under this warranty shall be
limited to the repair or replacement of any parts found by
the manufacturer to be defective, provided that the product
is returned to See Water, Inc.’s factory, postage prepaid with
proof of original purchase included.
The manufacturer of this warranty shall not be liable under this
warranty if the product has not been properly installed; any
alterations/additions/changes to the product will result in a void
warranty. Failure to properly install and test this product can
result in personal injury or equipment malfunction.
See Water, Inc. shall not be liable for any loss, damage or
expenses from installation or use of its products.
www.seewaterinc.com
951.487.8073 • 888.733.9283 • [email protected]
22220 Opportunity Way, Suite 101 • Riverside, CA 92518
Page 3-3 IM 804 REV. 02/20

This manual suits for next models

13

Other See Water Control Panel manuals

See Water Oil Smart OSSIM-30 User manual

See Water

See Water Oil Smart OSSIM-30 User manual

See Water WD3P-4-302 Series User manual

See Water

See Water WD3P-4-302 Series User manual

See Water Oil Smart OSD1P-102 Series User manual

See Water

See Water Oil Smart OSD1P-102 Series User manual

See Water OSSIM-TP-100 Series User manual

See Water

See Water OSSIM-TP-100 Series User manual

See Water WS1P-TP-1001 User manual

See Water

See Water WS1P-TP-1001 User manual

See Water WS Series Setup guide

See Water

See Water WS Series Setup guide

See Water WS Series Setup guide

See Water

See Water WS Series Setup guide

See Water WS Series User manual

See Water

See Water WS Series User manual

See Water Oil Smart OSSIM-30 Setup guide

See Water

See Water Oil Smart OSSIM-30 Setup guide

See Water OSSIM-TP-30 Series User manual

See Water

See Water OSSIM-TP-30 Series User manual

Popular Control Panel manuals by other brands

Bluesound Professional CP100 owner's manual

Bluesound Professional

Bluesound Professional CP100 owner's manual

Jung Smart Panel 5.1 KNX operating instructions

Jung

Jung Smart Panel 5.1 KNX operating instructions

Watts Vision BT-CT02-RF manual

Watts

Watts Vision BT-CT02-RF manual

Cooper Controls Greengate CK4-120NO Installation sheet

Cooper Controls

Cooper Controls Greengate CK4-120NO Installation sheet

Setec DRIFTER owner's manual

Setec

Setec DRIFTER owner's manual

Simon XTi System manual

Simon

Simon XTi System manual

Eaton Cutler-Hammer PanelMate manual

Eaton

Eaton Cutler-Hammer PanelMate manual

Mitsubishi Electric GT10 General description

Mitsubishi Electric

Mitsubishi Electric GT10 General description

Metso LCP9H Series Installation maintenance and operating instructions

Metso

Metso LCP9H Series Installation maintenance and operating instructions

birddog PTZ KEYBOARD user manual

birddog

birddog PTZ KEYBOARD user manual

ABB ACSM1 Series user guide

ABB

ABB ACSM1 Series user guide

Sony BKDS-7080 Operation manual

Sony

Sony BKDS-7080 Operation manual

schmersal BDF100 operating instructions

schmersal

schmersal BDF100 operating instructions

HUBBELL LIGHTING CX Series installation instructions

HUBBELL LIGHTING

HUBBELL LIGHTING CX Series installation instructions

Beijer Electronics X2 control quick start guide

Beijer Electronics

Beijer Electronics X2 control quick start guide

Advantech UbiQ user manual

Advantech

Advantech UbiQ user manual

CAME ZT6 installation manual

CAME

CAME ZT6 installation manual

Superior Electric ELTERM 24 Installation and operating instructions

Superior Electric

Superior Electric ELTERM 24 Installation and operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.