MI00555-1-EN INSTALLATION MANUAL 3/4
Through the lateral connection, it is possible to add optional modules.
For more information on accessories and optional modules, visit the website on page 1 or scan the QR-CODE.
ENVIRONMENTAL
CONDITIONS
Operating temperature:
from -25°C to +65 °C
Humidity: 10% ÷ 90% non condensing.
Storage temperature: from -30°C to +80°C
Protection rating: IP20
ASSEMBLY 35mm DIN rail IEC EN60715
CONNECTIONS Removable 3.5mm pitch terminal block, 1.5mm2 max cable section
COMMUNICATION
PORTS
1 USB A connector
4 RJ45 Ethernet ports
1 RS485/RS232 serial port congurable via software
1 RS485 serial port
1 micro USB dedicated to debugging
POWER SUPPLY 10 ÷ 40Vdc; 19 ÷ 28Vac; 8W max
INSULATION
DIGITAL OUTPUTS OptoMOS® 30Vdc, 25mA max
DIGITAL
INPUTS
Number of channels: 4, Absorbed current: 2.2mA
Input voltage: 0÷30V, Threshold ON > 9V, Threshold OFF < 8V
IEC6113-2 Type 1 & 3 compliant
ANALOGUE
INPUTS
Voltage 0 ÷ 30Vdc, impedance 20kΩ
Current 0 ÷ 25mA, impedance ~ 50Ω
AUXILIARY
VOLTAGE
OUTPUT 12Vdc; Max. 50mA
WI-FI
(only R-PASS-W) Integrated WiFi 802.11 b/g/n, 2.4 ÷ 2.4835GHz band, max Output Power: 17dBm (50mW)
ELECTRICAL CONNECTIONS
POWER SUPPLY ANALOG INPUT
VOLTAGE
ANALOG INPUT
CURRENT
mA
mA
55 - AI2
53 - GND
54 - AI1
DIGITAL INPUT DIGITAL OUTPUT
PNP
DIGITAL OUTPUT
NPN
40 - CI
41 - DI1
42 - DI2
43 - DI3
44 - DI4
12÷24Vdc
49 - DO4
48 - DO3
47 - DO2
46 - DO1
45 - CO
12÷24Vdc
LOAD
LOAD
LOAD
LOAD 49 - DO4
48 - DO3
47 - DO2
46 - DO1
45 - CO
12÷24Vdc
LOAD
LOAD
LOAD
LOAD
23 -
25 -
24 -
+
+
55 - AI2
53 - GND
54 - AI1
The upper power supply limits must not be exceeded, as this could cause serious damage to the module.
Switch the module off before connecting inputs and outputs.
To meet the electromagnetic immunity requirements:
- use shielded signal cables;
- connect the shield to a preferential instrumentation earth system;
- separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc...).
CAUTION