MI00580-1-EN INSTALLATION MANUAL 3/4
FACTORY IP ADDRESS
The default module IP address is static: 192.168.90.101
WEB SERVER
To access the maintenance Web Server with 192.168.90.101 factory IP address:
Default user: admin, Default password: admin, http://192.168.90.101
The device may only be powered by a power supply unit with a limited energy electric circuit max.
40Vdc / 28Vac Max output in accordance with CAN/CSA-C22.2 No. 61010-1-12 / UL Std. No. 61010-1 (3rd Edi-
tion) chapter 6.3.1/6.3.2 and 9.4 or class 2 according to CSA 223/UL 1310.
ATTENTION
CONNECTIONS
3-way removable screw terminals, pitch 5 mm
Rear connector IDC10 for DIN bar 46277
RJ45 front connector
COMMUNICATION
PORTS
RS232 or RS485 switchable on terminal 10 - 11 - 12 (serial port 2)
Maximum Baud rate 115 k, maximum cable length RS232 < 3m
RS485 IDC10 rear connector: Maximum Baud rate 115 k. (serial port 1)
RJ45 front Ethernet connector: 100 Mbit/s, maximum distance 100 m
CONFIGURATION
Conguration and FW update via webserver;
Via DIP - SWITCH
Via EASY SETUP 2 conguration software
SETTING THE DIP-SWITCHES
RS232/RS485 SETTING: RS232 or RS485 conguration on terminals 10-11-12 (serial port 2)
SW2
1 ON RS232 ACTIVATION
0 OFF RS485 ACTIVATION
KEY
1 ON
0 OFF
SW2 DIP-SWITCH:
Through DIP-SWITCH-SW1 it is possible to set the IP conguration of the device:
DESCRIPTION DIP 1 DIP 2
To obtain the conguration from the Flash memory, both SW1
DIP switch selectors must be set to OFF
To reset the device to factory settings both SW1 DIP switches
must be set to ON
To force the device’s IP address to the standard value of
SENECA Ethernet products: 192.168.90.101
Reserved
IDC10 CONNECTOR
RS485GND
RS485A
RS485B
Power Supply AC / +
Power Supply AC / -
IDC 10
1
The illustration shows the meanings of the various IDC10
connector pins if signals are to be sent via them directly.
The DIP-switch settings are read only at boot time. At each change, perform a restart.
WARNING