Siemens PL 50 User manual

PL 50/100
Smart Communication, PL 50/100 Product Information
C53000-X6040-C604-1 Edition Sept. 2021 1
ENGLISH
Read and understand these instructions and the relevant manual before installing,
operating, or maintaining the device. For available software and complete documentation for
PowerLink 50/100 see:
Siemens Industry Online Information platform SIOS
Further Support
If special problems arise, or further information are required, please contact your Siemens
representative. Our Customer Support Center provides a 24-hour service.
Siemens AG
Smart Infrastructure – Digital Grid
Customer Support Center
● Phone: +49 911 2155 4466
● E-Mail: energy.aut[email protected]om
Disclaimer of Liability
Although we have carefully checked the contents of this publication for conformity with the
hardware and software described, we cannot guarantee complete conformity since errors
cannot be excluded.
The information provided in this manual is checked at regular intervals and any corrections
that might become necessary are included in the next releases. Any suggestions for
improvement are welcome.
Copyright
Copyright © Siemens AG 2021 – All Rights Reserved
The reproduction, transmission or use of this document or its contents is not permitted
without express written authority. Offenders will be liable for damages. All rights, including
rights created by patent grant or registration of a utility model or design, are reserved.
OpenSSL
This product includes software developed by the OpenSSL Project for use in OpenSSL
Toolkit (http://www.openssl.org/).
This product includes software written by Tim Hudson (tjh@cryptsoft.com).
This product includes cryptographic software written by Eric Young (ea[email protected]).
Notes on Safety
This document contains notes that must be adhered to ensure personal safety and to avoid
damage to property during commissioning and use.
However, it does not constitute a complete description of all safety measures required for
installation, service, and maintenance of the device. Details are to be taken from the device
manual; those are mandatory. Keep it safe for later usage.
Warning: Danger of severe personal injury or substantial damage to property
Hazardous voltages may occur in devices and modules during operation. Always
observe the
instructions given in “Qualified Electrical Engineering Personnel” below.
Qualified Electrical Engineering Personnel
Qualified electrical engineering personnel must have up to date technical qualifications
as electrical technicians. Only these persons
may commission, use, maintain,
decommission
, and dispose of the device according to the state-of-the-art
standards of
engineering
in the high voltage power line environment.
Warning:
Laser radiation! Danger of eye injury
This device may contain a
class 1 laser. Do not look directly into the beam.
Warning:
Danger of damage due to static electrical charges
The printed circuit boards of numerical relays contain CMOS circuits. These shall not
be withdrawn or inserted under live conditions! The modu
les must be so handled that
any possibility of damage due to static electrical charges is excluded.
During any necessary handling of individual
modules, the recommendations relating to
the handling of electrostatically endangered components (EEC) must be ob
served.
In installed conditions, the modules are in no danger.
Use as Prescribed
The device may only be used for such applications as set out in the user instructions, and
only in combination with equipment recommended and approved by Siemens.
Correct and safe operation of the product requires adequate transportation, storage,
installation and mounting in a control cabinet, as well as appropriate use and maintenance.
Only qualified electrical engineering personnel may install, set up, commission, attach
communication cables, power supply lines and ground to the device.
Check and follow the electrical operating conditions, mechanics and climatic max. ambient
conditions for safe operation. Connect and operate the device only in conformance with the
values as specified in the ‘Technical Data’ below.
Commissioning must be carried out in accordance with good engineering practice and
under consideration of local installation rules and laws (also applicable and obligatory for
cabinet internal wiring).
Fuses may be required on all phases in the electrical installation, depending on local
installation conditions and requirements.
During operation of the equipment, it is unavoidable that certain parts will carry dangerous
voltages. Severe injury or damage to property can occur if the appropriate measures during
use are not taken:
•Make sure, that the equipment is properly connected to ground at all times and
mechanically fixed in the rack.
•Degree of protection by enclosure IP20.
•Device may only be operated in a dry location within a temperature range of
-5 to +55 degree Celsius.
•This is a Class A device. It is intended to be operated in an industrial environment only. It
may cause harmful interference if operated in residential/light industry environment.
•Hazardous voltages can be present on all components when the device is connected to a
power source. Before opening the device, makes sure all power sources are
disconnected or switched off. Even after the power supply has been disconnected,
hazardous voltages can still be present within the device (capacitor storage).
•The limit values indicated in the manual must not be exceeded; that also applies to
testing and commissioning.
Statement of Conformity
The product is in conformity with the regulations of the fol
lowing European Directives:
•EMC Directive 2014/30/EU
•Low Voltage Directive 2014/35/EU
•
RoHS Directive 2011/65/EU
Used Symbols
Caution, hazard. The documentation
must be observed.
Protection class I / protective
earthing
CE conformity
Hazardous voltage
Qualified Electrical Engineering
Personnel
Note
Distributor statement according to WEEE-Guideline 2012/19/EU
Do not throw the device in the household trash! Please dispose of the device
according to the guidelines regarding electronic waste in your country.
Application
PowerLink 50/100
The PowerLink system permits carrier frequency transmission of speech, data, telecontrol,
and teleprotection signals via high voltage overhead power lines and cables.
Unpacking a Device
•Check the package for external transport damage. A damaged packing may indicate that
the device inside is also damaged.
•Unpack the device carefully; do not use force.
•Visually check the device to ensure that it is in perfect mechanical condition.
•Return a damaged device to the manufacturer or dispose it correctly. A defect device
may not either be used or repaired by the user.
Note:
Before commissioning the device, leave it in the final operation room for at least
2
hours. This allows it to reach room temperature and to prevent dampness and
condensation.
Repacking a Device
•If you store devices after incoming inspection, pack them in suitable storage packaging.
•If devices are to be transported, pack them in transport packing.
•Put the accessories supplied in the packing with the device.
Storing a Device
•Only store devices on which you have carried out an incoming inspection, thus ensuring
that the warranty remains valid.
•The relative humidity must be at a level where condense water and ice are prevented
from forming.
•If the device has been in storage for more than 2 years, connect it to the primary voltage
source, and operate it for 1 to 2 days. This will cause the electrolytic capacitors to form on
the printed circuit board assemblies again.
•When the device is reshipped ensure that the transport requirements for the selected
means of transport are met. The outer package alone is not adequate for transport
purposes.
Mounting
The device is designed for horizontal mounting in a cabinet or rack. Min. distance between
two PL 50/100 devices is one unit of height (= 1.75 inches or 44.45 mm). The climatic
conditions must be within the specified values (see technical data). Consider the weight and
position of the device to avoid personal injuries.
Commissioning
Before making any connections, ground the equipment and the grounding
terminal.
•After switching on the external supply voltage and with the device switched off (switch
S1 enable/disable
•Power Supply on CSPi in down position) LED "i" (red) lights up on the PSPA2 power
supply unit(s). The yellow LED (disabled) lights up on the power supply units.
•After switching on the device (switch S1 enable/disable Power Supply on CSPi, located
behind the front cover, in upper position) the OK LED (green) must light up on the
power supply unit and on the CSPi module.
•The RX-AL LED must light up green if the device is connected to the transmission line,
receiving properly from the remote station and receive levels are set correctly.
Correction of the receive level is only possible with the PowerSys service program.
PL 50/100
Smart Communication, PL 50/100 Product Information
C53000-X6040-C604-1 Edition Sept. 2021 2
•Connecting the Service PC
A service PC and the service program PowerSys are needed for startup, maintenance,
and diagnostic purpose of the PL 50/100 units. The service PC is connected to the
ETH socket (Default IP address 192.168.20.5) on the front panel of the CSPI module
with a RJ45 plug cable.
•The service program PowerSys and the communication to the device via the serial
interface from the service PC or via a TCP/IP connection is described in the device
manual.
•The corresponding software package (formerly delivered on
DVD) is available for download on SIOS (Siemens Industry
Online Support) platform free of charge, a registration is
required.
Product Support/Energy/Energy automation and smart
grid/Smart communication/Download
•Test protocols are available for download under
https://www.ea-testreports.siemens.com
Enter BF code of device to view the requested test protocol
in pdf format. The installed software package version
loaded into the device can be seen in the protocol.
Module slot position PL 100
1) CFS-2 part
2) Integrated SWT3000-2
3) Integrated SWT3000-1
Module slot position PL 50
1) IFC-2 or EN100
Functions/Features
Feature
Digital
PLC
system
Analog
PLC
system
Universally applicable in analog, digital, or mixed operation X X
Carrier frequency range 24 kHz to 1000 kHz
X
X
Bandwidth selectable 2 kHz to 32 kHz
X
X
Data rate up to 320 Kbps @ 32 kHz X
X
Transmission power
20 W / 50 W / 100 W, fine adjustment through software
X
X
Operation with or without frequency band spacing with
automatic cross talk canceller
X X
Digital interface
Synchronous X.21 (max. 2 channels)
Asynchronous RS 232 (max. 8 channels)
TCP/IP (2 x electrical, 1 x optical)
E1 (2 Mbps) for voice compression
G703.1 (64 kbps)
1)
X
X
X
X
X
Analog interface
VF (VFM, VFO, VFS), max. 8 channels for voice, data, and
protection signal 2)
Asynchronous RS232 (max. 4) via FSK
X
X
X
Miscellaneous
Adaptive dynamic data rate adjustment
X
TCP/IP Layer 2 Bridge
X
Integrated versatile multiplexer for voice and data
Max. 5 compressed voice channels via VF interface 3)
Max. 8 voice channels via E1 interface
StationLink bus for the cross-connection of max. 4 PLC
transmission routes (compressed voice and data without voice
compression on repeater)
Reverse FSK analog RTU/modem data via dPLC (2 x)
X
X
X
X
X
Protection signal transmission system SWT 3000
Integration of 2 devices in PowerLink 100 and 1 in PowerLink 50
Remote operation via cable or fiber-optic cable1) identical to the
integrated version
Single purpose or multi purpose/alternate multi purpose mode
X
X
X
X
X
X
Element manager, based on a graphical user interface for the
control and monitoring of PLCand teleprotection systems
X
X
Command interface binary and in accordance with IEC 61850 X X
Remote access to PowerLink
Via TCP/IP connection
Via in-band service channel
X
X
X
X
SNMP compatibility for integrating NMS
X
X
Event memory with time stamp
X
X
Simple feature upgrade through software
X
X
1) Not applicable in PowerLink 50
2) Max. 7 VF channels for PowerLink 50
3) 4 compressed voice channels via VF for PowerLink 50
Technical Data
Power Supply
Input voltage
PSPA2-AC
DC 38 V to DC 72 V
PSPA2-DC
AC 93 V to AC 264 V (47 Hz to 63 Hz)
DC 85 V to DC 264 V
Power consumption PL 100
50 W Amplifier (AC/DC) Normal operation: 250 VA/140 W
Max *): 340 VA/200 W
100 W Amplifier (AC/DC)
Normal operation: 390 VA/250 W
Max *): 520 VA/360 W
Power consumption PL 50
50 W Amplifier (AC/DC) Normal operation: 250 VA/140 W
Max *): 320 VA/180 W
*) Single tone operation
Climatic Conditions IEC 60721-3
During operation
-5° C to + 55° C
During storage and transport
-40° C to +70° C
Relative humidity
5 % to 95 %
Absolute humidity
29 g/m3 no condensation
Mechanical Design PL 100
19” frame
Dimensions
482 mm x 578 mm x 270 mm (W x H x D)
Weight with 50-W amplifier 21 kg
with 100-W amplifier 26 kg
Degree of protection
IP20
Mechanical Design PL 50
19” frame
Dimensions
482 mm x 266 mm x 270 mm (W x H x D)
Weight
18 kg
Degree of protection
IP20

This manual suits for next models

1

Other Siemens Circuit Breaker manuals

Siemens SION User manual

Siemens

Siemens SION User manual

Siemens 3VA51 ED1 Series User manual

Siemens

Siemens 3VA51 ED1 Series User manual

Siemens 3VA2 JP Series User manual

Siemens

Siemens 3VA2 JP Series User manual

Siemens Sentron 3VA9157-0PK1 Series User manual

Siemens

Siemens Sentron 3VA9157-0PK1 Series User manual

Siemens 3VT9300-8CB30 User manual

Siemens

Siemens 3VT9300-8CB30 User manual

Siemens Sentron 3VA91 8-0VF30 Series User manual

Siemens

Siemens Sentron 3VA91 8-0VF30 Series User manual

Siemens 3AH37 User manual

Siemens

Siemens 3AH37 User manual

Siemens N250X User manual

Siemens

Siemens N250X User manual

Siemens 3AH47 series User manual

Siemens

Siemens 3AH47 series User manual

Siemens QR2 User manual

Siemens

Siemens QR2 User manual

Siemens MP120DFP User manual

Siemens

Siemens MP120DFP User manual

Siemens 3VL9431-6 30 Series User manual

Siemens

Siemens 3VL9431-6 30 Series User manual

Siemens 3VA25-JP Series User manual

Siemens

Siemens 3VA25-JP Series User manual

Siemens MBKJD1A User manual

Siemens

Siemens MBKJD1A User manual

Siemens 3WL10 Series User manual

Siemens

Siemens 3WL10 Series User manual

Siemens 3VT9524-4TG30 User manual

Siemens

Siemens 3VT9524-4TG30 User manual

Siemens 3VT9500-3MF20 User manual

Siemens

Siemens 3VT9500-3MF20 User manual

Siemens 3VA11-E Series User manual

Siemens

Siemens 3VA11-E Series User manual

Siemens 3WX3653-1J 00 Series User manual

Siemens

Siemens 3WX3653-1J 00 Series User manual

Siemens SIRIUS 3RV1742 User manual

Siemens

Siemens SIRIUS 3RV1742 User manual

Siemens 8DJH Manual

Siemens

Siemens 8DJH Manual

Siemens SENTRON 3WL User manual

Siemens

Siemens SENTRON 3WL User manual

Siemens 3RV1.2 User manual

Siemens

Siemens 3RV1.2 User manual

Siemens 3WX3653-1JB00 User manual

Siemens

Siemens 3WX3653-1JB00 User manual

Popular Circuit Breaker manuals by other brands

GE Magne-Blast AM-13.8-1000-3H instructions

GE

GE Magne-Blast AM-13.8-1000-3H instructions

Circutor RECmax Lpd instruction manual

Circutor

Circutor RECmax Lpd instruction manual

GE AM-13.8-500-7 INSTRUCTIONS AND RECOMMENDED PARTS FOR MAINTENANCE

GE

GE AM-13.8-500-7 INSTRUCTIONS AND RECOMMENDED PARTS FOR MAINTENANCE

Eaton XNH1-A Series Instruction leaflet

Eaton

Eaton XNH1-A Series Instruction leaflet

ABB Infinity S quick start guide

ABB

ABB Infinity S quick start guide

Projoy Electric PEBS-S Instructions for installation and operation

Projoy Electric

Projoy Electric PEBS-S Instructions for installation and operation

GE MicroVersaTrip AKR-75 Maintenance manual

GE

GE MicroVersaTrip AKR-75 Maintenance manual

ABB VBF Series Instruction for Installation, Service and Maintenance

ABB

ABB VBF Series Instruction for Installation, Service and Maintenance

Allen-Bradley 140U Instruction leaflet

Allen-Bradley

Allen-Bradley 140U Instruction leaflet

Secheron UR46-81S instruction manual

Secheron

Secheron UR46-81S instruction manual

Gewiss 90 RESTART AUTOTEST 2P PRO manual

Gewiss

Gewiss 90 RESTART AUTOTEST 2P PRO manual

Allen-Bradley 140G Series manual

Allen-Bradley

Allen-Bradley 140G Series manual

Eaton IZM Series Installation and Removal Instructions

Eaton

Eaton IZM Series Installation and Removal Instructions

GE AM-13.8-750-5 INSTRUCTIONS AND RECOMMENDED PARTS FOR MAINTENANCE

GE

GE AM-13.8-750-5 INSTRUCTIONS AND RECOMMENDED PARTS FOR MAINTENANCE

Eaton Magnum Air MWN-408 user manual

Eaton

Eaton Magnum Air MWN-408 user manual

NATIONAL SWITCHGEAR HFC21B instructions

NATIONAL SWITCHGEAR

NATIONAL SWITCHGEAR HFC21B instructions

Scame ISOLATORS-EX 20A manual

Scame

Scame ISOLATORS-EX 20A manual

ABB eVD4 Installation and service instructions

ABB

ABB eVD4 Installation and service instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.