
Maintenance
4.
Rotate the racking screw to the
TEST
position (approxi-
mately 3 turns) to clear the spring discharge interlock. This
is
necessary before the closing springs
can
be charged,
and
also makes removal
of
the arc chutes easier.
5.
Remove arc chutes and examine arc chutes and circuit
breaker contacts for burned, cracked, or broken parts.
To remove arc chutes, proceed
as
follows:
a.
Remove mounting screws for holding clips, remove
support
and
phase barriers.
b.
Liftarc chutes vertically
to
clear arc runners.
6.
Inspect arc chutes for excessively burned arcing plates.
Replace arc chutes under the following conditions:
a.
Copper-plated steel plates
in
the arc chutes measure
less
than 0.06" thickness for
RL-800
through
RLE-2000
circuit breakers.
b.
Copper-plated steel plates
in
the arc chutes measure
less
than
0.08" thickness for
RL-3200
through
RL-5000
circuit breakers.
7. Wipe the contacts
with
a clean cloth saturated
with
a non-
toxic cleaning fluid, such
as
denatured alcohol.
8.
Replace badly burned
or
pitted contacts. (See 'Contact
Replacement', Page 15,
and
'Lubrication Chart', Table
5.)
Do not lubricate faces of contacts.
9.
Clean any accumulation
of
dust
or dirt
from
the circuit
breaker.
For
insulating parts, use a clean cloth saturated
with a non-toxic cleaner, such
as
denatured alcohol.
10.
Bearing pins
and
other sliding or rotating surfaces should
be cleaned and then coated
with
a light film
of
grease.
(See
'Lubrication Chart', Table
5.)
11. Perform a maintenance closing operation (see Page 14
and
Table
4)
to
check latch and linkage movement. (Be
sure
to
rotate the racking screw
to
the
TEST
position to
clear the spring discharge interlock before attempting
to
charge closing springs).
12. Check circuit breaker adjustments. (See 'Adjustments
Page 14.)
13.
Exercise
the circuit
breaker
through
several
close-open
cycles.
For
electrically operated circuit breakers, operate the circuit
breaker electrically. (Refer to the specific wiring information
for your circuit breaker
to
determine where control voltage
signals should be applied. Usually, spring charging power
is
connected between secondary disconnects
SD12
and
SD16,
closing control power between SD13
and
SD16,
and
tripping
power between
SD11
and
SD15. Secondary disconnects
are arranged with
SD1
on
top,
and
SD16
on
the bottom).
Examine the operation of the circuit breaker during these
operations for
any
evidence ofdifficulty, erratic operation, etc.
14. Test the tripping system, using
an
appropriate
test
set,
such
as
the Siemens Portable Static Trip Set, model
PTS-
4. Refer
to
'Static Trip Ill Information and Instruction
Guide', SG-3118, and 'Portable Test Set Instructions',
SG-
3138, for information on testing. The test should include
tripping ofthe circuit breaker by the trip device. This confirms
the functionality of the system, including
the
trip device
and
the tripping components.
15. Reinstall arc chutes. Close and open the circuit breaker
to
ensure that
the
arc chutes do not interfere
with
circuit
breaker operation.
16.
A megger test should be made
on
the high voltage circuit
to
be sure
that
all
connections
are free
of
undesired
grounds. A meggertest
is
also
advisable
on
the control circuit.
17. A dielectric test, if possible, should be made
on
the high
voltage (power) circuit for one minute at
the
appropriate
test
voltage. (Voltage transformers, control
power
trans-
formers, surge arresters, and surge capacitors
must
be
disconnected during this test).
Note: Do not perform dielectric tests on the Static Trip Ill
tripping system. Refer
to
'Static Trip Ill Information and
Instruction Guide', SG-3118.
Rated voltage
of
circuit Test voltage
480 or 600 volts 75%
of2200=1650VAC
208 or 240 volts 75%
of
1500 = 1125
VAC
Secondary & control circuits 75%
of
1500 = 1125
VAC
Note: Certain control devices. such
as
motors
and
motor
circuits, should be tested at 675
VAC.
Electronic devices
should be tested at the voltages specified
in
the instruction
manual for the electronic device).
Dielectric tests are also recommended
when
new
units
are added
to
an
existing installation, or after major field
modifications. The equipment should be put in good condi-
tion prior
to
the field test. It
is
not expected that equip-
ment shall be subjected
to
these tests after it
has
been
stored for long periods of time or
has
accumulat!'ld a large
amount
of
dust, moisture, or other contaminants without
being first restored
to
good condition.
.A.CAUTION
Excessive
test
voltages may result in damage
to
equipment.
Do
not
perform dielectric
tests
at
test
voltages
exceeding the ratings ofthe tested equipment.
18. Turn the racking screw
to
the DISCONNECT position,
and
reinstall the circuit breaker
in
the cubicle.
19. Log the details
of
the maintenance into a suitable record
of circuit breaker maintenance for future use.
13
Courtesy of NationalSwitchgear.com