Hazardous voltage.
Will cause death or
severe injury.
Turn off and lock out all power
supplyingthisdevicebefore
removingcover(s)or device and
whilecover(s)are removed.
Replaceall covers and shields
beforepowersupplying this device
is turned on.
Page 5 of 5
Pc. No.761411A03
© Siemens Energy & Automation, Inc. 1989
Siemens Energy & Automation, Inc.
Bellefontaine, OH 43311 U.S.A.
Installation Instructions
RESIDUAL SETTING (OUTGOING CIRCUIT
METHOD)– This is the standard position to which
the breaker is set when shipped from the factory.
With the switch in this position the circuit breaker
may be usedon 3 phase 3wire or,with the addition
of an external neutral sensing transformer, on 3
phase 4 wire systems. See Neutral SensingTrans-
former section for moreinformation.
GROUNDRETURNSETTING(GROUNDRETURN
METHOD) –This setting may only be used for ser-
vice disconnects or separately derived systems.
With the switch in this position, the circuit breaker
may be used on 3 phase 3 wire and 3 phase 4 wire
systems. Anexternal sensingtransformer, which is
installed on the main bonding jumper, is required
for this method. See Neutral SensingTransformer
sectionfor moreinformation.
Neutral SensingTransformer
Anexternaltransformer isrequired forcircuit break-
ers equipped with ground fault protection when op-
erating in the RESIDUAL mode on 3 phase 4 wire
systems and when operating in the GROUND RE-
TURN mode on any system. The sensors listed
belowmustbeused fortheseapplications. The sen-
sor catalog number must be matched to the circuit
breakerMaximum ContinuousCurrent rating(ln) as
shown in the table. Please note that sensors used
with other breaker types cannot be used with the
SJD/SLD circuit breakers. Installation instructions
are included with the sensors.
Transformer Circuit Transformer
Catalog No. BreakerRating __Color__
N02SJD 200Amps GREEN
N03SJD 300Amps GREEN
N04SJD 400Amps GREEN
N05SLD 500Amps GREEN
N06SLD 600Amps GREEN
ElectronicTesting
Sensitrip III solid state molded case circuit break-
ers may be tested for electronic functionality by the
useofaTS-31test setavailablefromlocal Siemens
salesoffices.
NOTE: Time current characteristic curves and in-
formation on factory installed accessories can be
obtained from local Siemens sales offices.
Maintenance
JD and LD frame circuit breakers are designed to
provideyearsof maintenance freeservice. Experi-
encehasshown that properlyapplied molded case
circuit breakers normally do not require mainte-
nance. However,some industrialusersmaychoose
to establish an inspection and maintenance proce-
dure to be carried out on a regular basis. For de-
tailed information, consult applicable NEMA publi-
cation or your local Siemens sales office.
NOTE: Do not spray or allow any petroleum based
chemicals,solvents or paintsto contact themolded
parts or nameplates.
This product is covered by one or more of the following patents: 4,631,525; 4,513,267; 4,484,164.